| 2015-07-24 09:28:39 | 7/24/2015 |
| | PROJECT: YOUNG. PERGOLA ELECTRICAL |
| | PERMIT#: 15070104 |
| | CODE: 2011 EDITION OF THE NEC, 5TH EDITION OF THE FBC, |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER ONE, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | 1) PROVIDE ADDITIONAL INFORMATION INDICATING THE ACTUAL |
| | DIMENSION OF THE NEW RECEPTACLES PROPOSED TO BE |
| | INSTALLED NEAR THE EDGE OF THE POOL. RECEPTACLES SHALL |
| | BE NOT LESS THAN 6 FT FROM THE INSIDE WALLS OF A POOL |
| | AND SHALL BE GFI PROTECTED. SEE .NEC 680.22(A)(2) AND |
| | NEC 680.22(A)(4) |
| | |
| | 2) PROVIDE ADDITIONAL INFORMATION INDICATING THE ACTUAL |
| | DIMENSION OF THE NEW CEILING FAN OUTLETS PROPOSED TO BE |
| | INSTALLED NEAR THE EDGE OF THE POOL. IN OUTDOOR POOL |
| | AREAS, LUMINAIRES, LIGHTING OUTLETS, AND |
| | CEILINGSUSPENDED (PADDLE) FANS INSTALLED ABOVE THE POOL |
| | OR THE AREA EXTENDING 5 FT HORIZONTALLY FROM THE INSIDE |
| | WALLS OF THE POOL SHALL BE INSTALLED AT A HEIGHT NOT |
| | LESS THAN12 FT ABOVE THE MAXIMUM WATER LEVEL. NEC |
| | 680.22(B)(1) AND 680.22(B)(4) |
| | |
| | 3) PROVIDE ADDITIONAL INFORMATION INDICATING THE |
| | LOCATION OF THE SOURCE OF POWER AND WIRING METHOD FOR |
| | THE NEW RECEPTACLES AND CEILING FAN OUTLETS. WPB |
| | AMENDMENTS TO THE FBC 107.2.1 |
| | |
| | 4) PROVIDE ADDITIONAL INFORMATION INDICATING HOW THE |
| | CEILING FANS ARE PROPOSED TO BE CONTROLLED. SEE NEC |
| | 680.22(C) |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |
| | |