Plan Review Details - Permit 15070083
Plan Review Stops For Permit 15070083
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-07-28 Cont ID  
Sent By jwitmer Date 2015-07-14 Time 13:30 Rev Time 0.00
Received By jwitmer Date 2015-07-14 Time 12:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-07-20 Cont ID  
Sent By albarran Date 2015-07-20 Time 18:07 Rev Time 0.00
Received By albarran Date 2015-07-20 Time 17:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-07-06 Cont ID  
Sent By scaldero Date 2015-07-06 Time 16:40 Rev Time 0.00
Received By scaldero Date 2015-07-06 Time 16:14 Sent To  
Notes
2015-07-06 16:42:06PERMIT # 15070083
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected])
 ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR.
  
 EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN
 STOREROOM TO ENSURE EGRESS PATH REQUIREMENTS ARE
 MAINTAINED AT ALL TIMES.
  
 AN APPROVED WRITTEN EMERGENCY PLAN FOR THE EMERGENCY
 EGRESS OF OCCUPANTS IS REQUIRED PRIOR TO OCCUPANCY. ALL
 EMPLOYEES SHALL BE INSTRUCTED AND PERIODICALLY DRILLED
 WITH RESPECT TO THEIR DUTIES UNDER THE PLAN.
  
 EMPLOYEES SHALL BE PERIODICALLY TRAINED OR INSTRUCTED
 IN THE USE OF PORTABLE FIRE EXTINGUISHERS.
  
 SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO THE
 FIRE ALARM AND SPRINKLER SYSTEM.
  
 WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT
 SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED
 AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE
 MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM
 SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD
 INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY
 BE NEEDED.
  
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-28 Cont ID  
Sent By tklarge Date 2015-07-28 Time 06:41 Rev Time 0.00
Received By tklarge Date 2015-07-02 Time 15:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-07-23 Cont ID  
Sent By ccole Date 2015-07-23 Time 09:35 Rev Time 0.00
Received By ccole Date 2015-07-23 Time 09:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2015-12-03 Cont ID  
Sent By tklarge Date 2015-07-28 Time 06:41 Rev Time 0.00
Received By skennedy Date 2015-07-28 Time 05:24 Sent To  
Notes
2015-12-03 13:51:02PLUBMING IS EXISTING.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2015-08-03 Cont ID  
Sent By skennedy Date 2015-08-03 Time 09:59 Rev Time 0.00
Received By skennedy Date 2015-07-31 Time 10:41 Sent To  
Notes
2015-07-31 10:41:49RECEIVED HARD COPY SIGNED AND SEALED SET OF PLANS