Plan Review Details - Permit 15070198
Plan Review Stops For Permit 15070198
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2015-12-03 Cont ID  
Sent By shill Date 2015-12-03 Time 07:19 Rev Time 0.00
Received By shill Date 2015-12-03 Time 07:19 Sent To  
Notes
2015-12-03 07:25:12ENGINEER CALLED AND SAID THAT THE LANGUAGE
 "CONSTRUCTION DESIGN & MANAGEMENT SERVICES" IS A
 DESCRIPTION OF SERVICES OFFERED, NOT A COMPANY NAME. HE
 SAID THAT HE HAS TWO OFFICES; ONE ON SUNRISE AND ONE AT
 7430 RAMONA STREET WHICH IS HIS RESIDENCE.
  
 ENGINEER WAS ADVISED THAT IT APPEARS THAT "CONSTRUCTION
 DESIGN & MANAGEMENT SERVICES" IS A COMPANY. A
 SUNBIZ.ORG WAS FILED FOR THIS NAME WITH THE RAMONA
 ADDRESS (BUT NOW INACTIVE).
  
 THIS IS FURTHER EVIDENCED BY THE EMAIL FROM THE
 CONTRACTOR WHICH STATED SAME (ENGINEER WORKS FOR
 HIMSELF THROUGH A COMPANY). ENGINEER (DONALD DIXON, PE)
 WAS ADVISED THAT ON FUTURE DOCUMENTS IS TO AMEND TITLE
 BLOCK TO BE CLEARLY IN COMPLIANCE WITH FS471 AND
 FAC61G15.
  
 THE EMAIL AND OTHER DOCUMENTS HAVE BEEN RETAINED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2015-11-21 Cont ID  
Sent By shill Date 2015-11-21 Time 14:37 Rev Time 0.00
Received By shill Date 2015-11-21 Time 14:36 Sent To  
Notes
2015-11-21 14:38:38****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE PLAN SUBMITTED DOES NOT HAVE A TITLE BLOCK IN
 COMPLIANCE WITH FS471, FAC61G15-23.002.
  
 2. AS CONTRACTOR DID NOT PROVIDE A REASONABLE VALUE, A
 VALUE ADJUSTMENT HAS BEEN DONE FBC 109.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-11-09 Cont ID  
Sent By shill Date 2015-11-09 Time 07:16 Rev Time 0.00
Received By shill Date 2015-11-09 Time 07:16 Sent To  
Notes
2015-11-09 07:26:39****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 THE ENGINEERED DETAIL SUBMITTED IS NOT CONSISTENT WITH
 THE FIELD CONDITION. ROOF FRAMING AND ROOFING WORK WAS
 DONE WITHOUT PERMIT. THE RESUBMITTAL DOES NOT ADDRESS
 PREVIOUS COMMENT LIST:
  
 1. SEE CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE SECTION 107:
  
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS
 107.2.1 THROUGH 107.2.5.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE
 SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS
 CODE AND RELEVANT LAWS, ORDINANCES, RULES
 AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. (SEE ALSO SECTION 107.3.5).
  
 STRUCTURAL DETAILS FOR ROOF FRAMING WERE NOT PROVIDED;
 ROOF FRAMING IS STILL SHOWN AS "EXISTING".
  
 2. REVISE PLAN TO INCLUDE WIND DESIGN CRITERIA FBC 5TH
 EDITION RESIDENTIAL 301.2.1.
  
 THIS WAS NOT INCLUDED ON THE PLAN AND THE PLAN REFERS
 TO AN OUTDATED VERSION OF ASCE7.
  
