Plan Review Details - Permit 15070192
Plan Review Stops For Permit 15070192
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-10-19 Cont ID  
Sent By   Date 2015-10-19 Time   Rev Time 0.00
Received By jwitmer Date 2015-10-19 Time 11:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-10-02 Cont ID  
Sent By jwitmer Date 2015-10-02 Time 07:15 Rev Time 0.00
Received By jwitmer Date 2015-10-02 Time 06:45 Sent To  
Notes
2015-10-02 07:14:09BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15070192
 ADD: 2070 PALM BEACH LAKES / CHICK-FIL-E
 CONT: TBD (TO BE DETERMINED)
 TEL: (?????????????????? NOT PROVIDED ON APPLICATION
 E-MAIL:???????????????? NOT PROVIDED ON APPLICATION
  
 2014 FLORIDA BUILDING CODE W
 * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. OCT. 02/ 2015
 ACTION: DENIED
  
 ) NOTICE!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA
 STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A
 FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE
 REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
  
 1) PREVIOUS COMMENT # 6. A TRANSMITTAL LETTER LISTING
 THE ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION
 OF THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
  
 2) PROVISO: PLEASE BE AWARE IF THERE IS WORK BEING
 COMPLETED ON EITHER THE A/C CONDENSOR STAND OR THE
 EQUIPMENT ITSELF THAT IS WITHIN 10 FT. OF THE PARAPET
 WALL, IF THE PARAPET WALL IS NOT 42 INCHES TALL THEN
 COMPLIANCE WITH 2014 FBC-B 1013.6 WOULD BE REQUIRED.
  
 3) 2ND REQUEST, HIGHLIGHT ON TECHNICAL SHEET, UNIT
 SIZE, DECK TYPE & AMOUNT OF FASTENERS PER SIDE. SHEET
 A-1.7 ALSO SHOWS A NEW ROOF TOP EXHAUST FAN AND CURB.
 PLEASE PROVIDE PRODUCT APPROVALS FOR BOTH THE ROOF TOP
 CURB AND EXHAUST FAN.
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES & FANS
  
 4) 2ND REQUEST. 2014 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5)2ND REQUEST. PLEASE PROVIDE STRUCTURAL DETAILS OF THE
 NEW HOLE TO BE CUT INTO THE ROOF DECK NOT IN THE
 ARCHITECTURAL SHEETS NOR MECHANICAL SHEETS. . PROVIDE
 REINFORING OF THE NEW HOLE, IF BAR JOIST OR WOOD
 TRUSSES, BRACING FOR THE POINT LOAD, AS WELL AS THE
 ANCHORING OF THE EXHAUST FAN CURB TO THE ROOF DECK AND
 THE CURB TO THE BODY OF THE EXHAUST FAN. CURB TO TO BE
 ATTACHED TO FRAMING MEMBERS, PART OF THE MWFRS. MAIN
 WIND FORCE RESISTING SYSTEM. 1609.6.4.4.1.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-12 Cont ID  
Sent By jwitmer Date 2015-08-12 Time 15:36 Rev Time  
Received By jwitmer Date 2015-08-12 Time 14:46 Sent To  
Notes
2015-08-12 15:36:00BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15070192
 ADD: 2070 PALM BEACH LAKES / CHICK-FIL-E
 CONT: TBD (TO BE DETERMINED)
 TEL: (?????????????????? NOT PROVIDED ON APPLICATION
 E-MAIL:???????????????? NOT PROVIDED ON APPLICATION
  
 2014 FLORIDA BUILDING CODE W
 * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. AUGUST 12/ 2015
 ACTION: DENIED
  
 1) SHEET A-1.7 ROOF TOP PLAN HAS A NOTE ABOUT AVCOA
 ALUMINUM EQUIPMENT STAND. THE NOTE STATES THE FREEZER/
 COOLER AND ICE MAKER CONDENSORS ARE TO REMAIN. IS THE
 EQUIPMENT STAND ITSELF BEING REPLACED? IF SO THEN
 PROVIDE A PRODUCT APPROVAL FOR THE STAND, IF
 PRE-ENGINEEERED. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS: (31)(G) PRE-ENGINEERED A/C STAND.
 SEE 2014 FBC-B TABLE 1509.6.5.
  
