Plan Review Details - Permit 15070020
Plan Review Stops For Permit 15070020
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-07-28 Cont ID  
Sent By shill Date 2015-07-28 Time 17:12 Rev Time 0.00
Received By shill Date 2015-07-28 Time 17:11 Sent To FIRE
Notes
2015-07-28 17:13:12****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. IMPACT PROTECTION REQUIRED, FBC 5TH ED. 1609.1.4. IF
 REMOVABLE SHUTTERS ARE PROPOSED, PROVIDE THE PRODUCT
 APPROVAL AND COMPLETE THE SAMPLE INSTALLATION SCHEDULE.
 THIS FORM CAN BE OBTAINED IN OUR LOBBY OR ON THE
 INTERNET:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/SCHEDULE_FOR_INSTALLATION.PDF
  
 IF REMOVABLE IMPACT PROTECTION IS PROPOSED, PROVIDE A
 PLAN WHICH SHOWS WHERE ONSITE THE SHUTTERS WILL BE
 STORED. ALSO PROVIDE A LETTER, SIGNED BY THE OWNER,
 WHICH ACKNOWLEDGES THE RESPONSIBILITY TO INSTALL THE
 SHUTTERS IN THE EVENT OF A HURRICANE WATCH AS WELL AS
 INFORMATION AS TO WHO WILL DO THE INSTALLATION (AND WHO
 WILL DO THE INSTALLATION IF THE FIRST PERSON IS
 UNAVAILABLE).
  
 2. IF THE PLAN IS REQUIRED TO BE REVISED BY THE
 ENGINEER DUE TO OTHER COMMENTS, INCLUDE THE OCCUPANCY
 CLASSIFICTION OF THE SPACE, FBC CHAPTER 3 (PER
 CONTRACTOR, THIS IS EITHER BUSINESS OR STORAGE).
  
 3. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9N-3, FBC 5TH EDITION 301.
  
 FOR FLORIDA STATE PRODUCT APPROVAL, PROVIDE THE
 FOLLOWING FOR EACH PRODUCT:
  
 COVER SHEET (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE
 THE CODE VERSION, PRODUCT APPROVAL NUMBER, STATUS,
 GENERAL INFORMATION ABOUT THE PRODUCT)
 EVALUATION REPORT
 INSTALLATION INSTRUCTIONS
  
 PRIOR TO SUBMITTAL PLEASE CONFIRM THAT CODE VERSION IS
 CORRECT (2014) IF USING A FLORIDA STATE PRODUCT
 APPROVAL RATHER THAN A MIAMI DADE NOA.
  
 4. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC
 109.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-07-31 Cont ID  
Sent By pleduc Date 2015-07-31 Time   Rev Time 0.00
Received By pleduc Date 2015-07-31 Time 12:26 Sent To M
Notes
2015-07-31 12:32:13THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. PROVIDE BUILDING FLOOR PLAN, INCLUDING OCCUPANY
 LOADS AND ALL EXITS, EXIT SIGNS, EMERGENCY LIGHTS, ETC.
  
 2. DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY,
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS SIDE.
  
 INDICATE IF THE DOORS WILL BE EQUIPPED WITH ANY
 LOCK/LATCH. IF THE DOORS WILL BE EQUIPPED WITH A
 LOCK/LATCH, INDICATE HOW THE LOCK/LATCH WILL BE
 RELEASED FROM THE EGRESS SIDE OF THE DOOR.
  
 PER SECTION 7.2.1.5.9, THE LOCK/LATCH RELEASING
 MECHANISM ON ALL DOORS SHALL OPEN THE DOOR WITH NOT
 MORE THAN ONE RELEASING OPERATION. THE RELEASING
 MECHANISM SHALL HAVE AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY OPERATED UNDER ALL LIGHTING CONDITIONS.
 THE RELEASING DEVICE SHOULD BE CAPABLE OF BEING
 OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE TIGHT
 GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST TO
 OPERATE.
  
 A THUMB TURN LOCK IS NOT PERMITTED ON THE MAIN ENTRY
 DOOR(S). IN LIEU OF PANIC HARDWARE, THE MAIN ENTRY IS
 PERMITTED TO BE EQUIPPED WITH A KEYED LOCK WITH
 LOCK/UNLOCK INDICATOR WINDOW AND SIGNAGE STATING THE
 DOOR IS TO REMAIN UNLOCKED DURING BUSINESS HOURS. NO
 OTHER LOCKING OR LATCHING MECHANISMS ARE PERMITTED.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By shill Date   Time 17:13 Rev Time 0.00
Received By shill Date 2015-07-01 Time 16:06 Sent To  
Notes
2015-07-29 11:10:497/29 TO FIRE
  
2015-07-07 13:30:13MOVED TO MISC 1 (DID VALUE ADJUSTMENT)
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-07-31 Cont ID  
Sent By ccole Date 2015-07-31 Time 15:10 Rev Time 0.00
Received By ccole Date 2015-07-31 Time 15:10 Sent To  
Notes
2015-07-31 15:31:561ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15070020
 7/31/15
  
 1) THE PLAN IS INDICATING THE GARAGE SPACE IS BEING
 CONVERTED INTO A DIFFERENT USE: REFER TO CHAPTER 3
 FBC-14 BUILDING CODE AND PROVIDE THE USE AND OCCUPANCY
 OF THE SPACE. REFER TO SECTION 1009.1 (MECHANICAL
 REQUIREMENTS) FBC-14 EXISTING BUILDING CODE- AND
 PROVIDE A VENTILATION CALCULATION FOR THE PROPOSED NEW
 USE IN ACCORDANCE WITH TABLE 403.3 FBC-10 MECHANICAL.
 INDICATE ON THE PLAN THE REQUIRED AMOUNT OF OUTDOOR AIR
 AND THE AMOUNT BEING PROVIDED FOR THE OCCUPANTS EITHER
 BY EXISTING SYSTEMS OR PROPOSED NEW SYSTEMS. PLEASE
 NOTE THAT A SPACE HEATING SYSTEM WILL ALSO BE REQUIRED
 PER SECTION 309.1 FBC-14 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  