Plan Review Details - Permit 15070442
Plan Review Stops For Permit 15070442
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-09-21 Cont ID  
Sent By albarran Date 2015-09-21 Time 16:18 Rev Time 0.00
Received By albarran Date 2015-09-18 Time 12:05 Sent To I
Notes
2015-09-21 16:18:41PER A TELEPHONE CONVERSATION THIS MORNING WITH BYRON
 WALKER OF TYCO INTEGRATED, THE SMOKE DETECTOR PLACEMENT
 HAS BEEN VERIFIED TO BE WITHING THE CODE REQUIRED
 PARAMETERS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-09-02 Cont ID  
Sent By albarran Date 2015-09-02 Time 09:56 Rev Time 0.00
Received By albarran Date 2015-09-02 Time 12:04 Sent To I
Notes
2015-09-02 10:15:24PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 1. YOU SHALL SUBMIT A DATA SHEET FOR THE UNIMODE 600
 ANN. ( I TRIED TO GET THIS FOR YOU BUT WAS UNABLE TO)
 2. SMOKE DETECTOR IN MANAGER'S APARTMENT LIVING ROOM
 SHALL BE RELOCATED CLOSER TO THE BEDROOM, MAKE SURE TO
 STAY 3' FROM BATHROOM DOOR AND 10' FROM RANGE.
 3. LEVEL 2, UNIT 1 BEDROOM 2 MISSING S/D OUTSIDE OF
 DOOR. WHAT IS THAT WIC EXITING TO CORRIDOR? IF EXIT TO
 CORRIDOR WILL NEED A S/D AS WELL.
 4. LEVEL 2, UNIT 3 BEDROOM 2 MISSING S/D AS WELL.
 5. LEVELS 3 THROUGH LEVEL 7 ARE MISSING THE HEAT
 DETECTOR UNIT FROM THE LEGEND AS WELL AS THE TYPICAL
 MISSING S/D AS INDICATED ABOVE.
 6. LEVEL 8 UNITS 1 & UNIT 2 MISSING S/D FOR BEDROOM 2.
 7. MAY HAVE TO ADJUST LIVING ROOM S/D WITH RELATION TO
 THE BEDROOM DOOR.
 8. RISER AND CALCULATIONS MAY VARY DEPENDING ON HOW THE
 ABOVE CORRECTIONS ARE ADDRESSED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-07-15 Cont ID  
Sent By albarran Date 2015-07-15 Time 17:49 Rev Time 0.00
Received By albarran Date 2015-07-15 Time 15:24 Sent To I
Notes
2015-07-15 17:49:50PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. THE FIRST FLOOR BEDROOM ON THE EAST END IS MISSING
 THE NOTIFICATION APPLIANCE.
 2. THAT SAME BEDROOM IS MISSING THE SMOKE DETECTOR
 REQUIRED ON THE OUTSIDE OF THE ROOM.
 3. ELEVATOR LOBBY MISSING RECALL DETECTOR.
 4. THE N.E. PARKING AREA MISSING NOTIFICATION
 APPLIANCE.
 5. TYPICAL TO FLRS. 2 ? 6 & 8:
 A) MISSING SMOKE DETECTOR IN ELEVATOR LOBBIES.
 B) SMOKE DETECTORS SHALL NOT BE INSTALLED WITHIN A
 RADIUS OF 10? FROM A COOKING APPLIANCE UNLESS
 SPECIFICALLY LISTED FOR THE PURPOSE.
 6. FLOOR PLAN FOR LEVEL 7 VARIES FROM THE REST; ROOMS
 SHALL BE LABELED FOR IDENTIFICATION.
 7. FLOOR 9 VARIES AS WELL, ALL ROOMS SHALL BE
 IDENTIFIED.
 8. BECAUSE THE DEVICE COUNT WILL VARY, THE RISER AND
 CALCS SHALL BE REVISED ACCORDINGLY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2015-09-15 Cont ID  
Sent By pleduc Date 2015-09-15 Time   Rev Time 0.00
Received By pleduc Date 2015-09-15 Time 10:17 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-08-27 Cont ID  
Sent By pleduc Date 2015-08-27 Time   Rev Time 0.00
Received By pleduc Date 2015-08-27 Time 09:11 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-07-13 Cont ID  
Sent By Lindow Date 2015-07-13 Time   Rev Time  
Received By   Date 2015-07-13 Time   Sent To E
Notes
2015-07-13 14:47:11SUBJECT TO FIELD INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-09-21 Cont ID  
Sent By albarran Date 2015-09-21 Time 16:21 Rev Time 0.00
Received By albarran Date 2015-09-11 Time 10:14 Sent To  
Notes
2015-09-21 16:21:119/21/15 - PASSED ELECTRICAL W/PROVISO. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT TO SMALL READY BIN "T". MA
2015-09-14 10:14:44ROUTED TO FIRE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-02 Cont ID  
Sent By albarran Date 2015-09-02 Time 10:16 Rev Time 0.00
Received By albarran Date 2015-08-25 Time 16:14 Sent To  
Notes
2015-09-02 10:17:229/2/15 - FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT TO SMALL DENIED BIN "T". MA
2015-08-25 16:14:28RESUB ROUTED TO FIRE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-15 Cont ID  
Sent By albarran Date 2015-07-15 Time 17:50 Rev Time 0.00
Received By albarran Date 2015-07-10 Time 18:59 Sent To  
Notes
2015-07-15 17:53:167/15/15 - FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT TO SMALL DENIED BIN "T". MA
2015-07-10 19:00:17IN FIRE BOX