 2) PLEASE BE AWARE IF THERE IS WORK BEING COMPLETED ON
 EITHER THE A/C CONDENSOR STAND OR THE EQUIPMENT ITSELF
 THAT IS WITHIN 10 FT. OF THE PARAPET WALL, IF THE
 PARAPET WALL IS NOT 42 INCHES TALL THEN COMPLIANCE WITH
 2014 FBC-B 1013.6 WOULD BE REQUIRED.
  
 3) SHEET A-1.7 ALSO SHOWS A NEW ROOF TOP EXHAUST FAN
 AND CURB. PLEASE PROVIDE PRODUCT APPROVALS FOR BOTH THE
 ROOF TOP CURB AND EXHAUST FAN.
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES & FANS
 (G) PRE-ENGINEERED A/C STANDS
  
 4) 2014 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) PLEASE PROVIDE STRUCTURAL DETAILS OF THE NEW HOLE TO
 BE CUT INTO THE ROOF DECK. PROVIDE REINFORING OF THE
 NEW HOLE, IF BAR JOIST OR WOOD TRUSSES, BRACING FOR THE
 POINT LOAD, AS WELL AS THE ANCHORING OF THE EXHAUST FAN
 CURB TO THE ROOF DECK AND THE CURB TO THE BODY OF THE
 EXHAUST FAN. CURB TO TO BE ATTACHED TO FRAMING MEMBERS,
 PART OF THE MWFRS. MAIN WIND FORCE RESISTING SYSTEM.
 1609.6.4.4.1.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-08-25 Cont ID  
Sent By skennedy Date 2015-08-25 Time 15:29 Rev Time 0.00
Received By skennedy Date 2015-08-25 Time 15:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-08-03 Cont ID  
Sent By scaldero Date 2015-08-03 Time 12:39 Rev Time 0.00
Received By scaldero Date 2015-08-03 Time 12:28 Sent To  
Notes
2015-08-03 12:37:51PERMIT # 15070192
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED WITH COMMENTS:
  
 1) PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 2) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
 3) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OF THE NEW KITCHEN HOOD AND KITCHEN HOOD
 SUPPRESSION SYSTEM.
  
  
 SUE ELLEN CALDERON
 ASST. FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-10-23 Cont ID  
Sent By   Date 2015-10-23 Time   Rev Time 0.00
Received By lmarchan Date 2015-10-15 Time 11:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-02 Cont ID  
Sent By lmarchan Date 2015-10-02 Time 08:02 Rev Time 0.00
Received By lmarchan Date 2015-09-15 Time 14:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-25 Cont ID  
Sent By skennedy Date 2015-08-25 Time 15:29 Rev Time 0.00
Received By skennedy Date 2015-07-29 Time 09:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-10-23 Cont ID  
Sent By ccole Date 2015-10-23 Time 12:53 Rev Time 0.00
Received By ccole Date 2015-10-23 Time 12:53 Sent To  
Notes
2015-10-23 12:56:05PERMIT #15070192
 10/23/15
 PROVISOS:
  
 1) SEPARATE PERMITS ARE REQUIRED FOR THE NEW HOOD-1 AND
 FIRE SUPPRESSION SYTEM.
 2) AC-1 WHICH IS SUPPLYING MAKE-UP AIR FOR HOOD-1 SHALL
 SHUTDOWN IN THE EVENT OF AN ALARM AND FIRE SUPPRESSION
 ACTIVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-09-25 Cont ID  
Sent By ccole Date 2015-09-25 Time 08:37 Rev Time 0.00
Received By ccole Date 2015-09-25 Time 07:17 Sent To  
Notes
2015-09-25 08:57:352ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15070192
 9/25/15
  
