Plan Review Details - Permit 15061462
Plan Review Stops For Permit 15061462
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-09-27 Cont ID  
Sent By jwitmer Date 2015-09-27 Time 08:59 Rev Time 0.00
Received By jwitmer Date 2015-09-27 Time 07:59 Sent To  
Notes
2015-09-27 08:33:29BUILDING PLAN REVIEW
 W. P. B. PERMIT:15061462
 ADD: 1500 CLARE AVE.
 CONT: FLORIDA FILTRATION
 TEL: (561)582-5543
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: SUN. SEPT. 27/ 2015
 ACTION: PROVISO
  
 2) SHEET B-4 SHOWS A DETAIL WHERE CEILING JOIST/
 RAFTERS WITH ONE CEILING JOIST/ RAFTER IS CUT AND
 HEADERS ATTACHED. PLEASE PROVIDE TYPE OF HANGER OR
 BUCKET USED TO INSTALL THE HEADER JOIST PROVIDE AT TIME
 OF INSPECTION TO THE CITY BUILDING INSPECTOR.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-09-04 Cont ID  
Sent By jwitmer Date 2015-09-04 Time 09:57 Rev Time 0.00
Received By jwitmer Date 2015-09-04 Time 07:02 Sent To  
Notes
2015-09-04 09:57:50BUILDING PLAN REVIEW
 W. P. B. PERMIT:15061462
 ADD: 1500 CLARE AVE.
 CONT: FLORIDA FILTRATION
 TEL: (561)582-5543
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. SEPT. 04/ 2015
 ACTION: DENIED
  
 NOTICE!!!!!!!!!!!!!!!!!!!!!!!!!!! CHAPTER 553.80(2)(B)
 FLORIDA STATUTES STATES THAT A LOCAL GOVERNMENT SHALL
 IMPOSE A FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF
 PLANS ARE REJECTED (3) OR MORE TIMES FOR REPEATED
 FAILURE TO CORRECT A CODE VIOLATION.
  
 1A) NEW COMMENT, THERE IS A DISCREPANCY IN THE
 PLANS.SHEET B1. THE PLANS SHOW THE FLOOR LAYOUT OF 2
 NEW SPRAY BOOTHS AND A MIXING ROOM WHERE THERE IS
 ANOTHER DETAIL SHOWING A SINGLE SPRAY BOOTH AND MIXING
 ROOM ATTACHED. PLEASE REPRESENT THE ACTUAL LAYOUT NOT A
 GENERIC SHEET THAT COVERS ALL INSTALLATIONS.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS..
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES.
  
 1B) SHEET B-2 SHOWS A FULLY ENCLOSED SPRAY BOOTH, THE
 GFS INSTALLATION & MAINTENANCE MANUAL IS FOR A
 DIFFERENT MODEL, A OPEN FACE BOOTH NOT MEETING THE
 REQUIREMENTS OF 2014 FBC-B 416.4 SPRAY BOOTHS. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES.
  
 1C) ATTACHED AMEREX FIRE SUPRESSION SYSTEM IS FOR A
 PREVIOUS JOB. DATED 11/25/2013 (WHITED-OUT) NEW STICKER
 APPLIED DATED JUNE 23/ 2015 ADDRESS LOCATION 3076 SE
 DOMINICA TER. STUART, FL. 2010 FBC-B [F] 416.5 FIRE
 PROTECTION.
 AN AUTOMATIC SPRINKLER SYSTEM OR FIRE-EXTINGUISHING
 SYSTEM SHALL BE PROVIDED IN ALL SPRAY, DIP AND
 IMMERSING SPACES AND STORAGE ROOMS AND SHALL BE
 INSTALLED IN ACCORDANCE WITH CHAPTER 9.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS..
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES.
  
