| 2015-07-16 11:02:39 | 7/16/2015 |
| | PROJECT: 909 HENRIETTA |
| | PERMIT#: 15070169 |
| | CODE: 2011 EDITION OF THE NEC, 5TH EDITION OF THE FBC, |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER ONE, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | 1) WHAT IS THE PURPOSE OF THE SERVICE AND PANEL CHANGE? |
| | IS THIS AN UPGRADE? WHAT IS THE EXISTING SERVICE? IS |
| | THERE NEW EQUIPMENT TO BE INSTALLED? INDICATE ANY NEW |
| | EQUIPMENT TO BE INSTALLED. |
| | |
| | 2) PROVIDE A PANEL SCHEDULE FOR EACH PANEL. EVERY |
| | CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY |
| | IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC |
| | PURPOSE OR USE. NEC 408.4 |
| | |
| | 3) PROVIDE A SITE PLAN THAT INDICATES THE LOCATION OF |
| | THE SERVICE OUTSIDE AND A FLOOR PLAN THAT INDICATES THE |
| | LOCATION OF THE PANEL INSIDE. |
| | |
| | 4) INDICATE THE CONTENTS OF EACH CONDUIT. THE SERVICE |
| | ENTRANCE CONDUIT IS SHOWN AS A 2" RIDGED WITH 3, #1/0. |
| | WHAT IS THE FEEDER BETWEEN THE MAIN AND THE PANEL? |
| | |
| | 5) VERIFY OR INDICATE THE EXISTANCE OR INSTALLATION OF |
| | INTERCONNECTED SMOKE DETECTORS AS REQUIRED FOR NEW |
| | CONSTRUCTION. WHEN ALTERATIONS, REPAIRS, OR ADDITIONS |
| | REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| | ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| | INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE |
| | ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| | FBC-RESIDENTIAL 314 AND 315. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |
| | |
| | |
| | |
| | |