 1) REFER TO COMMENT #1 FROM THE 1ST REVIEW. AS NOTED IN
 THE COMMENT, SEPARATE PERMITS ARE REQUIRED FOR KITCHEN
 HOODS AND FIRE SUPPRESSION SYSTEMS. FOR CLARIFICATION
 PURPOSES, PLEASE PLACE A NOTE ON THE MECHANICAL PLANS
 TO THAT EFFECT AND INDICATE THE HOOD DRAWINGS AND
 DETAILS ARE FOR REFERENCE ONLY.
 2) REFER TO COMMENT #3 FROM THE 1ST REVIEW: THE PLANS
 ARE NOT IN COMPLIANCE WITH SECTION 508.1 FBC-14
 MECHANICAL. SEE SHEET M-3.1, KITCHEN PRESSURIZATION:
 THE AMOUNT OF MAKE UP AIR CFM'S FOR THE EXHAUST SYSTEMS
 SHOWN IN THE SCHEDULE IS NOT APPROXIMATELY EQUAL TO THE
 AMOUNT OF EXHAUST AIR CFM'S AS REQUIRED BY CODE. IN
 ADDITION THE SCHEDULES DO NOT CLEARLY INDICATE HOW MUCH
 OF THE O/A FORM AC-1 IS PROVIDED FOR OCCUPANTS (AS
 REQUIRED BY THE O/A SCHEDULE) OR HOW MUCH IS PROVIDED
 FOR COOKING APPLIANCE COMBUSTION. PLEASE CLARIFY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-08-13 Cont ID  
Sent By ccole Date 2015-08-13 Time 08:29 Rev Time 0.00
Received By ccole Date 2015-08-13 Time 07:56 Sent To  
Notes
2015-08-13 08:50:121ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15070192
 8/13/15
  