  
 COMMENT # 1 1ST REVIEW.THE PLAN LABELED B-1 SHOWS THE
 SPRAY BOOTH AGAINST THE EXTERIOR WALL. THE 2014 FBC-B
 416.4 SPRAY BOOTHS SHALL BE DESIGNED, CONSTRUCTED AND
 OPERATED IN ACCORDANCE WITH THE FLORIDA FIRE PREVENTION
 CODE. THE PLAN SHOWS THE SPRAY BOOTH AGAINST THE
 EXTERIOR WALLS.
 NFPA 33 5.3 REQUIRES THE SPRAY BOOTH TO BE A 1 HOUR
 CONSTRUCTION AND AT LEAST 3 FEET AWAY FROM THE EXTERIOR
 WALL. EXCEPTION # 2 WILL ALLOW THE UNIT TO BE CLOSER
 THAN 3 FT IF THE SPRAY BOOTH CAN BE MAINTAINED AND
 CLEANED. PLEASE PROVIDE THE MANUFACTURERS
 SPECIFICATIONS FOR THE ONE HOUR FIRE RATING AS WELL AS
 SHOWING HOW THE UNIT WILL BE MAINTAINED AND KEPT CLEAN.
  
 2) COMPLIED. SHEET B-2 SHOWS A DETAIL WHERE CEILING
 JOIST/ RAFTERS WITH ONE CEILING JOIST/ RAFTER IS CUT
 AND HEADERS ATTACHED. THE PLANS FAIL TO SHOW COMPLIANCE
 WITH 2014 FBC-B 2308.10.4.3 FRAMING AROUND HOLES.
 TRIMMERS AND HEADERS RAFTERS SHALL BE DOUBLED, OR OF
 LUMBER OF EQUIVALENT CROSS SECTION, WHERE THE SPAN OF
 THE HEADER EXCEEDS 4 FEET. THE PLANS DO NOT INDICATE
 WHAT THE DOUBLE LINES REPRESENT, THE OUTER BAND IS PAST
 THE FRAMING MEMBER WHICH WILL REQUIRE THE FRAMING
 HEADER TO GO TO THE NEXT RAFTER. THE PLANS ALSO WILL
 NEED TO INDICATE THE TYPE OF HANGER/ BUCKET TO BE USED
 IN THIS INSTALATION FOR BOTH THE HEADER AND THE CUT
 RAFTERS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-07-27 Cont ID  
Sent By jwitmer Date 2015-07-27 Time 13:50 Rev Time 0.00
Received By jwitmer Date 2015-07-27 Time   Sent To  
Notes
2015-07-27 14:54:20BUILDING PLAN REVIEW
 W. P. B. PERMIT:15061462
 ADD: 1500 CLARE AVE.
 CONT: FLORIDA FILTRATION
 TEL: (561)582-5543
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JULY 27/ 2015
 ACTION: DENIED
  
 1) THE PLAN LABELED B-1 SHOWS THE SPRAY BOOTH AGAINST
 THE EXTERIOR WALL. THE 2014 FBC-B 416.4 SPRAY BOOTHS
 SHALL BE DESIGNED, CONSTRUCTED AND OPERATED IN
 ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE. THE
 PLAN SHOWS THE SPRAY BOOTH AGAINST THE EXTERIOR WALLS.
 NFPA 33 5.3 REQUIRES THE SPRAY BOOTH TO BE A 1 HOUR
 CONSTRUCTION AND AT LEAST 3 FEET AWAY FROM THE EXTERIOR
 WALL. EXCEPTION # 2 WILL ALLOW THE UNIT TO BE CLOSER
 THAN 3 FT IF THE SPRAY BOOTH CAN BE MAINTAINED AND
 CLEANED. PLEASE PROVIDE THE MANUFACTURERS
 SPECIFICATIONS FOR THE ONE HOUR FIRE RATING AS WELL AS
 SHOWING HOW THE UNIT WILL BE MAINTAINED AND KEPT CLEAN.
  
