| 2015-08-05 08:12:29 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15070178 |
| | MASTER: 14120580 |
| | ADD: 901 45TH ST. |
| | CONT: HEDRICK BROTHERS |
| | TEL: ( 561)718-9166 |
| | E-MAIL: |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: WED. AUGUST 05/2015 |
| | ACTION: DENIED |
| | |
| | 1) THE PRODUCT APPROVAL A MIAMI-DADE NOA 10-1202.01 |
| | NEITHER PAGE 3 OR 4 OF THE FASTENER TYPES HAS BEEN |
| | CIRCLED TO PROVIDE WHAT THE SLOPE IS, MOMENT DUE TO |
| | GRAVITY, OR THE TYPE OF FASTENER. |
| | |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 107.2.1.2 FOR ROOF |
| | ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION |
| | DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE |
| | TYPE OF ROOFING SYSTEM, MATERIALS, FASTENING |
| | REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE |
| | RATING THAT ARE REQUIRED TO BE INSTALLED. PRODUCT |
| | EVALUATION AND INSTALLATION SHALL INDICATE COMPLIANCE |
| | WITH THE WIND CRITERIA REQUIRED FOR THE SPECIFIC SITE |
| | OR A STATEMENT BY AN ARCHITECT OR ENGINEER FOR THE |
| | SPECIFIC SITE MUST BE SUBMITTED WITH THE CONSTRUCTION |
| | DOCUMENTS. |
| | |