 1) THE CITY OF WEST PALM BEACH CONSTRUCTION SERVICES
 DIVISION REQUIRES SEPARATE PERMITS FOR KITCHEN HOODS
 AND FIRE SUPPRESSION. PLEASE PLACE A NOTE ON THE PLAN
 ACCORDINGLY TO CLARIFY AND LABEL ALL HOOD DETAILS AS
 "FOR REREFENCE ONLY"
 2) NO VALUE IS INDICATED FOR THE PROPOSED PROJECT ON
 THE PERMIT APPLICATION. REFER TO SECTION 109.3 WPB
 AMENDMENTS TO THE FLORIDA BUILDING CODE 2010 BUILDING
 PERMIT VALUATIONS:
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED
 VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL OR PLUMBING SYSTEMS
 APPEARS TO BE UNDERESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED, UNLESS THE APPLICANT
 CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE
 SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO
 MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND
 DESIGN FEES, MARKETING COSTS, OVERHEAD AND
 PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES
 MAY INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL
 CODE CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE
 SET BY THE BUILDING OFFICIAL.
 *PLEASE NOTE THAT THE VALUES FOR THE HOOD AND FIRE
 SUPPRESSION PROJECT MUST BE BROKEN OUT FROM THE TOTAL
 VALUE OF THIS PERMIT APPLICATION.
 3) PLEASE REVIEW THE FOLLOWING COMMENTS IN REREFENCE TO
 THE FUTURE HOOD AND FIRE SUPPRESSION PERMIT APPLICATION
 AND PLANS.
 A) REFERENCE SECTION 508.1 FBC-14 MECHANICAL AND SHOW
 COMPLIANCE:
 MAKEUP AIR.
 MAKEUP AIR SHALL BE SUPPLIED DURING THE OPERATION OF
 COMMERCIAL KITCHEN EXHAUST SYSTEMS THAT ARE PROVIDED
 FOR COMMERCIAL COOKING APPLIANCES. THE AMOUNT OF MAKEUP
 AIR SUPPLIED TO THE BUILDING FROM ALL SOURCES SHALL BE
 APPROXIMATELY EQUAL TO THE AMOUNT OF EXHAUST AIR FOR
 ALL EXHAUST SYSTEMS FOR THE BUILDING. THE MAKEUP AIR
 SHALL NOT REDUCE THE EFFECTIVENESS OF THE EXHAUST
 SYSTEM.MAKEUP AIR SHALL BE PROVIDED BY GRAVITY OR
 MECHANICAL MEANS OR BOTH. MECHANICAL MAKEUP AIR SYSTEMS
 SHALL BE AUTOMATICALLY CONTROLLED TO START AND OPERATE
 SIMULTANEOUSLY WITH THE EXHAUST SYSTEM. MAKEUP AIR
 INTAKE OPENING LOCATIONS SHALL COMPLY WITH SECTION
 401.4.
 *PLEASE CLARIFY HOW THE PROPOSED SYSTEM IS MEETING
 COMPLIANCE WITH THIS SECTION- 1) HOW MUCH OF THE AIR
 LISTED IN THE SCHEDULE ON SHEET M-3.1 IS FOR THE HOOD
 MAKEUP AIR, AND HOW MUCH FOR CONDITIONING THE SPACE?
 PLEASE NOTE THAT SHEET M-1.1 INDICATES THE CLOSEST
 DIFFUSER TO THE HOOD IS SUPPLYING 630 CFM. 2) HOW IS
 THE MAKEUP LINKED TO OPERATE AUTOMATICALLY WITH THE
 EXHAUST SYSTEM?
 B) REFERENCE SECTION 506.3.4 AND PROVIDE AN AIR
 VELOCITY CALCULATION FOR THE PROPOSED GREASE EXHAUST
 DUCT.
 C) REFERENCE SECTION 507.9 AND SHOW COMPLIANCE:
 CLEARANCES FOR TYPE I HOOD.
 A TYPE I HOOD SHALL BE INSTALLED WITH A CLEARANCE TO
 COMBUSTIBLES OF NOT LESS THAN 18 INCHES (457 MM).
 EXCEPTION: CLEARANCE SHALL NOT BE REQUIRED FROM GYPSUM
 WALLBOARD OR 1/2-INCH (12.7 MM) OR THICKER CEMENTITIOUS
 WALLBOARD ATTACHED TO NONCOMBUSTIBLE STRUCTURES
 PROVIDED THAT A SMOOTH, CLEANABLE, NONABSORBENT AND
 NONCOMBUSTIBLE MATERIAL IS INSTALLED BETWEEN THE HOOD
 AND THE GYPSUM OR CEMENTITIOUS WALLBOARD OVER AN AREA
 EXTENDING NOT LESS THAN 18 INCHES (457 MM) IN ALL
 DIRECTIONS FROM THE HOOD.
 C) SHEET M-4.1: SUBMIT TWO COPIES OF A CURRENT FLORIDA
 PRODUCT APPROVAL OR MIAMI-DADE NOA FOR THE ROOF MOUNTED
 EXHAUST FAN AND CURB. REFER TO FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWING.
 D) SUBMIT TWO COPIES OF MANUFACTURER'S SPECIFICATIONS
 AND INSTALLATION INSTRUCTIONS FOR THE FYREWRAP REVIEWED
 ANSD APPROVED BY THE DESIGN PROFESSIONAL OF RECORD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-08-15 Cont ID  
Sent By tklarge Date 2015-08-15 Time 04:03 Rev Time 0.00
Received By tklarge Date 2015-08-15 Time 02:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2015-11-04 Cont ID  
Sent By lmarchan Date 2015-11-03 Time 16:11 Rev Time 0.00
Received By lmarchan Date 2015-11-03 Time 16:11 Sent To  
Notes
2015-11-04 16:11:24ADOBE DIGITAL SIGNATURES OK PER SKENNEDY