 3. OK
  
 4. VALUE IS UNREASONABLY LOW. PROVIDE AN ACCURATE
 VALUE. VALUE IS TO INCLUDE THE MARKET VALUE OF LABOR,
 MATERIALS, OVERHEAD, PROFIT, ENGINEERING - EVERYTHING
 EXCEPT FOR LAND, CITY OF WEST PALM BEACH AMENDMENTS TO
 THE FLORIDA BUILDING CODE SECTION 109. WHEN PROVIDING
 THE VALUE, PROVIDE A COST BREAKDOWN ITEM BY ITEM. IF IT
 IS DETERMINED THAT THE VALUE IS STILL UNREASONABLY LOW,
 VALUE WILL BE BALLPARKED. IF APPLICANT OBJECTS, A STICK
 ESTIMATE WILL BE DONE BUT BE AWARE THAT THIS WILL DELAY
 PLAN REVIEW DUE TO THE LENGTH OF TIME REQUIRED.
  
 5. A STOP WORK VIOLATION HAS BEEN ISSUED. PLANS
 PROVIDED DO NOT MEET THE MINIMUM REQUIREMENTS FOR PLANS
 (SEE COMMENT 1).
 3RD REVIEW, INCLUDE ALL WORK DONE WITHOUT PERMIT IN
 THIS PLAN. ROOF FRAMING AND ROOFING WAS DONE WITHOUT
 PERMITS BUT IS NOT INCLUDED ON THIS PLAN. THIS PERMIT
 IS TO INCLUDE ALL WORK DONE WITHOUT PERMITS.
  
 7. THE DETAIL SUBMITTED DOES NOT HAVE A TITLE BLOCK IN
 COMPLIANCE WITH FS471, FAC61G15-23.002.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-10-20 Cont ID  
Sent By shill Date 2015-10-20 Time 07:19 Rev Time 0.00
Received By shill Date 2015-10-20 Time 07:19 Sent To  
Notes
2015-10-20 07:21:43****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 THE ENGINEERED DETAIL SUBMITTED IS NOT CONSISTENT WITH
 THE FIELD CONDITION. WORK SHOWN ON THE DETAIL AS
 "EXISTING" WAS PERFORMED WITHOUT PERMIT. THE
 RESUBMITTAL DOES NOT ADDRESS PREVIOUS COMMENT LIST:
  
 1. SEE CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE SECTION 107:
  
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS
 107.2.1 THROUGH 107.2.5.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE
 SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS
 CODE AND RELEVANT LAWS, ORDINANCES, RULES
 AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. (SEE ALSO SECTION 107.3.5).
  
 STRUCTURAL DETAILS FOR WALL AND ROOF FRAMING ARE NOT
 PROVIDED. AS THIS AFFECTS EXTERIOR WALLS (BUILDING
 ENVELOPE) EITHER PROVIDE ENGINEERING FOR STRUCTURAL
 LOAD BEARING ELEMENTS OR REVISE PLAN TO STATE DESIGN
 CRITERIA (FBC 5TH EDITION RESIDENTIAL 301.1). IF ASCE7
 IS USED AS DESIGN CRITERIA AND PLANS ARE NOT PREPARED
 BY A DESIGN PROFESSIONAL, PROVIDE CALCULATIONS FOR
 STRUCTURAL ELEMENTS (FRAMING, CONNECTORS).
  
 2. REVISE PLAN TO INCLUDE WIND DESIGN CRITERIA FBC 5TH
 EDITION RESIDENTIAL 301.2.1.
  
 3. REVISE PLAN TO INCLUDE METHOD OF COMPLIANCE
 SELECTED, FBC 5TH EDITION EXISTING BUILDING CODE 301.1.
  
 4. VALUE IS UNREASONABLY LOW. PROVIDE AN ACCURATE
 VALUE. VALUE IS TO INCLUDE THE MARKET VALUE OF LABOR,
 MATERIALS, OVERHEAD, PROFIT, ENGINEERING - EVERYTHING
 EXCEPT FOR LAND, CITY OF WEST PALM BEACH AMENDMENTS TO
 THE FLORIDA BUILDING CODE SECTION 109. WHEN PROVIDING
 THE VALUE, PROVIDE A COST BREAKDOWN ITEM BY ITEM. IF IT
 IS DETERMINED THAT THE VALUE IS STILL UNREASONABLY LOW,
 VALUE WILL BE BALLPARKED. IF APPLICANT OBJECTS, A STICK
 ESTIMATE WILL BE DONE BUT BE AWARE THAT THIS WILL DELAY
 PLAN REVIEW DUE TO THE LENGTH OF TIME REQUIRED.
  
