Plan Review Details - Permit 15070312
Plan Review Stops For Permit 15070312
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-09-09 Cont ID  
Sent By jgomez Date 2015-09-09 Time 10:49 Rev Time 0.00
Received By jgomez Date 2015-09-09 Time 10:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-08-03 Cont ID  
Sent By jgomez Date 2015-08-03 Time 17:09 Rev Time 0.00
Received By jgomez Date 2015-08-03 Time 17:09 Sent To  
Notes
2015-08-03 17:10:16MET WITH CONTRACTOR TO REVIEW NEW UNDERLAYMENT.
 INFORMATION SUBMITTED WAS FOR AN 8" CONCRETE SLAB WITH
 ACOUSTICAL CEILING. NO GOOD.
  
  
 RESIDENTIAL (R2) FLOORING BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014)
  
 1- COPIES OF ASTM E 90 AND ASTM E 492TESTING SUBMITTED
 IS FOR AN 8" CONCRETE SLAB FLOOR/CEILING ASSEMBLY WITH
 AN ACOUSTICAL SUSPENDED CEILING. THIS ASSEMBLY DOESN'T
 MATCH FLOOR/CEILING ASSEMBLY FOR THIS BUILDING. PROVIDE
 TWO COPIES OF SOUND TRANSMISSION CLASS (STC) AND IMPACT
 INSULATION CLASS (IIC) TESTING FOR ASSEMBLY THAT
 MATCHES ACTUAL CONDITIONS. SEC. 1207.2 AND SEC. 1207.3
 OF FBC 5TH EDITION (2014)
  
 2- PROVIDE TWO COPIES OF THE FLAME SPREAD INDEX AND
 SMOKE DEVELOPED INDEX TEST DONE FOR THE UNDERLAYMENT
 MATERIAL TO BE USED AS REQUIRED BY SEC. 720.1 OF FBC
 5TH EDITION (2014).
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS AND
 CONTRACTORS OVERHEAD AND PROFIT AS REQUIRED BY SEC.
 109.3 CITY AMENDMENTS. PROVIDE COPY OF SIGNED CONTRACT
 THAT INCLUDES ALL THE SCOPE OF WORK.
  
 4- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713 F.S.
  
 5- NEED OWNER NOTARIZED SIGNATURE ON THE PERMIT
 APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-07-24 Cont ID  
Sent By jgomez Date 2015-07-24 Time 09:07 Rev Time 0.00
Received By jgomez Date 2015-07-24 Time 07:55 Sent To  
Notes
2015-07-24 09:29:09RESIDENTIAL (R2) FLOORING BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014)
  
 1- COPIES OF ASTM E 90 AND ASTM E 492TESTING SUBMITTED
 IS FOR AN 8" CONCRETE SLAB FLOOR/CEILING ASSEMBLY WITH
 AN ACOUSTICAL SUSPENDED CEILING. THIS ASSEMBLY DOESN'T
 MATCH FLOOR/CEILING ASSEMBLY FOR THIS BUILDING. PROVIDE
 TWO COPIES OF SOUND TRANSMISSION CLASS (STC) AND IMPACT
 INSULATION CLASS (IIC) TESTING FOR ASSEMBLY THAT
 MATCHES ACTUAL CONDITIONS. SEC. 1207.2 AND SEC. 1207.3
 OF FBC 5TH EDITION (2014)
  
 2- PROVIDE TWO COPIES OF THE FLAME SPREAD INDEX AND
 SMOKE DEVELOPED INDEX TEST DONE FOR THE UNDERLAYMENT
 MATERIAL TO BE USED AS REQUIRED BY SEC. 720.1 OF FBC
 5TH EDITION (2014).
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS AND
 CONTRACTORS OVERHEAD AND PROFIT AS REQUIRED BY SEC.
 109.3 CITY AMENDMENTS. PROVIDE COPY OF SIGNED CONTRACT
 THAT INCLUDES ALL THE SCOPE OF WORK.
  
 4- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713 F.S.
  
 5- NEED OWNER NOTARIZED SIGNATURE ON THE PERMIT
 APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-09 Cont ID  
Sent By jgomez Date 2015-09-09 Time 13:55 Rev Time 0.00
Received By jgomez Date 2015-09-04 Time 08:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-24 Cont ID  
Sent By jgomez Date 2015-07-24 Time 07:55 Rev Time 0.00
Received By jgomez Date 2015-07-08 Time 08:28 Sent To  
Notes
***NONE***