| 2015-07-08 12:22:18 | 7/8/2015 |
| | PROJECT: PARKING AUTHORITY |
| | PERMIT#: 15050564 |
| | CODE: 2011EDITION OF THE NEC, FIFTH EDITION OF THE FBC |
| | , WPB AMENDMENTS TO THE FBC, CHAPTER 1, ADMINISTRATION, |
| | FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW. REVISION 15070024 |
| | ACTION: DENIED |
| | |
| | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | 1) THE SUBMITTAL IS INDICATED AS A REVISION. THERE IS |
| | NO WAY TO REVIEW THIS SUBMITTAL AS THERE ARE NO CLOUDED |
| | OR OTHERWISE INDICATED REVISIONS. PLEASE INDICATE |
| | CLEARLY WHAT HAS CHANGED FOR THE ORIGINAL. |
| | |
| | 2) PROVIDE THE ALTERRED RIDER DIAGRAM BATTERY |
| | CALCULATIONS, VOLTAGE DROP CALCULATIONS. |
| | |
| | 3) PROVIDE MANUFACTURER PRODUCT INFORMATION FOR ANY |
| | WIRING METHODS AND MATAERIALS. |
| | |
| | 3) PROVIDE A FIRE STOP DETAIL FOR ALL WALL AND FLOOR |
| | PENETRATIONS OF FIRE RATED ASSEMBLIES. NEC 300.21 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |
| | |
| | |