 5. A STOP WORK VIOLATION HAS BEEN ISSUED. PLANS
 PROVIDED DO NOT MEET THE MINIMUM REQUIREMENTS FOR PLANS
 (SEE COMMENT 1). IF A DESIGN PROFESSIONAL IS HIRED,
 SEND A COPY OF THE CONTRACT. APPLICANT WAS GIVEN 30
 DAYS TO OBTAIN A PERMIT. EXTENSIONS WILL NOT BE GRANTED
 WITHOUT EVIDENCE THAT CONTRACTOR IS PURSUING RESOLUTION
 (EITHER A COMPETENT DESIGN PROFESSIONAL HIRED, OR PLANS
 RESUBMITTED).
  
 2ND REVIEW, IT IS NOT CLEAR WHY AN ENGINEER WOULD STATE
 THAT WORK IS "EXISTING" WHEN IT IS CLEARLY WORK
 RECENTLY INSTALLED WITHOUT A PERMIT. PLANS ARE TO SHOW
 SCOPE AND NATURE OF WORK. WORK DONE WITHOUT PERMIT IS
 TO BE SHOWN AS "PROPOSED" AS IT IS NOT "EXISTING"
 UNLESS LEGALLY PERMITTED AND INSPECTED.
  
 6. PLANS SHOW "EXISTING SMOKE DETECTORS." I WAS UNABLE
 TO LOCATE AN ELECTRICAL PERMIT FOR THIS ADDRESS FOR
 THIS ITEM. PROVIDE MORE INFORMATION, FBC 107. IF
 ADDITIONAL WORK WAS DONE WITHOUT PERMITS ON THIS
 STRUCTURE WHICH WAS NOT INCLUDED ON THE STOP WORK
 VIOLATION, REVISE PLAN TO INCLUDE.
  
 2ND REVIEW, AN ELECTRICAL PERMIT WAS ISSUED BUT DOES
 NOT APPEAR TO INCLUDE ALL WORK DONE WITHOUT PERMITS.
  
 NEW COMMENT:
  
 7. THE DETAIL SUBMITTED DOES NOT HAVE A TITLE BLOCK IN
 COMPLIANCE WITH FS471, FAC61G15-23.002.
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-01 Cont ID  
Sent By shill Date 2015-08-01 Time 10:03 Rev Time 0.00
Received By shill Date 2015-08-01 Time 10:03 Sent To P
Notes
2015-08-01 10:15:05****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SEE CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE SECTION 107:
  
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS
 107.2.1 THROUGH 107.2.5.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE
 SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS
 CODE AND RELEVANT LAWS, ORDINANCES, RULES
 AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. (SEE ALSO SECTION 107.3.5).
  
 STRUCTURAL DETAILS FOR WALL AND ROOF FRAMING ARE NOT
 PROVIDED. AS THIS AFFECTS EXTERIOR WALLS (BUILDING
 ENVELOPE) EITHER PROVIDE ENGINEERING FOR STRUCTURAL
 LOAD BEARING ELEMENTS OR REVISE PLAN TO STATE DESIGN
 CRITERIA (FBC 5TH EDITION RESIDENTIAL 301.1). IF ASCE7
 IS USED AS DESIGN CRITERIA AND PLANS ARE NOT PREPARED
 BY A DESIGN PROFESSIONAL, PROVIDE CALCULATIONS FOR
 STRUCTURAL ELEMENTS (FRAMING, CONNECTORS).
  
