Plan Review Details - Permit 15061460
Plan Review Stops For Permit 15061460
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-10-27 Cont ID  
Sent By jgomez Date 2015-10-27 Time 14:10 Rev Time 0.00
Received By jgomez Date 2015-10-27 Time 13:56 Sent To  
Notes
2015-10-27 14:27:5510/27/15 MET W/ OWNER AND CONTRACTOR. BECAUSE OF PLAN
 REVIEW WORK LOAD I OFFER THEM THE OPTION OF PROVISO.
 THEY AGREED FOR ISSUANCE OF PERMIT WITH PROVISO. THEY
 WILL SUBMIT ALL THE REQUIRED INFORMATION AFTER THE
 PERMIT IS ISSUED. ADVISED THEM FEES WOULD APPLY AND TO
 SUBMIT INFORMATION BEFORE INSPECTIONS TO AVOID
 CONFLICTS OR DELAYS. JG.
  
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 1- DESIGNER OF RECORD TO SPECIFY ON PLANS ROOF TILE
 FASTENING. SEC. 107.2.1.2 CITY AMENDMENTS.
 2- SHEET A.05: CODES SPECIFIED ON THE DRAINAGE
 CALCULATIONS ARE MISMATCHED. REVISE AS REQ'D.
 3- DETAIL 3/A.06: SPECIFY HANDRAIL HEIGHT & OPENING
 LIMITATIONS. SEC. R311.7.8 & SEC. R312.1.3
 4- SPECIFY ROOF VENTILATION FOR THE NEW CARRIAGE HOUSE
 & NEW FLORIDA ROOM. SEC. R806. IF DESIGNING UNVENTED
 ATTIC, PROVIDE SPECS AS REQ'D BY SEC. R806.5 . PROVIDE
 ICC EVALUATION REPORT REVIEWED BY THE ARCHITECT IF
 USING FOAM INSULATION.
 5- SHEET S-1:
 A) CODE IN EFFECT IS THE FBC-5TH EDITION (2014). REVISE
 PLANS AS REQUIRED.
 B) DETAIL 8/S-1: PROVIDE COMPLETE DETAIL THAT MATCHES
 EXTERIOR ELEVATIONS. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR THE FRAMING OF THE PARAPET WALLS.
 ALSO, REVISE SIZE OF ROOF TRUSSES TO MATCH: 12" OR 16"
 TRUSSES?. SEC. R301. .
 C) REVISE ROOF SHEATHING SPECIFICATIONS SHOWN ON THE
 MAIN HOUSE COVERED PORCH ROOF FRAMING PLAN. NEED TO
 SPECIFY MIN. 8D RING SHANK NAILS AS REQUIRED BY SEC.
 R803.2.3.1 OR PROVIDE ENGINEERING ANALYSIS SHOWING THAT
 10D COMMON NAILS ARE EQUIVALENT TO THE 8D RING SHANK
 NAILS. SEC. 107.2.1.3 CITY AMENDMENTS. NOTE: THIS
 APPLIES TO THE CARRIAGE HOUSE ALSO.
 D) PROVIDE COMPLETE DOOR AND WINDOW FRAMING DETAILS FOR
 ALL NEW DOORS AND WINDOWS. SPECIFY ALL FRAMING MEMBERS
 AND CONNECTORS. SEC. R301.
 E) WALL SECTIONS: SPECIFY 6" MIN. CLEARANCE FROM GRADE
 AS REQUIRED BY SEC. R404.1.6.
 F) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ALL
 COLUMNS CONNECTIONS AT TOP AND BOTTOM. SPECIFY ALL
 PLATES SIZES, LENGTH AND NUMBER OF ANCHORS AND ALL TOP
 CONNECTORS. SEC. R301.
 G) COVERED PORCH ROOF FRAMING PLAN: SPECIFY CONNECTORS
 AT THE ENDS OF ALL WOOD BEAMS AND GIRDER TRUSS SHOWN
 NEXT TO THE EXISTING WALL. SEC. R301.
 6- SHEET S-2:
