Plan Review Details - Permit 15070038
Plan Review Stops For Permit 15070038
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-07-11 Cont ID  
Sent By spalmer Date 2016-07-11 Time 16:52 Rev Time 0.00
Received By spalmer Date 2016-07-11 Time 16:52 Sent To  
Notes
2015-08-11 16:25:12RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-11 Cont ID  
Sent By lmarchan Date 2015-08-10 Time 16:22 Rev Time 0.00
Received By lmarchan Date 2015-08-06 Time 16:28 Sent To  
Notes
2015-08-06 16:28:42RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-06 Cont ID  
Sent By lmarchan Date 2015-07-01 Time 16:28 Rev Time 0.00
Received By lmarchan Date 2015-07-01 Time 13:08 Sent To  
Notes
2015-07-01 13:08:58ROUTED TO MECHANICAL

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-08-12 Cont ID  
Sent By ccole Date 2015-08-12 Time 07:19 Rev Time 0.00
Received By ccole Date 2015-08-12 Time 07:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-08-10 Cont ID  
Sent By ccole Date 2015-08-10 Time 09:32 Rev Time 0.00
Received By ccole Date 2015-08-10 Time 09:32 Sent To  
Notes
2015-08-10 09:50:242ND REVIEW: FBC 2014 MECHANICAL
  
 1) BALANCED RETURN AIR REQUIRED IN ACCORDANCE WITH
 SECTION M1602.4 FBC-14 RESIDENTIAL. SHOW HOW AIR IS
 BEING RETURNED FROM THE BEDROOMS TO THE AIR HANDLER IN
 THE NEW CLOSET.
 2) PROVIDE A SUB-PERMIT AND DRAWINGS FOR INSTALLATION
 OF THE NEW AIR HANDLER CLOSET, OR INDICATE THAT IT WILL
 BE DONE UNDER A SEPARATE PERMIT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-07-01 Cont ID  
Sent By ccole Date 2015-07-01 Time 15:09 Rev Time 0.00
Received By ccole Date 2015-07-01 Time 15:09 Sent To  
Notes
2015-07-01 15:45:561ST REVIEW: FBC 2014 MECHANICAL
  
 1) THE PREVIOUSLY UNCONDITIONED HOUSE NOW BEING
 CONDITIONED WITH A NEW AC SYSTEM IS REQUIRED TO TO BE
 BROUGHT INTO FULL COMPLIANCE WITH THE FLORIDA ENERGY
 CONSERVATION CODE 2014 PER SECTION R101.4.6. SUBMIT TWO
 COPIES OF EITHER PRESCRIPTIVE FORM R402, OR THE
 PERFORMANCE BASED FORM R405, OR A FLORIDA RESCHECK
 COMPUTER PRINTOUT- REFERENCE SECTION R101.5.1.1. PLEASE
 SUBMIT A PLAN THAT CORRELATES WITH THE CHOSEN
 COMPLIANCE FORM, THAT INDICATES INSULATION R-VALUES FOR
 WALLS, AND ATTICS, AND EFFICIENCY RATINGS FOR WINDOWS
 AND DOORS. PLEASE NOTE THAT ALL ENVELOPE COMPONENTS NOT
 MEETING COMPLIANCE SHALL BE BROUGHT UP TO THE CURRENT
 STANDARDS REQUIRED PER THE COMPLIANCE PATH CHOSEN.
 2) THE SUBMITTED AC LOAD CALCULATION FORM IS NOT AN
 APPROVED ACCA MANUAL J METHOD. PLEASE PROVIDE A
 CALCULATION USING APPROVED ACCA MANUAL J SOFTWARE AND
 INCLUDE THE ROOM-BY-ROOM WORKSHEETS- SEE SECTION
 R403.6.1 FBC-14 ENERGY CONSERVATION.
 3) SHOW THE REQUIRED MINIMUM CLEARANCES FOR THE NEW AIR
 HANDLER IN THE CLOSET PER SECTION M1305.1.1 FBC-14
 RESIDENTIAL- 3" ALONG THE BACK, SIDES, AND TOP, WITH
 THE TOTAL WIDTH OF THE ENCLOSING SPACE AT LEAST 12"
 WIDER THAN THE AIR HANDLER.
 4) THE SUBMITTED PLAN DOES NOT INDICATE A RETURN AIR
 SYSTEM- REFERENCE SECTION M1602.4 AND REVISE THE PLAN
 ACCORDINGLY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  