Plan Review Details - Permit 15070263
Plan Review Stops For Permit 15070263
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-09-04 Cont ID  
Sent By jwitmer Date 2015-09-04 Time 14:25 Rev Time 0.00
Received By jwitmer Date 2015-09-04 Time 13:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-07-22 Cont ID  
Sent By jwitmer Date 2015-07-22 Time 16:21 Rev Time  
Received By jwitmer Date 2015-07-22 Time   Sent To  
Notes
2015-07-22 16:21:50BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15070263
 ADD: 2580 METROCENTRE BLVD. SUITE # 3B
 CONT: EMERALD CONSTRUCTION
 TEL: (954)241-2583
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JULY 22/ 2015
 ACTION: DENIED
  
 1) THE COVERSHEET A-0.0 INDICATES THE PLANS WERE
 DESIGNED TO THE 2010 FBC. PLEASE BE AWARE THAT THE 2014
 FBC WAS ADOPTED STATE WIDE JUNE 30/ 2015.
 PLANS WILL NEED TO BE UPDATED TO THE CURRENT ADOPTED
 CODE.
  
 2) SHEET A-1.0:
 1A) THE NEW DOOR IN THE OLD TENANT SEPARATION WALL IS
 ONLY IDENTIFIED AS R SHEET A-3.0 INDICATES THIS DOOR TO
 BE RE-USED BUT NO DOOR SIZE IS GIVEN. PLEASE PROVIDE
 CODE COMPLIANCE WITH THE 2014 FBC-B 1008.1.1 SIZE OF
 DOORS. THE MINIMUM WIDTH OF EACH DOOR OPENING SHALL BE
 SUFFICIENT FOR THE OCCUPANT LOAD THEREOF AND SHALL
 PROVIDE A CLEAR WIDTH OF 32 INCHES (813 MM). CLEAR
 OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE
 MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP,
 WITH THE DOOR OPEN 90 DEGREES.
  
 1B) SHEET A-1.0 DOOR IS A NEW DOOR LOCATION, A NEW
 DOOR, THE DOOR SCHEDULE ON A-3.0 INDICATES THIS DOOR TO
 BE A 2'-6" DOOR. PLEASE PROVIDE CODE COMPLIANCE WITH
 THE 2014 FBC-B 1008.1.1 SIZE OF DOORS. THE MINIMUM
 WIDTH OF EACH DOOR OPENING SHALL BE SUFFICIENT FOR THE
 OCCUPANT LOAD THEREOF AND SHALL PROVIDE A CLEAR WIDTH
 OF 32 INCHES (813 MM). CLEAR OPENINGS OF DOORWAYS WITH
 SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF
 THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES.
  
 2) COVERSHEET AT THE TOP OF THE SHEET THE MEANS OF
 EGRESS GOES THROUGH WHAT APPEARS TO BE A BREAK ROOM.
 NONE OF THE SHEETS LABEL THE USE OF THIS ROOM, FBC-B
 ALLOWS FOR EGRESS THROUGH INTERVENING ROOM THIS ROOM
 APPEARS TO BE A BREAK ROOM. THE CODE WILL NOT ALLOW A
 MEANS OF EGRESS THROUGH A KITCHEN, PLEASE LABEL THE USE
 OF THIS SPACE.
  
 3) IT APPEARS ON M-1.0 THERE WILL BE A NEW EXTERIOR
 WALL LOUVER FOR OUTSIDE AIR.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (3)(C) WALL LOUVERS
  
 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-08-11 Cont ID  
Sent By albarran Date 2015-08-11 Time 18:25 Rev Time 0.00
Received By albarran Date 2015-08-11 Time 16:00 Sent To M
Notes
2015-08-11 18:26:11ELECTRIC PROVISO TO PERMIT 15070263
 1. BATHROOM MISSING THE O/S PER FBC-E SECTION 505.
 2. SWITCHES FOR LIGHTING SHALL HAVE A NEUTRAL CONDUCTOR
 RUN TO THEM.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-08-26 Cont ID  
Sent By pleduc Date 2015-08-26 Time   Rev Time 0.00
Received By pleduc Date 2015-08-26 Time 14:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-07-09 Cont ID  
Sent By pleduc Date 2015-07-09 Time   Rev Time 0.00
Received By pleduc Date 2015-07-09 Time 15:35 Sent To  
Notes
2015-07-09 15:59:58THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET A-3.0, DOOR SCHEDULE, DOORS R & E LOCATED AT
 THE SPACE INDICATED ON SHEET A-1.0 AS NEW CORRIDOR,
 DOES NOT INDICATE THE DOOR HARDWARE AND LOCKING OR
 LATCHING.
  