 2) SHEET B-2 SHOWS A DETAIL WHERE CEILING JOIST/
 RAFTERS WITH ONE CEILING JOIST/ RAFTER IS CUT AND
 HEADERS ATTACHED. THE PLANS FAIL TO SHOW COMPLIANCE
 WITH 2014 FBC-B 2308.10.4.3 FRAMING AROUND HOLES.
 TRIMMERS AND HEADERS RAFTERS SHALL BE DOUBLED, OR OF
 LUMBER OF EQUIVALENT CROSS SECTION, WHERE THE SPAN OF
 THE HEADER EXCEEDS 4 FEET. THE PLANS DO NOT INDICATE
 WHAT THE DOUBLE LINES REPRESENT, THE OUTER BAND IS PAST
 THE FRAMING MEMBER WHICH WILL REQUIRE THE FRAMING
 HEADER TO GO TO THE NEXT RAFTER. THE PLANS ALSO WILL
 NEED TO INDICATE THE TYPE OF HANGER/ BUCKET TO BE USED
 IN THIS INSTALATION FOR BOTH THE HEADER AND THE CUT
 RAFTERS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2015-08-19 Cont ID  
Sent By albarran Date 2015-08-19 Time 14:31 Rev Time 0.00
Received By albarran Date 2015-08-17 Time 16:48 Sent To I
Notes
2015-08-19 14:31:52SEE PERMIT 15080142

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2015-11-23 Cont ID  
Sent By Mgonzale Date 2015-11-23 Time   Rev Time 1.00
Received By mgonzale Date 2015-11-23 Time   Sent To ENG
Notes
2015-10-11 12:35:03REVIEW FOR UNITY OF TITLE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2015-09-18 Cont ID  
Sent By pleduc Date 2015-09-18 Time   Rev Time 0.00
Received By pleduc Date 2015-09-18 Time 10:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-08-24 Cont ID  
Sent By pleduc Date 2015-08-24 Time   Rev Time 0.00
Received By pleduc Date 2015-08-24 Time 12:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-07-07 Cont ID  
Sent By pleduc Date 2015-07-07 Time   Rev Time 0.00
Received By pleduc Date 2015-07-07 Time 14:13 Sent To  
Notes
2015-07-07 14:56:18THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) PROVIDE BOOTH MANUFACTURER'S SPEC SHEETS.
  
 2) PROVIDE MANUFACTURER'S JUSTIFICATION FOR APPLYING
 THE EXCEPTION FOR 3' SPACE AROUND THE SIDES OF THE
 BOOTHS.
  
 3) HOW WOULD A REPAIR TAKE PLACE ALONG A WALL SECTION
 AGAINST A WALL?
  
 4) HOW WOULD THE ACCUMULATION OF DUST AND DEBRI TAKE
 PLACE ALONG A WALL SECTION AGAINST A WALL?
  
 5) THE MIXING ROOM SHALL COMPLY WITH ALL REQUIRMENTS OF
 NFPA 33 8.3,
  
 6) PROVIDE DIMENSIONS OF THE MIXING ROOM
  
 7) PROVIDED THE MIXING ROOM WITH A AUTOMATIC FIRE
 PROTECTION SYSTEM.
  
 8) PROVIDE A FE INSIDE THE MIXING ROOM. PER NFPA 10
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-09-27 Cont ID  
Sent By jwitmer Date 2015-09-27 Time 08:59 Rev Time 0.00
Received By jwitmer Date 2015-09-16 Time 13:36 Sent To  
Notes
2015-09-16 13:37:23C02

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-04 Cont ID  
Sent By jwitmer Date 2015-09-04 Time 09:58 Rev Time 0.00
Received By jwitmer Date 2015-08-20 Time 09:12 Sent To  
Notes
2015-08-21 09:12:11C10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-19 Cont ID  
Sent By albarran Date 2015-08-19 Time 14:32 Rev Time 0.00
Received By albarran Date 2015-06-30 Time 10:26 Sent To  
Notes
2015-08-19 14:37:428/19/15 - COMPLETED THE REVIEW CYCLE AND IS NOW READY
 FOR CORRECTIONS. CONTRACTOR NOTIFIED VIA EMAIL. SENT TO
 SMALL DENIED BIN "F". MA
2015-06-30 13:43:50ROUTED TO MECHANICAL OVER $5000

