Plan Review Details - Permit 15070429
Plan Review Stops For Permit 15070429
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-08-13 Cont ID  
Sent By jwitmer Date 2015-08-13 Time 13:31 Rev Time 0.00
Received By jwitmer Date 2015-08-13 Time 11:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-07-21 Cont ID  
Sent By jwitmer Date 2015-07-21 Time 12:28 Rev Time 0.00
Received By jwitmer Date 2015-07-21 Time 07:46 Sent To  
Notes
2015-07-21 08:04:13BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15070429
 ADD: 1600 N. DIXIE HWY.
 CONT: COOL TEAM SERVICES
 TEL: (561)683-7110
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 801.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JULY 21/ 2015
 ACTION: DENIED
  
 1) SHEET A2.1 SHOWS NEW ROOF TOP UNITS REQUIRING CURBS
 AND NEW OPENINGS THROUGH THE ROOF. DETAIL # 3 SHOWS A
 NEW OPENING TO BE CUT INTO THE ROOF SHEATHING AND NEW
 FRAMING AROUND THE HOLE. THE PLANS DO NOT PROVIDE WHAT
 THE MINIMUM AND OR MAXIMUM SIZE OF THE HOLE TO BE CUT
 IN THE ROOF SHEATHING. ADDITIONAL INFORMATION IS
 REQUIRED. 107.2.1.3. CODE COMPLIANCE CAN NOT BE
 DETERMINED.
  
 2) SHEET A2.1 SHOWS THE ROOF JOIST AT THE END OF THE
 HOLE TO BE DOUBLED 2 X12'S, THE PLANS DO NOT PROVIDE
 HOW OFTEN THEY ARE TO BE NAILED TOGETHER AND WHAT SIZE
 NAILS, TO FORM A DOUBLED FRAMING MEMBER OR GIRDER.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 3) SHEET A2.1 DOES NOT PROVIDE THE LENGTH OF THE NEW
 OPENING. SECTION 2308.8.3 OF THE FBC-B REQUIRES BOTH
 THE TRIMMER AND HEADER JOIST TO BE COUBLED, OR OF
 LUMBER OF EQUIVALENT CROSS SECTION. THE PLANS ONLY SHOW
 THE HEADER TO BE A SINGLE MEMBER NOT DOUBLED.
  
 4) SHEET A2.1 DETAIL # 3 SHOWS 2 DETAILS IT APPEARS
 THEY ARE MIS-LABELED, IT APPEARS THEY SHOULD BE LABELED
 DETAIL # 2/ A2.1 TYPO, DISCREPANCY IN PLANS, 107.2.1.3.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 5) SHEET A2.1 INDICATES IN DETAIL # 2 INDICATES TTHE
 USE OF PRE-MANUFACTURED ROOF CURBS, PLEASE PROVIDE
 COMPLIANCE WITH:
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31) (D) ROOFING PRODUCTS AND ASSEMBLIES/
 PRE-MANUFACTURED ROOF CURBS.
  
 6) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) SHEET A1.0 PROVIDES THE WIND DESIGN CRITERIA BUT
 NEITHER SHEET A1.0 OR A2.1 PROVIDE THE PRESSURES THAT
 WILL BE ASSOCIATED ON THE ROOF CURB TO THE ROOF FRAMING
 MEMBERS. 2010 FBC-B 1609.4.4.1.
  