 2. REVISE PLAN TO INCLUDE WIND DESIGN CRITERIA FBC 5TH
 EDITION RESIDENTIAL 301.2.1.
  
 3. REVISE PLAN TO INCLUDE METHOD OF COMPLIANCE
 SELECTED, FBC 5TH EDITION EXISTING BUILDING CODE 301.1.
  
 4. VALUE IS UNREASONABLY LOW. PROVIDE AN ACCURATE
 VALUE. VALUE IS TO INCLUDE THE MARKET VALUE OF LABOR,
 MATERIALS, OVERHEAD, PROFIT, ENGINEERING - EVERYTHING
 EXCEPT FOR LAND, CITY OF WEST PALM BEACH AMENDMENTS TO
 THE FLORIDA BUILDING CODE SECTION 109. WHEN PROVIDING
 THE VALUE, PROVIDE A COST BREAKDOWN ITEM BY ITEM. IF IT
 IS DETERMINED THAT THE VALUE IS STILL UNREASONABLY LOW,
 VALUE WILL BE BALLPARKED. IF APPLICANT OBJECTS, A STICK
 ESTIMATE WILL BE DONE BUT BE AWARE THAT THIS WILL DELAY
 PLAN REVIEW DUE TO THE LENGTH OF TIME REQUIRED.
  
 5. A STOP WORK VIOLATION HAS BEEN ISSUED. PLANS
 PROVIDED DO NOT MEET THE MINIMUM REQUIREMENTS FOR PLANS
 (SEE COMMENT 1). IF A DESIGN PROFESSIONAL IS HIRED,
 SEND A COPY OF THE CONTRACT. APPLICANT WAS GIVEN 30
 DAYS TO OBTAIN A PERMIT. EXTENSIONS WILL NOT BE GRANTED
 WITHOUT EVIDENCE THAT CONTRACTOR IS PURSUING RESOLUTION
 (EITHER A COMPETENT DESIGN PROFESSIONAL HIRED, OR PLANS
 RESUBMITTED).
  
 6. PLANS SHOW "EXISTING SMOKE DETECTORS." I WAS UNABLE
 TO LOCATE AN ELECTRICAL PERMIT FOR THIS ADDRESS FOR
 THIS ITEM. PROVIDE MORE INFORMATION, FBC 107. IF
 ADDITIONAL WORK WAS DONE WITHOUT PERMITS ON THIS
 STRUCTURE WHICH WAS NOT INCLUDED ON THE STOP WORK
 VIOLATION, REVISE PLAN TO INCLUDE.
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2015-12-03 Cont ID  
Sent By shill Date 2015-12-03 Time 07:25 Rev Time 0.00
Received By shill Date 2015-11-25 Time 15:19 Sent To  
Notes
2015-11-25 15:19:14RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-11-21 Cont ID  
Sent By shill Date 2015-11-21 Time 14:38 Rev Time 0.00
Received By shill Date 2015-11-19 Time 12:40 Sent To  
Notes
2015-11-20 12:40:37RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-11-10 Cont ID  
Sent By tklarge Date 2015-11-10 Time 05:30 Rev Time 0.00
Received By tklarge Date 2015-11-05 Time 15:58 Sent To  
Notes
2015-11-09 07:48:2111/9 TO PLUMBING BOX
  
2015-11-05 15:58:58RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-20 Cont ID  
Sent By shill Date 2015-10-20 Time 07:28 Rev Time 0.00
Received By shill Date 2015-10-20 Time 07:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-03 Cont ID  
Sent By gjohnson Date 2015-08-03 Time 15:09 Rev Time 0.00
Received By gjohnson Date 2015-07-07 Time 08:59 Sent To  
Notes
2015-08-01 10:25:178/1 TO PLUMBING
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2015-11-29 Cont ID  
Sent By tklarge Date 2015-11-29 Time 08:28 Rev Time 0.00
Received By tklarge Date 2015-11-29 Time 08:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-11-21 Cont ID  
Sent By tklarge Date 2015-11-21 Time 04:27 Rev Time 0.00
Received By tklarge Date 2015-11-21 Time 04:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-11-10 Cont ID  
Sent By tklarge Date 2015-11-10 Time 05:30 Rev Time 0.00
Received By tklarge Date 2015-11-10 Time 05:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-08-03 Cont ID  
Sent By gjohnson Date 2015-08-03 Time 15:10 Rev Time 0.00
Received By gjohnson Date 2015-08-03 Time 15:10 Sent To  
Notes
***NONE***