 A) UPDATE THE "BASIS OF DESIGN" INFORMATION. REFER TO
 CURRENT CODE 2014. REVISE BUILDING EXPOSURE ACCORDING
 TO THE LOCATION OF BUILDING AND THE WIND VELOCITY. SEC.
 R301.
 B) OUTRIGGER DETAIL: SPECIFY ALL FRAMING MEMBERS AND
 CONNECTORS. SEC. R301.
 C) SITE WALL DETAIL. (1)THERE ARE TWO DIFFERENT HEIGHTS
 SHOWN ON PLANS. REVISE AS REQUIRED TO MATCH PLANS. SEC.
 107.2.1 CITY AMENDMENTS. (2)PROVIDE EMBEDMENT DEPTH OR
 PROVIDE GEOTECHNICAL REPORT AS SPECIFIED ON THE DETAIL.
 SEC. R301. (3)PROVIDE MANUFACTURER'S SPECS FOR THE
 SPECIFIED HELICAL CONNECTORS.
 D) PROVIDE ONLY THE DETAILS THAT APPLY TO THIS PROJECT
 TO AVOID CONFLICTS. SEC. 107.2.1 CITY AMENDMENTS.
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) CONCRETE TILE ADHESIVE IF SPECIFIED BY THE DESIGNER
 OF RECORD. SEE CONCRETE TILE NOA FOR LISTED ADHESIVES.
 B) SLIDING GLASS DOORS AS SHOWN ON PLANS. PROVIDE
 PRODUCT APPROVAL THAT MATCHES PLANS AND THAT MEETS THE
 DESIGN PRESSURES CALCULATED BY THE DESIGNER OF RECORD.
 FLORIDA PRODUCT APPROVAL FL15232-R1 SUBMITTED DOESN'T
 MATCH DOORS SHOWN ON PLANS AND DOESN'T MEET THE DESIGN
 PRESSURES CALCULATED BY THE ENGINEER OF RECORD.
 C) NEW STORAGE DOORS AS SHOWN ON PLANS.
 D) NEW CRAWL SPACE ACCESS DOOR AS SHOWN ON PLANS.
 E) FLAT ROOF. AND CLEARLY IDENTIFY APPROVED ASSEMBLY TO
 BE INSTALLED. AND PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS IF REQUIRED BY THE PRODUCT APPROVAL
 SUBMITTED TO MEET THE CALCULATED DESIGN PRESSURES. SEC.
 R301.
 F) CASEMENT WINDOW SIZE AS SHOWN ON PLANS AND WINDOW
 SCHEDULE FOR WINDOW W20. FLORIDA PRODUCT APPROVAL
 FL15190-R1 SUBMITTED DOESN'T COVER THIS WINDOW WIDTH.
 8- DESIGNER OF RECORD TO APPROVE IN WRITING ALL PRODUCT
 APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS.
 9-DESIGNER OF RECORD TO APPROVE A/C PLAN DESIGN AND
 APPROVE AND SPECIFY LOUVERED DOOR FOR THE BEDROOM IN
 THE CARRIAGE HOUSE. BALANCED RETURN AIR WAS DESIGNED TO
 BE ACCOMPLISHED WITH LOUVERED DOOR. SEC. M1602.4

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-10-23 Cont ID  
Sent By jgomez Date 2015-10-21 Time 15:46 Rev Time 0.00
Received By jgomez Date 2015-10-21 Time 15:46 Sent To  
Notes
2015-10-21 15:47:36RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF USING
 SCREWS/NAILS, THEN SPECIFY SIZE AND NUMBER.
  
 RESPONSE:
 RESPONSE LETTER SAYS SEE NOA SPECIFYING ATTACHMENT. THE
 PRODUCT APPROVAL IS JUST TO SHOW COMPLIANCE WITH THE
 DESIGNER OF RECORD DESIGN SPECIFICATIONS. DESIGNER OF
 RECORD TO SPECIFY FASTENING METHOD AS REQUIRED BY SEC.
 107.2.1.2.
  
