Plan Review Details - Permit 15061473
Plan Review Stops For Permit 15061473
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-11-09 Cont ID  
Sent By jwitmer Date 2015-11-09 Time 13:25 Rev Time 0.00
Received By jwitmer Date 2015-11-09 Time 13:00 Sent To E
Notes
2015-11-09 13:38:16BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15061473
 ADD: 2401 MERCER AVE. BLDG. B
 CONT: GREENVIEW CONSTRUCTION/ CHRISTOPHER TYSON
 TEL: (561)727-5013
 E-MAIL: [email protected]
  
 5TH EDITION OF THE FLORIDA BUILDING CODE (2014)
 5TH EDITION OF THE EXISTING BUILDING CODE (2014)
  
 5TH EDITION OF THE EXISTING BUILDING CODE LEVEL II
 801.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. NOV. 09/ 2015
  
 ACTION: BUILDING PROVISO
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
  
 1) SHEET A-2 :
  
 1) SHEET A-2 SHOWS IN CLASSROOM # 4 A NEW EGRESS
 WINDOW. PROVIDE PRODUCT APPROVAL BEFORE THE 1ST
 INSPECTION.
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(B) WINDOWS
  
 2) 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-07-10 Cont ID  
Sent By jwitmer Date 2015-07-10 Time 16:25 Rev Time 0.00
Received By jwitmer Date 2015-07-10 Time 12:01 Sent To  
Notes
2015-07-10 13:27:50BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15061473
 ADD: 2401 MERCER AVE. BLDG. B
 CONT: GREENVIEW CONSTRUCTION/ CHRISTOPHER TYSON
 TEL: (561)727-5013
 E-MAIL: [email protected]
  
 5TH EDITION OF THE FLORIDA BUILDING CODE (2014)
 5TH EDITION OF THE EXISTING BUILDING CODE (2014)
  
 5TH EDITION OF THE EXISTING BUILDING CODE LEVEL II
 801.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JULY 10/ 2015
 ACTION: DENIED
  
 1) SHEET A-2 :
  
 1A) THE PLANS INDICATE THEY WERE DESIGNED TO THE 2010
 FBC. AS OF JUNE 30/ 2015 THE 5TH EDITION OF THE FLORIDA
 BUILDING CODE (2014) WAS ADOPTED STATE WIDE.
  
 1B) THIS SHEET ALSO INDICATES THIS IS A LEVEL II
 ALTERATION. BUILDING A, THIS IS CONSIDERED A "CHANGE OF
 OCCUPANCY", IN 2005-2008 ART STUDIO, THEN IN 2008-2009
 IT WAS A RETAIL STORE AND IN2011-2012 A BUSINESS
 OCCUPANCY AS A CONTRACTING OFFICE. THE BUILDING WILL
 NEED TO COMPLY WITH THE 5TH EDITION FBC-EXISTING
 BUILDING CHAPTER 10 CHANGE OF OCCUPANCY. NOTE IN THE
 EXISTING BUILDING CODE CHAPTERS HAVE BEEN MOVED.
  
 1C) UNDER THE 5TH EDITION OF THE FBC- EXISITNG BUILDING
 CODE 301.1 ALL EXISITNG BUILDINGS SHALL COMPLY WITH ONE
 OF THE METHODSLISTED IN SECTION 301.1.1 THROUGH 301.1.3
 AS SELECTED BY THE APPLICANT.
  
 2) SHEET A-2 INDICATES A STORAGE OCUPANCY BUT THE TYPE
 OF STORAGE IS NOT DECLARED S1 OR S2? MAY REQUIRE A 2 HR
 OCCUPANCY SEPARATION WALL. 2014 FBC-B TABLE 508.4.
  
 3) SHEET A-2 INDICATES A NEW RATED WALL BETWEEN THE
 STORAGE OCCUPANCY & EDUCATIONAL OCCUPANCY, PLEASE
 PROVIDE A RATED WALL ASSEMBLY TYPE. 2010 FBC-B 707.5
 CONTINUITY.
  
 4) SHEET A-2 THE EXIT ACCESS CORRIDOR BETWEEN
 CLASSROOMS 4 & 6 IS 5 FEET WIDE. PLEASE REVIEW TABLE
 1018.2 (2014) FBC-B.
  
 5) SHEET A-2 CLASSROOM 2 & 4 BOTH HAVE ROLLED DOWN THE
 PART OF A OCCUPANT. WHEN THERE IS A PART OF AN OCCUPANT
 IN FIGURING THE OCCUPANT LOAD FOR A ROOM, YOU ALWAYS
 ROUND UP TO THE NEXT WHOLE NUMBER. 2014 FBC-B 1004.1.1.
  
