| Plan Review Stops For Permit 15070442 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2015-09-21 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-09-21 |
Time |
16:18 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-09-18 |
Time |
12:05 |
Sent To |
I |
|
| Notes |
| 2015-09-21 16:18:41 | PER A TELEPHONE CONVERSATION THIS MORNING WITH BYRON | | | WALKER OF TYCO INTEGRATED, THE SMOKE DETECTOR PLACEMENT | | | HAS BEEN VERIFIED TO BE WITHING THE CODE REQUIRED | | | PARAMETERS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2015-09-02 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-09-02 |
Time |
09:56 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-09-02 |
Time |
12:04 |
Sent To |
I |
|
| Notes |
| 2015-09-02 10:15:24 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE | | | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. | | | | | | 1. YOU SHALL SUBMIT A DATA SHEET FOR THE UNIMODE 600 | | | ANN. ( I TRIED TO GET THIS FOR YOU BUT WAS UNABLE TO) | | | 2. SMOKE DETECTOR IN MANAGER'S APARTMENT LIVING ROOM | | | SHALL BE RELOCATED CLOSER TO THE BEDROOM, MAKE SURE TO | | | STAY 3' FROM BATHROOM DOOR AND 10' FROM RANGE. | | | 3. LEVEL 2, UNIT 1 BEDROOM 2 MISSING S/D OUTSIDE OF | | | DOOR. WHAT IS THAT WIC EXITING TO CORRIDOR? IF EXIT TO | | | CORRIDOR WILL NEED A S/D AS WELL. | | | 4. LEVEL 2, UNIT 3 BEDROOM 2 MISSING S/D AS WELL. | | | 5. LEVELS 3 THROUGH LEVEL 7 ARE MISSING THE HEAT | | | DETECTOR UNIT FROM THE LEGEND AS WELL AS THE TYPICAL | | | MISSING S/D AS INDICATED ABOVE. | | | 6. LEVEL 8 UNITS 1 & UNIT 2 MISSING S/D FOR BEDROOM 2. | | | 7. MAY HAVE TO ADJUST LIVING ROOM S/D WITH RELATION TO | | | THE BEDROOM DOOR. | | | 8. RISER AND CALCULATIONS MAY VARY DEPENDING ON HOW THE | | | ABOVE CORRECTIONS ARE ADDRESSED. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2015-07-15 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-07-15 |
Time |
17:49 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-07-15 |
Time |
15:24 |
Sent To |
I |
|
| Notes |
| 2015-07-15 17:49:50 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE | | | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. | | | 1. THE FIRST FLOOR BEDROOM ON THE EAST END IS MISSING | | | THE NOTIFICATION APPLIANCE. | | | 2. THAT SAME BEDROOM IS MISSING THE SMOKE DETECTOR | | | REQUIRED ON THE OUTSIDE OF THE ROOM. | | | 3. ELEVATOR LOBBY MISSING RECALL DETECTOR. | | | 4. THE N.E. PARKING AREA MISSING NOTIFICATION | | | APPLIANCE. | | | 5. TYPICAL TO FLRS. 2 ? 6 & 8: | | | A) MISSING SMOKE DETECTOR IN ELEVATOR LOBBIES. | | | B) SMOKE DETECTORS SHALL NOT BE INSTALLED WITHIN A | | | RADIUS OF 10? FROM A COOKING APPLIANCE UNLESS | | | SPECIFICALLY LISTED FOR THE PURPOSE. | | | 6. FLOOR PLAN FOR LEVEL 7 VARIES FROM THE REST; ROOMS | | | SHALL BE LABELED FOR IDENTIFICATION. | | | 7. FLOOR 9 VARIES AS WELL, ALL ROOMS SHALL BE | | | IDENTIFIED. | | | 8. BECAUSE THE DEVICE COUNT WILL VARY, THE RISER AND | | | CALCS SHALL BE REVISED ACCORDINGLY. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2015-09-15 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2015-09-15 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2015-09-15 |
Time |
10:17 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2015-08-27 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2015-08-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2015-08-27 |
Time |
09:11 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2015-07-13 |
|
|
Cont ID |
|
| Sent By |
Lindow |
Date |
2015-07-13 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
2015-07-13 |
Time |
|
Sent To |
E |
|
| Notes |
| 2015-07-13 14:47:11 | SUBJECT TO FIELD INSPECTION. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2015-09-21 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-09-21 |
Time |
16:21 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-09-11 |
Time |
10:14 |
Sent To |
|
|
| Notes |
| 2015-09-21 16:21:11 | 9/21/15 - PASSED ELECTRICAL W/PROVISO. CONTRACTOR | | | NOTIFIED VIA EMAIL. SENT TO SMALL READY BIN "T". MA | | 2015-09-14 10:14:44 | ROUTED TO FIRE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2015-09-02 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-09-02 |
Time |
10:16 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-08-25 |
Time |
16:14 |
Sent To |
|
|
| Notes |
| 2015-09-02 10:17:22 | 9/2/15 - FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR | | | NOTIFIED VIA EMAIL. SENT TO SMALL DENIED BIN "T". MA | | 2015-08-25 16:14:28 | RESUB ROUTED TO FIRE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-07-15 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-07-15 |
Time |
17:50 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-07-10 |
Time |
18:59 |
Sent To |
|
|
| Notes |
| 2015-07-15 17:53:16 | 7/15/15 - FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR | | | NOTIFIED VIA EMAIL. SENT TO SMALL DENIED BIN "T". MA | | 2015-07-10 19:00:17 | IN FIRE BOX |
|
|