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2015-11-23 Cont ID  
Sent By ccole Date 2015-11-23 Time 16:31 Rev Time 0.00
Received By ccole Date 2015-11-23 Time 16:31 Sent To  
Notes
2015-11-23 16:38:49MECHANICAL PASSED 11/23/15 BY CHRISTOPHER LEE COLE
 THE LIMITED CLEARANCE OF 20 FT. FROM THE PAINT SPRAY
 BOOTH EXHAUST TERMINATION TO THE RAILROAD PROPERTY LINE
 WAS APPROVED BY BUILDING OFFICIAL ROBERT BROWN AND
 CHIEF PLANS EXAMINER STEVE KENNEDY.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2015-09-23 Cont ID  
Sent By ccole Date 2015-09-23 Time 15:05 Rev Time 0.00
Received By ccole Date 2015-09-23 Time 15:04 Sent To  
Notes
2015-09-23 15:14:013RD REVIEW: FBC 2010 MECHANICAL
 PERMIT #15061462
 9/23/15
  
 1) SHEET B-4: THE REVISED PLAN IS INDICATING A 23'
 CLEARANCE DISTANCE FROM THE TWO PAINT BOOTH EXHAUST
 DUCT TERMINATIONS TO TO THE REAR PROPERTY LINE- MINIMUM
 30' CLEARANCE IS REQUIRED IN ACCORDANCE WITH SECTION
 501.3.1 FBC-10 MECHANICAL ITEM #1. PLEASE RELOCATE THE
 TERMINATIONS TO BE IN COMPLIANCE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-09-01 Cont ID  
Sent By ccole Date 2015-09-01 Time 13:29 Rev Time 0.00
Received By ccole Date 2015-09-01 Time 13:29 Sent To  
Notes
2015-09-01 14:33:252ND REVIEW: FBC 2010 MECHANICAL
 PERMIT #15061462
 9/1/15
  
 1) THE SUBMITED AMEREX FIRE SUPPRESSION SYSTEM PLAN HAS
 A STUART FL. PROJECT ADDRESS AND THE BOOTH DIMENSIONS
 DO NOT MATCH THE BOOTH DIMENSIONS SHOWN ON THE MAIN
 SPRAY BOOTH PLAN- PLEASE PROVIDE THE CORRECT
 SUPPRESSION PLAN.
 2) THE SUBMITTED MANUAL FOR THE GFS SPRAY BOOTH HAS CUT
 SHEETS AT THE BACK FN THE DOCUMENT (PAGES 1-6) WITH
 PRINT TOO SMALL TO READ. PLEASE ENLARGE THESE PAGES.
 3) THE MODEL NUMBER AND SPECIFICATIONS FOR THE SPRAY
 BOOTH FAN THAT ARE MARKED UP ON THE SUBMITTAL
 (GFA-30VP-030) DO NOT MATCH THE MODEL NUMBER AND SPECS
 LISTED IN THE EQUIPMENT SCHEDULE (30VP-050T3T) SHEET
 B2.
 4) AS PREVIOUSLY REQUESTED IN THE1ST REVIEW, SUBMIT
 SPECS FOR THE MIXING BOOTH FAN.
 5) AS PREVIOUSLY REQUESTED PROVIDE AIR VELOCITY
 CALCULATIONS (ON THE PLAN) FOR THE SPRAY BOOTH.
 6) AS PREVIOUSLY REQUESTED PROVIDE A ROOF PLAN
 INDICATING THE REQUIRED MINIMUM CLEARANCE DISTANCES FOR
 EXHAUST TERMINATIONS TO PROPERTY LINES, AIR INTAKES,
 COMBUSTIBLE CONSTRUCTION, EXTERIOR WALLS, AND OPERABLE
 OPENINGS.
 7) THE COMMENT RESPONSE LETTER FROM FL. FILTRATION &
 SPRAY BOOTH SERVICES INDICATES ALUMINUM COMPRESSED AIR
 PIPING, HOWEVER THE PLAN INDICATES STEEL. PLEASE
 CORREECT THE PLAN AND PROVIDE A HANGER SCHEDULE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-07-01 Cont ID  
Sent By ccole Date 2015-07-01 Time 16:45 Rev Time 0.00
Received By ccole Date 2015-07-01 Time 16:45 Sent To  
Notes
2015-07-01 17:26:581ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15061462
  