 8) PLEASE ALSO REVIEW THE 2010 FBC-B SECTION 1609.8
 ROOFTOP STRUCTURES AND EQUIPMENT.
 THE LATERAL FORCE ON ROOFTOP STRUCTURES AND EQUIPMENT
 WITH AF LESS THAN (0.1BH) LOCATED ON BUILDINGS OF ALL
 HEIGHTS SHALL BE DETERMINED FROM EQUATION 29.5-1 OF
 ASCE 7 IN WHICH THE VALUE OF GCF SHALL BE TAKEN AS 3.1.
 GCF SHALL BE PERMITTED TO BE REDUCED LINEARLY FROM 3.1
 TO 1.1 AS THE VALUE OF AF IS INCREASED FROM (0.1BH) TO
 (BH). THE VALUE OF G FROM SECTION 26.9 OF ASCE 7 SHALL
 NOT BE USED. ADDITIONALLY, A SIMULTANEOUS UPLIFT FORCE
 SHALL BE APPLIED, GIVEN BY EQUATION 29.5-1 OF ASCE 7 IN
 WHICH GCF = 1.5 AND AF IS REPLACED BY THE HORIZONTAL
 PROJECTED AREA, AR, OF THE ROOFTOP STRUCTURE OR
 EQUIPMENT. FOR THE UPLIFT FORCE GCF SHALL BE PERMITTED
 TO BE REDUCED LINEARLY FROM 1.5 TO 1.0 AS THE VALUE OF
 AR IS INCREASED FROM (0.1BL) TO (BL).
  
 9) SHEET A2.1 DETAIL # 2 FAILS TO IDENTIFY HOW THE RTU
 IS GOING TO BE ATTACHED TO THE ROOF TOP CURB FOR THE
 APPROPREATE ROOF PRESSURES TO RESIST THE MOMENT OF
 OVERTURNING. 2010 FBC-B 1604.4 ANALYSIS EVERY STRUCTURE
 SHALL BE DESIGNED TO RESIST THE OVERTURNING EFFECTS
 CAUSED BY THE LATERAL FORCES SPECIFIED IN THIS CHAPTER.
 SEE SECTION 1609 FOR WIND LOADS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-13 Cont ID  
Sent By jwitmer Date 2015-08-13 Time 13:31 Rev Time 0.00
Received By jwitmer Date 2015-08-11 Time 13:24 Sent To  
Notes
2015-08-11 13:24:42RESUB ROUTED TO CCOLE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2015-08-12 Cont ID  
Sent By ccole Date 2015-08-12 Time 08:10 Rev Time 0.00
Received By ccole Date 2015-08-12 Time 08:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-07-14 Cont ID  
Sent By ccole Date 2015-07-14 Time 08:17 Rev Time 0.00
Received By ccole Date 2015-07-14 Time 08:17 Sent To  
Notes
2015-07-14 08:40:301ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15070429
 7/14/15
  
 1) THE FLORIDA BUILDING CODES 5TH EDITION 2014 WENT
 INTO EFFECT ON JUNE 30, 2015. PLEASE REVIEW AND UPDATE
 THE DESIGN CRITERIA LISTED UNDER PROJECT INFORMATION ON
 SHEET A0.1.
 2) PROVIDE COOLING AND HEATING LOAD CALCULATIONS FOR
 THE NEW AC SYSTEMS IN ACCORDANCE WITH ACCA MANUAL N OR
 THE ACCA/ASHRAE STANDARD 183- SECTION C403.2.1 FBC-2014
 ENERGY CONSERVATION.
 3) THE PREVIOUSLY UNCONDITIONED BUILDING NOW BEING
 CONDITIONED MUST BE BROUGHT INTO FULL COMPLIANCE WITH
 THE FBC-2014 ENERGY CONSERVATION CODE- SEE SECTION
 C101.4.5. PLEASE SUBMIT TWO COPIES OF FORM C402 FOUND
 IN APPENDIX C OF THE CODE BOOK, OR A COMPLIANCE
 CERTIFICATION DOCUMENT FROM FLORIDA BUILDING COMMISSION
 APPROVED SOFTWARE.
 4) THE RTU TIE DOWN DETAILS ARE INCOMPLETE: INDICATE
 THE TYPE, SIZE, AND SPACINGS OF FASTENERS TO BE USED TO
 MOUNT THE RTU'S TO THE CURBS- REFERENCE SECTION 301.15
 FBC-14 MECHANICAL FOR ADDITIONAL COMPLIANCE CRITERIA.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  