Plan Review Details - Permit 15070034
Plan Review Stops For Permit 15070034
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-07-30 Cont ID  
Sent By wjolin Date 2015-07-30 Time 13:57 Rev Time 0.00
Received By wjolin Date 2015-07-29 Time 09:08 Sent To M
Notes
2015-07-29 09:23:39500 BELVEDERE ROAD
 PERMIT #15070034
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PERMIT VALUE OF $20,000 IS EXTREMELY LOW FOR A
 PROJECT OF +30,000 SQ.FT. THE PERMIT VALUE SHALL
 INCLUDE LABOR AND MATERIALS. THE SUBCONTRACT AGREEMENT
 SUBMITTED WAS FOR HVAC WORK AND NOT FIRE SPRINKLER
 INSTALLATION.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-07-08 Cont ID  
Sent By Lindow Date 2015-07-08 Time   Rev Time  
Received By   Date 2015-07-08 Time   Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-07-30 Cont ID  
Sent By ccole Date 2015-07-30 Time 14:06 Rev Time 0.00
Received By ccole Date 2015-07-28 Time 16:39 Sent To  
Notes
2015-07-28 16:40:00CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-28 Cont ID  
Sent By cpuell Date 2015-07-28 Time 16:39 Rev Time 0.00
Received By cpuell Date 2015-07-01 Time 15:47 Sent To  
Notes
2015-07-01 15:47:24ROUTED TO FIRE

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-07-30 Cont ID  
Sent By ccole Date 2015-07-30 Time 14:06 Rev Time 0.00
Received By ccole Date 2015-07-30 Time 14:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-07-29 Cont ID  
Sent By ccole Date 2015-07-29 Time 08:24 Rev Time 0.00
Received By ccole Date 2015-07-29 Time 08:24 Sent To  
Notes
2015-07-29 08:31:002ND REVIEW: FBC 2010 MECHANICAL
 PERMIT #15070034
  
 1) COMMENT #1 FROM THE 1ST REVIEW HAS NOT BEEN
 ADDRESSED. PLEASE COMPLY:
  
 1ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15070034
  
 THE $20,000.00 PROJECT COST LISTED ON THE APPLICATION
 IS UNDERVALUED FOR THE WORK TO BE PERFORMED. REFERENCE
 SECTION 109.3 WPB AMENDENTS TO THE FLORIDA BUILDING
 CODE:
 BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE
 WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 IN ACCORDANCE WITH THE MARSHALL & SWIFT VALUATION
 TABLES, THE COST FOR A NEW SPRINKLER SYSTEM IN A NEW
 SUPERMARKET AT 30,000 SQ. FT. IS LISTED AT 2.23 PER SQ.
 FT. ON THE LOW END, AND 4.26 ON THE HIGH END. BASED ON
 THE LOW END FIGURE, THE NEW PUBLIX BLDG AT 32,862 SF. X
 2.23 = A VALUE OF $73,282.26. PLEASE ADJUST THE PERMIT
 VALUE ON THE APPLICATION PER THE CALCULATION.
  
  
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-07-13 Cont ID  
Sent By ccole Date 2015-07-13 Time 17:39 Rev Time 0.00
Received By ccole Date 2015-07-13 Time 17:39 Sent To  
Notes
2015-07-13 17:55:141ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15070034
  
 1) THE $20,000.00 PROJECT COST LISTED ON THE
 APPLICATION IS UNDERVALUED FOR THE WORK TO BE
 PERFORMED. REFERENCE SECTION 109.3 WPB AMENDENTS TO THE
 FLORIDA BUILDING CODE:
 BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE
 WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 IN ACCORDANCE WITH THE MARSHALL & SWIFT VALUATION
 TABLES, THE COST FOR A NEW SPRINKLER SYSTEM IN A NEW
 SUPERMARKET AT 30,000 SQ. FT. IS LISTED AT 2.23 PER SQ.
 FT. ON THE LOW END, AND 4.26 ON THE HIGH END. BASED ON
 THE LOW END FIGURE, THE NEW PUBLIX BLDG AT 32,862 SF. X
 2.23 = A VALUE OF $73,282.26. PLEASE ADJUST THE PERMIT
 VALUE ON THE APPLICATION PER THE CALCULATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  