 6) SHEET A-2 SHOWS IN CLASSROOM # 4 A NEW EGRESS
 WINDOW. PLEASE PROVIDE THE PRODUCT APPROVAL FOR THE NEW
 WINDOW. SHOW COMPLIANCE WITH:
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(B) WINDOWS
  
 7) 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 8) PLEASE SHOW COMPLIANCE WITH:
 8A) 2014 FBC-B 468.3.2. GLARE FROM NATURAL LIGHT.
  
 8B) 2014 FBC-B 468.3.7.5 GLARE ELIMINATION.
  
 8C) 2014 FBC-B 468.3.5.5 WALLS
  
 8D) 2014 FBC-B 468.3.7.4 ILLUMINATION FAILURE OF
 GENERAL AND MEANS OF EGRESS LUMINARIS.
  
 8E) 2014 FBC-B 468.2.3 OUTDOOR WASTE CONTAINERS.
  
 9) THE STORAGE ROOM MAY NEED TO COMPLY WITH 2014 FBC-B
 468.3.6.5. CHEMICAL STORAGE.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-11-18 Cont ID  
Sent By albarran Date 2015-11-18 Time 13:54 Rev Time 0.00
Received By albarran Date 2015-11-18 Time 12:32 Sent To I
Notes
2015-11-18 14:05:15THE ELECTRICAL COMMENTS HAVE NOT BE ADDRESSED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-07-23 Cont ID  
Sent By albarran Date 2015-07-23 Time 12:02 Rev Time 0.00
Received By albarran Date 2015-07-23 Time 11:47 Sent To I
Notes
2015-07-23 12:20:23PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 1. NEC 220.16 (B) OTHER THAN DWELLING UNITS. LOADS FOR
 NEW CIRCUITS OR EXTENDED CIRCUITS IN OTHER THAN
 DWELLING UNITS SHALL BE CALCULATED IN ACCORDANCE WITH
 EITHER 220.12 OR 220.14, AS APPLICABLE.
 2. NEC 230.70(B) MARKING. EACH SERVICE DISCONNECT SHALL
 BE PERMANENTLY MARKED TO IDENTIFY IT AS A SERVICE
 DISCONNECT.
 3. NEC 408.4 EVERY CIRCUIT AND CIRCUIT MODIFICATION
 SHALL BE LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT,
 AND SPECIFIC PURPOSE OR USE. THE IDENTIFICATION SHALL
 INCLUDE SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS.
 4. PER FBC EMERGENCY LIGHTING IS REQUIRED.
 5. COMPLIANCE WITH FBC-ENERGY SECTION 505 IS REQUIRED.
 6. PROVIDE A DETAIL OF THE ATTACHMENT FOR THE NEW
 LUMINARIES AS PER THE REQUIREMENTS OF NEC 410.PART IV
 7. SEPARATE FIRE ALARM DRAWINGS AND PERMITS ARE
 REQUIRED.
 8. MANUAL FIRE ALARM PULL BOX REQUIRED WITHIN 5' OF
 EVERY EXIT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-11-04 Cont ID  
Sent By pleduc Date 2015-11-04 Time   Rev Time 0.00
Received By pleduc Date 2015-11-04 Time 15:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-07-06 Cont ID  
Sent By Lindow Date 2015-07-06 Time   Rev Time  
Received By   Date 2015-07-06 Time   Sent To  
Notes
2015-07-06 15:02:35EXIT DOORS CAN'T OPEN INTO EACH OTHER.
 CORRIDOR IS NOT 6FT WIDTH.
 PAGES ARE NOT BOUND.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-11-18 Cont ID  
Sent By albarran Date 2015-11-18 Time 14:07 Rev Time 0.00
Received By albarran Date 2015-11-02 Time 15:19 Sent To  
Notes
2015-11-18 14:09:0811/18/15 FAILED ELECTRICAL REVIEW BECAUSE NONE OF THE
 ELECTRICAL COMMENTS HAVE BEEN ADDRESSED. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT TO SMALL DENIED BIN "G". MA
2015-11-02 15:19:57B39

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-23 Cont ID  
Sent By albarran Date 2015-07-23 Time 12:21 Rev Time 0.00
Received By albarran Date 2015-06-30 Time 09:20 Sent To  
Notes
2015-07-23 12:22:437/23/15 - FAILED ALL REVIEWS. CONTRACTOR NOTIFIED VIA
 EMAIL. SENT TO SMALL DENIED BIN "G". MA