 2- SHEET A.05: CODES SPECIFIED ON THE DRAINAGE
 CALCULATIONS ARE MISMATCHED. CALCULATIONS CALL FOR FBC
 2010 AND FBC 2015. THERE IS NOT FBC 2015 AND THE
 CURRENT CODE IS THE FBC- RESIDENTIAL, 5TH EDITION
 (2014). REVISE AS REQUIRED.
  
 3- FRONT ENTRY STAIR DETAIL 3/A.06: RAILING TO COMPLY
 WITH SEC. R311.7.8 AND SEC. R312.1.3. SPECIFY HANDRAIL
 HEIGHT AND OPENING LIMITATIONS.
  
 4- SPECIFY ROOF VENTILATION FOR THE NEW CARRIAGE HOUSE
 AND FOR NEW FLORIDA ROOM (COVERED PORCH) DETAIL 3/A.11
 AS REQUIRED BY SEC. R806.
  
 RESPONSE:
 THERE IS NOT INFORMATION ON SHEET A.05 AS SPECIFIED ON
 RESPONSE LETTER.
  
 5- WINDOW AND DOOR SCHEDULES ON SHEET A.12: CLEARLY
 SPECIFY TYPE OF EACH WINDOW AND DOOR. FOR EXAMPLE
 CASEMENT WINDOW, SINGLE HUNG WINDOW, SLIDING GLASS
 DOOR, FRENCH DOOR ETC. SEC. 107.2.1 CITY AMENDMENTS.
  
 6- PROVIDE ENERGY CALCULATIONS FOR THE NEW CARRIAGE
 HOUSE AS REQUIRED BY SEC. 1106 OF FBC-EXISTING
 BUILDING, 5TH EDITION (2014).
 NOTE: PLANS AND ENERGY CALCULATIONS TO BE COORDINATED
 TO AVOID CONFLICTS OR DELAYS.
  
 RESPONSE;
 ENERGY CALCULATIONS SUBMITTED ARE INCORRECT. SEC.
 R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). (1)WALLS ARE NOT CONCRETE BLOCK. (2)CLARIFY WHY
 ARE THERE 3 OCCUPANTS IN ONE BEDROOM CARRIAGE HOUSE?.
 (3)CLARIFY WHERE ON PLANS IS THE GABLE AREA SPECIFIED
 ON PAGE 2 OF 4?. (4)THE ROOFING MATERIAL IS NOT
 COMPOSITION SHINGLES. (5)CLARIFY WHY THE CEILING
 R-VALUE SHOWN ON PAGE 2 OF 4 IS 0.1?. (6) REVISE THE
 WINDOWS OVERHANG SEPARATION TO MATCH PLANS. SEE PLANS
 AND REVISE AS REQUIRED. ALSO, PROVIDE BUILDER'S NAME ON
 TOP OF FORM.
  
 NOTE: LABELS SHOWING THE WINDOWS AND DOORS U-FACTOR AND
 SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL
 BE REQUIRED FOR INSPECTION.
  
 7- ENERGY CALCULATIONS CALL FOR CARRIAGE HOUSE TO HAVE
 UNVENTED ATTIC. PLANS TO PROVIDE SPECIFICATIONS SHOWING
 COMPLIANCE WITH UNVENTED ATTIC SEC. R806.5 OF
 FBC-RESIDENTIAL, 5TH EDITION. PROVIDE ICC EVALUATION
 REPORT FOR TYPE OF INSULATION SPECIFIED TO CLOSE THE
 BUILDING ENVELOPE (ICYNENE FOR EXAMPLE) AND ARCHITECT
 TO REVIEW AND APPROVE THE REPORT PRIOR TO SUBMITTAL TO
 THIS OFFICE.
  
 8- SHEET S-1:
 A) CODE IN EFFECT AS OF JUNE 30TH 2015 IS THE FBC-5TH
 EDITION (2014). REVISE PLANS AS REQUIRED.
  