 2) SHEET A-0.0 INDICATES EXIT PASSAGE THRU A ROOM
 INDICATED ON SHEET A-1.0 AS NEW CORRIDOR. ACCESS TO AN
 EXIT SHALL NOT PASS THROUGH KITCHENS, STOREROOMS,
 RESTROOMS, WORKROOMS, CLOSETS, BEDROOMS, OR OTHER
 SIMILAR SPACES, OR OTHER ROOMS OR SPACES SBJECT TO
 LOCKING UNLESS PERMITTED BY THE OCCUPANCY CHAPTER.
 CHAPTER 39, EXISTING BUSINESS OCCUPANCIES, DOES NOT
 ALLOW FOR PASSAGE THROUGH THIS ROOM.
 THE EXIT SHALL NOT PASS THROUGH THIS ROOM AS
 CONFIGURED.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-09-15 Cont ID  
Sent By ccole Date 2015-09-15 Time 14:05 Rev Time 0.00
Received By ccole Date 2015-09-14 Time 12:07 Sent To  
Notes
2015-09-15 12:08:14RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-04 Cont ID  
Sent By jwitmer Date 2015-09-04 Time 14:25 Rev Time 0.00
Received By jwitmer Date 2015-08-25 Time 16:05 Sent To  
Notes
2015-08-25 16:06:16B32

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-12 Cont ID  
Sent By cpuell Date 2015-08-12 Time 09:25 Rev Time 0.00
Received By cpuell Date 2015-07-08 Time 15:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-09-15 Cont ID  
Sent By ccole Date 2015-09-15 Time 14:05 Rev Time 0.00
Received By ccole Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-09-04 Cont ID  
Sent By ccole Date 2015-09-04 Time 16:37 Rev Time 0.00
Received By ccole Date 2015-09-02 Time 11:07 Sent To  
Notes
2015-09-02 11:11:562ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15070263
 9/2/15
  
 1) AS PREVIOUSLY REQUESTED IN THE 1ST REVIEW PROVIDE AC
 COOLING AND HEATING CALCULATIONS FOR THE NEW SYSTEM:
 C403.2.1 CALCULATION OF HEATING AND COOLING LOADS.
 DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE
 PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR
 ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE
 COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT
 WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE
 MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE
 SIZING CALCULATION SHALL BE SUBMITTED WITH THE
 APPLICATION FOR THE MECHANICAL PERMIT. HEATING AND
 COOLING LOADS SHALL BE ADJUSTED TO ACCOUNT FOR LOAD
 REDUCTIONS THAT ARE ACHIEVED WHEN ENERGY RECOVERY
 SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM IN ACCORDANCE
 WITH THE ASHRAEHVAC SYSTEMS AND EQUIPMENT HANDBOOK.
 ALTERNATIVELY, DESIGN LOADS SHALL BE DETERMINED BY AN
 APPROVED EQUIVALENT COMPUTATION PROCEDURE, USING THE
 DESIGN PARAMETERS SPECIFIED IN CHAPTER 3.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-08-12 Cont ID  
Sent By ccole Date 2015-08-12 Time 08:38 Rev Time 0.00
Received By ccole Date 2015-08-12 Time 08:38 Sent To  
Notes
2015-08-12 09:02:001ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15070263
 8/12/15
  
 1) REFERENCE SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION: PROVIDE COOLING AND HEATING LOAD
 CALCULATIONS FOR THE NEW OFFICE AC SYSTEM IN ACCORDANCE
 WITH ACCA MANUAL N OR THE ACCA/ASHRAE STANDARD 183.
 2) SHEET M-1, KEYNOTE #1: REFERENCE SECTION 306.1
 FBC-14 MECHANICAL AND REVISE THE NOTE TO SHOW
 COMPLIANCE.
 306.1 ACCESS FOR MAINTENANCE AND REPLACEMENT.
 APPLIANCES SHALL BE ACCESSIBLE FOR INSPECTION, SERVICE,
 REPAIR AND REPLACEMENT WITHOUT DISABLING THE FUNCTION
 OF A FIRE-RESISTANCE-RATED ASSEMBLY OR REMOVING
 PERMANENT CONSTRUCTION, OTHER APPLIANCES, VENTING
 SYSTEMS OR ANY OTHER PIPING OR DUCTS NOT CONNECTED TO
 THE APPLIANCE BEING INSPECTED, SERVICED, REPAIRED OR
 REPLACED. A LEVEL WORKING SPACE AT LEAST 30 INCHES DEEP
 AND 30 INCHES WIDE (762 MM BY 762 MM) SHALL BE PROVIDED
 IN FRONT OF THE CONTROL SIDE TO SERVICE AN APPLIANCE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-07-24 Cont ID  
Sent By tklarge Date 2015-07-24 Time 05:06 Rev Time 0.00
Received By tklarge Date 2015-07-24 Time 04:32 Sent To  
Notes
***NONE***