| 2015-08-03 17:10:16 | MET WITH CONTRACTOR TO REVIEW NEW UNDERLAYMENT. |
| | INFORMATION SUBMITTED WAS FOR AN 8" CONCRETE SLAB WITH |
| | ACOUSTICAL CEILING. NO GOOD. |
| | |
| | |
| | RESIDENTIAL (R2) FLOORING BUILDING REVIEW COMMENTS. |
| | CODE: FBC 5TH EDITION (2014) |
| | |
| | 1- COPIES OF ASTM E 90 AND ASTM E 492TESTING SUBMITTED |
| | IS FOR AN 8" CONCRETE SLAB FLOOR/CEILING ASSEMBLY WITH |
| | AN ACOUSTICAL SUSPENDED CEILING. THIS ASSEMBLY DOESN'T |
| | MATCH FLOOR/CEILING ASSEMBLY FOR THIS BUILDING. PROVIDE |
| | TWO COPIES OF SOUND TRANSMISSION CLASS (STC) AND IMPACT |
| | INSULATION CLASS (IIC) TESTING FOR ASSEMBLY THAT |
| | MATCHES ACTUAL CONDITIONS. SEC. 1207.2 AND SEC. 1207.3 |
| | OF FBC 5TH EDITION (2014) |
| | |
| | 2- PROVIDE TWO COPIES OF THE FLAME SPREAD INDEX AND |
| | SMOKE DEVELOPED INDEX TEST DONE FOR THE UNDERLAYMENT |
| | MATERIAL TO BE USED AS REQUIRED BY SEC. 720.1 OF FBC |
| | 5TH EDITION (2014). |
| | |
| | 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS AND |
| | CONTRACTORS OVERHEAD AND PROFIT AS REQUIRED BY SEC. |
| | 109.3 CITY AMENDMENTS. PROVIDE COPY OF SIGNED CONTRACT |
| | THAT INCLUDES ALL THE SCOPE OF WORK. |
| | |
| | 4- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713 F.S. |
| | |
| | 5- NEED OWNER NOTARIZED SIGNATURE ON THE PERMIT |
| | APPLICATION. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |