Plan Review Details - Permit 15061471
Plan Review Stops For Permit 15061471
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-07-14 Cont ID  
Sent By jwitmer Date 2015-07-14 Time 12:15 Rev Time 0.00
Received By jwitmer Date 2015-07-14 Time 08:00 Sent To  
Notes
2015-07-14 12:11:08BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15061471
 ADD: 6208 GEORGIA AVE.
 CONT: TBD
 TEL: (561)585-9211
 E-MAIL: [email protected]
  
 2014 FBC-B / 5TH EDITION OF THE FLORIDA BUILDING CODE
 2014 EXISTING BUILDING CODE LEVEL II 801.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JULY 14/ 2015
 ACTION: DENIED
  
 1) THIS PERMIT CAME IN AS A OWNER/ BUILDER PERMIT. THE
 PERMIT APPLICATION AS OWNER LIST A GEORGIA AVE PB LLC
 AS OWNER AND AUDRIA QUIST. ON THE OWNER/ BUILDER FORM
 THE OWNER IS LISTED AS CHAD QUIST. PLEASE NOTE THE P.
 B. C. PROPERTY APPRAISERS OFFICE SHOWS THE PROPERTY
 SOLD LAST JUNE/ 2014 TO A GEORGIA AVE P B LLC. IF THE
 CURRENT OWNER HAS BOUGHT IT SINCE THEN THEY WILL NEED
 TO SUBMIT DOCUMENTATION THAT THEY ARE THE CURRENT
 OWNERS. A CORPORATION, OR A LLC CAN NOT PULL PERMITS
 SINCE THEY AS A OWNER CAN NOT APPEAR AS A INDIVIDUAL.
 FL. S. 489.103. THE OTHER ISSUE THIS IS A 2 STORY
 COMMERCIAL BUILDING WITH 2 OFFICES UPSTAIRS THAT HAVE
 PULLED SEPARATE OCCUPATIONAL LICENSES
 (BUSINESS TAX). OWNER /BUILDERS CAN NOT RENT OR LEASE
 OUT THE PROPERTY UNDER A OWNER BUILDER PERMIT.
  
 2) THE PLANS INDICATE THEY WERE DESIGNED TO THE 2010
 FBC. THE FIFTHED EDITION OF THE FLORIDA BUILDING CODE
 (2014) WAS ADOPTED AND IN AFFECT STATE WIDE ON JUNE 30/
 2015, THE SAME DAY THESE PLANS WERE SUBMITTED. PLEASE
 REVISE TO THE CURRENT EDITION OF THE FBC 2014 EDITION.
  
 3) PLEASE NOTE THE PLANS INDICATE WORK IS ONLY BEING
 COMPLETED ON THE 1ST FLOOR. SHEET 1.1 INDICATES
 EXISTING / PROPOSED. PLEASE PROVIDE A EXISTING FLOOR
 PLAN AND A PROPOSED FLOOR PLAN OF THE 1ST FLOOR.
 107.3.5.1.1.1 COMMERCIAL BUILDINGS. FLOOR PLANS.
  
 4) PLEASE PROVIDE COMPLIANCE WITH THE 2014 EXISTING
 BUILDING CODE 806.1 A BUILDING OR ELEMENT THAT IS
 ALTERED SHALL COMPLY WITH THE PROVISIONS OF THE FLORIDA
 BUILDING CODE. 2014 FL. ACCESSIBLITY CODE 202.4.1
 DISPROPORTIONATE COST, PLEASE SHOW WHERE 20% OF THE
 CONTRACT VALUE WILL BE SPENT IN ACCESSIBLE UPGRADES IN
 THE ORDER STATED IN 202.4.1.
 4A) PLEASE SHOW COMPLIANCE WITH AN ACCESSIBLE ENTRANCE.
 2014 FL ACCESSIBILITY CODE206.2.4 SPACES & ELEMENTS &
 402.2 ACCESSIBLE ROUTES.
  
 4B) THE RESTROOM AS SHOWN DOES NOT COMPLY WITH THE 2014
 FL ACCESSIBLITY CODE, SEE 604.3.2.
  
 4C) THE BREAK ROOM SINK DOES NOT ALLOW FOR A SIDE NOR
 FRONT APPROACH. SEE 2014 FL ACCESSIBILITY CODE 606.1-5.
  
 5) SHEET 1.1 & 1.3 BOTH SHOW A DOORWAY BEING CHANGED
 INTO A NEW WINDOW. PLEASE REVIEW THE 2014 FBC-B 1026.6
 REQUIRES THE EXTERIOR WALL TO BE A 1 HOUR FIRE RATING
 BECAUSE OF THE EXTERIOR STAIRS. SHEET 1.1 SHOWS (2)
 TENANTS ON THE 2ND FLOOR BOTH WITH ONLY (1) MEANS OF
 EGRESS FOR BOTH. PLEASE NOTE THAT THE 2 STAIRS CAN ONLY
 COUNT AS 1 SICNE THEY DO NOT END AT 1/2 THE DISTANCE
 APART.
  
 6) SHEET 1.1 & 1.3 THE DOORWAY ON THE EAST SIDE OF THE
 BUILDING THAT IS BEING CHANGED INTO A WINDOW WILL NEED
 TO BE EITHER IN COMPLIANCE WITH 2014 FBC-B 716.5 &
 TABLE 716.5 OF 3/4 HR. THE NEW ENTRY DOOR AND SIDE
 LIGHTS WILL ALSO NEED TO MEET THIS SAME REQUIREMENT
 SINCE THEY ARE WITHIN 10'-0" OF THE STAIRS.
  
 7) PLEASE ALSO NOTE THE 2 FIRE RATED OPENINGS WILL NEED
 TO EITHER HAVE FIRE RATED GLAZING, THERE ARE VERY FEW
 PRODUCTS THAT HAVE FIRE RATED GLAZING AND LARGE MISSILE
 TESTED GLAZING UNITS. EITHER STORM SHUTTERS OR FIRE
 SHUTTERS WILL BE REQUIRED. A FIRE SHUTTER CAN NOT BE
 USED OVER THE ONLT MEANS OF EGRESS. FOR A FIRE SHUTTER
 TO BE INSTALLED FOR THE NEW CORNER WINDOW IT WILL BE
 REQUIRED TO BE ACTIVATED BY A FIRE ON THE INTERIOR OF
 THE BUILDING.
  
 8) SHEET 1.3 SHOWS THE NEW WINDOW TO HAVE PRESSURES OF
 +44.5/ -48.3. FOR ZONE 5 FOR 20 SQ. FT. THE PRESSURES
 FOR 170 MPH, VULT, EXPOSURE C, MEAN ROOF HEIGHT OF 20
 FT.,
 +38.6/ -50.4 VASD. THE NEGATIVE PRESSURES ARE LOW, FOR
 WALL ZONE # 5 END ZONE.
  
 9) 2014 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-07-16 Cont ID  
Sent By dhayes Date 2015-07-16 Time 16:25 Rev Time 0.00
Received By dhayes Date 2015-07-16 Time 16:00 Sent To  
Notes
2015-07-16 16:21:137/16/2015
 PROJECT: OFFICE RENNOVATION
 PERMIT#: 15061471
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC,
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER ONE,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) PROVIDE A PANEL SCHEDULE AND INDICATE THE OCPD AND
 WIRE SIZES. EVERY CIRCUIT AND CIRCUIT MODIFICATION
 SHALL BE LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT,
 AND SPECIFIC PURPOSE OR USE. NEC 408.4
  
 2) INDICATE THE REQUIRED A/C DISCONNECTS FOR NEW
 MECHANICAL EQUIPMENT. NEC 440.14 INCLUDE THE CIRCUIT
 AND DISCONNECT REQUIRED FOR THE DUCTLESS WALL MOUNT
 INDOOR UNIT
  
 3) PROVIDE A GFI RECEPTACLE OUTLET AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING, AIR
 CONDITIONING, AND REFRIGERATION EQUIPMENT. 210.63
  
 4) INDICATE GFI PROTECTION FOR THE RECEPTACLES
 INSTALLED WITHIN 6 FT OF THE OUTSIDE EDGE OF THE SINK.
 210.8(B)(5)
  
 5) PROVIDE A LIGHTING PLAN AND INCLUDE THE EGRESS
 LIGHTING REQUIRED BY NFPA 101 SECTION 7.10.1.5.1
  
 6) INDICATE THE REQUIRED CIRCUITRY FEEDING THE EGRESS
 LIGHTING IN COMPLIANCE WITH THE NEC 700.12
  
 7) INDICATE THE REQUIRED SIGN CIRCUIT IN COMPLIANCE
 WITH THE NEC 600.5 AND TIMER IN COMPLIANCE WITH THE
 FBC-E 505.2.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-07-08 Cont ID  
Sent By Lindow Date 2015-07-08 Time   Rev Time 0.00
Received By rlindow Date 2015-07-08 Time   Sent To  
Notes
2015-07-08 18:01:49PROVISO
 CHANGE EXIT LIGHTS TO EMERGENCY LIGHT/EXIT COMBINATION
 WITH BATTERY BACK UP. SEE PLANS FOR NOTES.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-16 Cont ID  
Sent By dhayes Date 2015-07-16 Time 16:25 Rev Time 0.00
Received By dhayes Date 2015-06-30 Time 09:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-07-16 Cont ID  
Sent By ccole Date 2015-07-16 Time 09:55 Rev Time 0.00
Received By ccole Date 2015-07-16 Time 09:55 Sent To  
Notes
2015-07-16 10:37:121ST REVIEW: FBC 2014 MECHANICAL
 7/16/15
  
 1) THE SUBMITTED ENERGY GAUGE FORM 506-2010 IS
 OUTDATED. THE FBC-2014 FIFTH EDITION OF THE ENERGY
 CONSERVATION CODE WENT INTO EFFECT ON JUNE 30, 2015, ON
 THE DAY OF THIS PERMIT APPLICATION. PLEASE SEE SECTION
 C101.5 FOR ACCEPTABLE COMPLIANCE FORMS.
 2) REVISE THE AC PLAN ON SHEET 3.1 TO SHOW THE 4 ZONES
 AS INDICATED IN THE SUBMITTED WRIGHTSOFT AC LOAD
 CALCULATIONS.
 3) PLEASE ADJUST THE AC CALCULATIONS TO SHOW THE
 CORRECT DESIGN TEMPERATURES PER THE ASHRAE FUNDAMENTALS
 HANDBOOK: WPB SUMMER DRY BULB- 91, WET BULB- 78.
 4) ADJUST THE AC CALCULATIONS TO INDICATE INTERNAL HEAT
 GAIN LOADS.
 5) PLEASE REVIEW SECTION 809.1 FBC-14 EXISTING
 BUILDING, AND PROVIDE A MINIMUM VENTILATION RATE
 CALCULATION ON THE PLAN FOR THE RECONFIGURED ROOMS AND
 SPACES- REFERENCE TABLE 403.3 FBC-14 MECHANICAL. PLEASE
 NOTE THE CURRENT PLAN IS NOT INDICATING A MEANS OF O/A
 SUPPLY: PLEASE CORRECT.
 6) SHEET 3.1: PLACE THE MODEL NUMBERS OF THE INDOOR
 UNITS AT THEIR CORRESPONDING LOCATIONS ON THE PLAN.
 7) SHEET 3.1: THE NEW CU SHALL BE ANCHORED TO RESIST
 WIND LOADS PER SECTION 301.15 FBC-10 MECH. REFER TO
 SECTION 1609 FBC-10 BUILDING AND STRUCTURAL DETAILS FOR
 THE PAD, AND TIE DOWN OF THE UNIT.
 8) SHEET 3.1: PROVIDE CONDENSATE DISPOSAL DETAILS FOR
 THE INDOOR UNITS. SHOW THE TYPE AND SIZE OF PIPE, PIPE
 RUNS, AND DISCHARGE LOCATIONS- SEE SECTION 307.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  