Plan Review Details - Permit 15070056
Plan Review Stops For Permit 15070056
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-08-18 Cont ID  
Sent By shill Date 2015-08-18 Time 09:43 Rev Time 0.00
Received By shill Date 2015-08-18 Time 09:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-08-18 Cont ID  
Sent By shill Date 2015-08-18 Time 08:43 Rev Time 0.00
Received By shill Date 2015-08-18 Time 08:43 Sent To  
Notes
2015-08-18 08:57:59****CORRECTIONS****
  
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. APPLICATION IS TO "REMOVE & REPLACE (5) WINDOWS ON
 SECOND FLOOR, SIDING & FRAMING REPAIRS NEEDED."
  
 PER OWNER, CONTRACTOR, AND PLAN, WINDOW REPLACEMENT IS
 INCLUDED IN THE SCOPE OF ANOTHER PERMIT BY ANOTHER
 CONTRACTOR.
  
 AS THIS IS PART OF THE WINDOW RENOVATION PERMIT
 (WINDOWS CANNOT BE INSTALLED WITHOUT STRUCTURAL FRAMING
 REPAIRS, REPAIRS CANNOT BE COMPLETED WITHOUT
 INSTALLATION OF WINDOWS), THIS SHOULD HAVE BEEN
 SUBMITTED AS A REVISION TO THE MASTER PERMIT.
  
 IF THE CONTRACTOR OF THIS PERMIT (15050961, GEORGE J.
 CASTLE CONSTRUCTION) THEN WOULD LIKE TO SUB CONTRACT
 THIS PORTION OF THE WORK TO ANOTHER CONTRACTOR (ABACOA
 CONSTRUCTION), THE OTHER CONTRACTOR SHOULD SUBMIT A
 PERMIT APPLICATION AS A SUBCONTRACTOR TO THE MASTER
 PERMIT. THE OWNER CANNOT SUBCONTRACT THESE TWO PORTIONS
 OF WORK TO TWO DIFFERENT UNRELATED CONTRACTORS; THIS IS
 CONSIDERED CONTRACTING PER FS 553.
  
 PLEASE DISCUSS WITH THE CONTRACTOR (GEORGE J. CASTLE
 CONSTRUCTION) WHO HAS AN OPEN PERMIT ON THIS PROPERTY.
 COMPLETE A REVISION FORM AND THE SAME NUMBER (15070056)
 WILL BE RETAINED. DETERMINE WHETHER THE CONTRACTOR
 (GEORGE J. CASTLE CONSTRUCTION) WOULD LIKE A STRUCTURAL
 SUB PERMIT ISSUED TO ABACOA CONSTRUCTION OR IF THIS
 WILL BE INCLUDED UNDER THE SCOPE OF THE PERMIT ALREADY
 ISSUED (15050961).
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-07-29 Cont ID  
Sent By shill Date 2015-07-29 Time 12:02 Rev Time 0.00
Received By shill Date 2015-07-29 Time 12:02 Sent To  
Notes
2015-07-29 17:32:52****CORRECTIONS****
  
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. REVISE PLAN TO INCLUDE GOVERNING CODE. CODE
 REFERENCED IS NOT GOVERNING CODE DUE TO APPLICATION
 DATE, FS553.
  
 2. REVISE FLOOR PLAN TO SHOW ROOM DESIGNATIONS.
  
 3. FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN
 HEIGHT, NOTE EXISTING CONDITIONS (TYPE OF WINDOW) AND
 OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB 704.1. THE
 CLEAR OPENING CANNOT BE REDUCED BY MORE THAN 5%.
  
 TO PROVIDE FURTHER CLARIFICATION REGARDING INFORMATION
 NEEDED FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN
 HEIGHT:
  
 STATE WHAT TYPE OF WINDOW IS THERE NOW IN THE BEDROOMS
 - AWNING, CASEMENT, SINGLE HUNG?
  
 STATE WHAT THE EXISTING CLEAR OPENING DIMENSIONS ARE.
 CLEAR OPENING IS THE OPENING WHICH EXISTS WHEN THE
 WINDOW IS FULLY OPEN.
  
 STATE WHAT THE PROPOSED CLEAR OPENING DIMENSIONS ARE.
 THIS CAN BE OBTAINED FROM THE MANUFACTURER.
  
 4. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9N-3, FBC 5TH EDITION 301.
  
 FOR FLORIDA STATE PRODUCT APPROVAL, PROVIDE THE
 FOLLOWING FOR EACH PRODUCT:
  
 COVER SHEET (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE
 THE CODE VERSION, PRODUCT APPROVAL NUMBER, STATUS,
 GENERAL INFORMATION ABOUT THE PRODUCT)
 EVALUATION REPORT
 INSTALLATION INSTRUCTIONS
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-18 Cont ID  
Sent By shill Date 2015-08-18 Time 08:58 Rev Time 0.00
Received By shill Date 2015-08-11 Time 14:23 Sent To  
Notes
2015-08-11 14:24:05RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-30 Cont ID  
Sent By shill Date 2015-07-30 Time 11:31 Rev Time 0.00
Received By shill Date 2015-07-01 Time 08:01 Sent To  
Notes
***NONE***