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2015-11-09 Cont ID  
Sent By jwitmer Date 2015-11-09 Time   Rev Time 0.00
Received By jwitmer Date 2015-11-09 Time   Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-07-10 Cont ID  
Sent By jwitmer Date 2015-07-10 Time 16:26 Rev Time 0.00
Received By jwitmer Date 2015-07-10 Time 16:26 Sent To  
Notes
2015-07-10 16:26:18BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-11-06 Cont ID  
Sent By ccole Date 2015-11-06 Time 15:30 Rev Time 0.00
Received By ccole Date 2015-11-06 Time 15:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-07-08 Cont ID  
Sent By ccole Date 2015-07-08 Time 17:30 Rev Time 0.00
Received By ccole Date 2015-07-08 Time 17:25 Sent To  
Notes
2015-07-08 17:42:401ST REVIEW: FBC 2014 MECHANICAL
  
 1) SHEET A3: SHOW THE SUPPLY DUCT SIZE AND DUCT RUN TO
 THE RELOCATED DIFFUSER IN CLASSROOM #5. INDICATE THE
 CFM SUPPLY AMOUNT AT THE DIFFUSER.
 2) PROVIDE CALCULATIONS VERIFYING COMPLIANCE WITH
 SECTION 809.2 FBC-14 EXISTING BUILDING- ALTERED
 EXISTING SYSTEMS: MECHANICAL VENTILATION SYSTEMS THAT
 ARE ALTERED, RECONFIGURED, OR EXTENDED SHALL PROVIDE
 NOT LESS THAN 5 CUBIC FEET PER MINUTE PER PERSON OF
 OUTDOOR AIR AND NOT LESS THAN 15 CFM OF VENTILATION AIR
 PER PERSON; OR NOT LESS THAN THE AMOUNT OF VENTILATION
 AIR DETERMINED BY THE INDOOR QUALITY PROCEDURE OF
 ASHRAE 62.1- 2010.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-11-03 Cont ID  
Sent By gjohnson Date 2015-11-03 Time 14:44 Rev Time 0.00
Received By gjohnson Date 2015-11-03 Time 14:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-07-14 Cont ID  
Sent By tklarge Date 2015-07-14 Time 06:44 Rev Time 0.00
Received By tklarge Date 2015-07-14 Time 05:21 Sent To  
Notes
2015-07-14 06:44:501) THE PLANS SHOW A STORAGE AREA. INDICATE ON THE PLANS
 WHAT TYPE OF ITEMS WILL BE STORED IN THIS AREA. WPB
 AMEND. TO FBC SEC. 107.2.1.
 2) SHT. A-2 - THE BUILDING SQ. FT. SUMMARY TABLE FOR
 BUILDING "B" SHOWS A "TEACHER PLANNING AREA." THIS AREA
 IS NOT IDENTIFIED ON THE PLANS. CLARIFY.
 3) SHT. A-2 - BUILDING SQUARE FOOT SUMMARY TABLE -
 LISTS AN "UNASSIGNED" AREA. PLEASE CLARIFY AS TO WHAT
 THIS SPACE IS AND WHERE IT IS. WPB AMEND. TO FBC SEC.
 107.2.1.
 4) THE PERMIT APPLICATION IS ONLY FOR BUILDING "B". WHY
 HAS INFORMATION FOR BUILDING "A" BEEN SUBMITTED?
 CLARIFY.
 5) A SERVICE SINK IS REQUIRED PER THE 2014
 FBC-PLUMBING, TABLE 403.1.
 6) SUBMIT A SANITARY AND WATER RISER FOR ANY CHANGES
 BEING MADE TO THE PLUMBING SYSTEM. WPB AMEND. TO FBC
 SEC.107.3.5.1.3. SUBMIT A NARRATIVE THAT CLEARLY
 EXPLAINS THE SCOPE OF WORK TO BE DONE IN THIS
 BUILDING.WPB AMEND. TO FBC SEC. 107.2.1.
 7) SHOW THE LOCATION OF THE WATER HEATER IN THE
 BUILDING. WPB AMEND. TO FBC SEC. 107.2.1.
 8) THE LEADING EDGE OF THE HIGH DRINKING FOUNTAIN MAY
 HAVE IT'S LEADING EDGE MORE THAN 27 INCHES ABOVE THE
 FINISH FLOOR WHICH WOULD ONLY ALLOW IT PROTRUDE INTO
 THE CIRCULATION PATH A MAXIMUM OF 4 INCHES PER THE 2010
 FBC-ACCESSIBILITY, SEC.307.2. A SKIRT MAY HAVE TO BE
 ADDED TO THE BOTTOM OF THE DRINKING FOUNTAIN TO BRING
 THE LEADING EDGE BELOW 27 INCHES.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  