 1) PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 SPRAY BOOTH, THE MIXING ROOM, THE AIR FILTERS, THE
 EXHAUST FANS, THE COMPRESSOR AND THE SPRAY EQUIPMENT
 REVIEWED AND STAMPED BY THE ENGINEER OF RECORD-
 REFERENCE NFPA 33 SECTIONS (5.1.1), )5.1.4), (7.10.1),
 (8.3.2), (11.1), (12.1).
 2) THE LOCATIONS OF THE SPRAY BOOTHS SHOWN ABUTTING THE
 EXTERIOR CONCRETE WALLS DOES NOT LEAVE AMPLE SPACE FOR
 MAINTENANCE AS REQUIRED BY SECTION 5.3.2 EXCEPTION (2)
 NFPA 33.
 3) PROVIDE EXHAUST FAN SCHEDULES ON THE PLAN FOR THE
 BOOTHS AND THE MIXING ROOM- SECTION 7.10.1.
 4) PROVIDE AIR VELOCITY CALCULATIONS FOR EACH SPRAY
 BOOTH INDICATING COMPLIANCE WITH SECTION 502.7.3.3
 FBC-14 MECHANICAL.
 5) PROVIDE AN EXHAUST VENTILATION CALCULATION FOR THE
 MIXING ROOM AND INDICATE HOW MAKE-UP AIR IS BEING
 PROVIDED. THERE IS NO LINK TO THE OVERHEAD DOOR SHOWN
 ON THE PLAN- SECTION 502.9.5.4 FBC-14 MECHANICAL.
 6) INDICATE HOW THE EXHAUST DUCTS ARE BEING SUPPORTED
 IN THE AREA BETWEEN THE TOP OF THE BOOTH AND THE ROOF
 LEVEL- SECTION 7.8 NFPA 33.
 7) REFERENCE SECTION 501.3.1(1) FBC-14 MECHANICAL AND
 PROVIDE A ROOF PLAN INDICATING THE REQUIRED MINIMUM
 CLEARANCE DISTANCES FOR EXHAUST TERMINATIONS TO
 PROPERTY LINES, AIR INTAKES, COMBUSTIBLE CONSTRUCTION,
 EXTERIOR WALLS, AND OPERABLE OPENINGS.
 8) INDICATE THE TYPE OF COMPRESSED AIR PIPING SUPPORTS
 OR HANGERS TO BE INSTALLED, AND SPACING OF THE HANGERS
 OR SUPPORTS.
 9) PROVIDE A THROUGH PENETRATION FIRE STOPPING METHOD
 FOR THE COMPRESSED AIR PIPING PENETRATING THE SPRAY
 BOOTHS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2015-09-18 Cont ID  
Sent By llouie Date 2015-09-18 Time 13:17 Rev Time 0.00
Received By llouie Date 2015-09-18 Time 13:17 Sent To  
Notes
2015-09-18 13:18:46NOTES:
  
 - VALUE OF CONSTRUCTION ($44,803) DOES NOT EXCEED 50 %
 OF IMPROVEMENT VALUE FOR 2014 PER PAPA ($96,796).
  
 - PAINT BOOTH FACILITY TO BE LOCATED WITHIN THE
 FOOTPRINT OF THE EXISTING BUILDING.

Review Stop Z ZONING
Rev No 1 Status P Date 2015-07-09 Cont ID  
Sent By llouie Date 2015-07-09 Time 08:46 Rev Time 0.00
Received By llouie Date 2015-07-09 Time 08:46 Sent To  
Notes
2015-07-09 08:50:57NOTES:
  
 - VALUE OF CONSTRUCTION ($44,803) DOES NOT EXCEED 50 %
 OF IMPROVEMENT VALUE FOR 2014 PER PAPA ($96,796).
  
 - PAINT BOOTH FACILITY TO BE LOCATED WITHIN THE
 FOOTPRINT OF THE EXISTING BUILDING.