 RESPONSE:
 RESPONSE LETTER SAID "PLANS REVISED TO REFLECT CHANGE".
 PLANS SUBMITTED STILL HAVE THE OLD DRAWINGS. NO CHANGES
 DONE.
  
 B) DETAIL 8/S-1: PROVIDE COMPLETE DETAIL THAT MATCHES
 EXTERIOR ELEVATIONS. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR THE FRAMING OF THE PARAPET WALLS.
 ALSO, REVISE SIZE OF ROOF TRUSSES TO MATCH: 12" OR 16"
 TRUSSES?. SEC. R301.
  
 RESPONSE:
 PLANS SUBMITTED STILL HAVE THE OLD DRAWINGS. NO CHANGES
 DONE.
  
 C) REVISE ROOF SHEATHING SPECIFICATIONS SHOWN ON THE
 MAIN HOUSE COVERED PORCH ROOF FRAMING PLAN. NEED TO
 SPECIFY MIN. 8D RING SHANK NAILS AS REQUIRED BY SEC.
 R803.2.3.1 OR PROVIDE ENGINEERING ANALYSIS SHOWING THAT
 10D COMMON NAILS ARE EQUIVALENT TO THE 8D RING SHANK
 NAILS. SEC. 107.2.1.3 CITY AMENDMENTS. NOTE: THIS
 APPLIES TO THE CARRIAGE HOUSE ALSO.
  
 RESPONSE:
 PLANS SUBMITTED STILL HAVE THE OLD DRAWINGS. NO CHANGES
 DONE.
  
 D) PROVIDE COMPLETE DOOR AND WINDOW FRAMING DETAILS FOR
 ALL NEW DOORS AND WINDOWS. SPECIFY ALL FRAMING MEMBERS
 AND CONNECTORS. SEC. R301.
  
 RESPONSE:
 PLANS SUBMITTED STILL HAVE THE OLD DRAWINGS. NO CHANGES
 DONE.
  
 E) WALL SECTIONS: SPECIFY 6" MIN. CLEARANCE FROM GRADE
 AS REQUIRED BY SEC. R404.1.6.
 NOTE: COORDINATE WITH FOOTING SIZE MF-1.
  
 RESPONSE:
 PLANS SUBMITTED STILL HAVE THE OLD DRAWINGS. NO CHANGES
 DONE.
  
 F) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ALL
 COLUMNS CONNECTIONS AT TOP AND BOTTOM. SPECIFY ALL
 PLATES SIZES, LENGTH AND NUMBER OF ANCHORS AND ALL TOP
 CONNECTORS. SEC. R301.
  
 RESPONSE:
 PLANS SUBMITTED STILL HAVE THE OLD DRAWINGS. NO CHANGES
 DONE.
  
 G) COVERED PORCH ROOF FRAMING PLAN: SPECIFY CONNECTORS
 AT THE ENDS OF ALL WOOD BEAMS AND GIRDER TRUSS SHOWN
 NEXT TO THE EXISTING WALL. SEC. R301.
  
 RESPONSE:
 PLANS SUBMITTED STILL HAVE THE OLD DRAWINGS. NO CHANGES
 DONE.
  
 9- SHEET S-2:
 A) UPDATE THE "BASIS OF DESIGN" INFORMATION. REFER TO
 CURRENT CODE 2014. REVISE BUILDING EXPOSURE ACCORDING
 TO THE LOCATION OF BUILDING AND THE WIND VELOCITY. SEC.
 R301.
  
 RESPONSE:
 PLANS SUBMITTED STILL HAVE THE OLD DRAWINGS. NO CHANGES
 DONE.
  
 B) OUTRIGGER DETAIL: SPECIFY ALL FRAMING MEMBERS AND
 CONNECTORS. SEC. R301.
  
 RESPONSE:
 PLANS SUBMITTED STILL HAVE THE OLD DRAWINGS. NO CHANGES
 DONE.
  
 C) SITE WALL DETAIL. (1)THERE ARE TWO DIFFERENT HEIGHTS
 SHOWN ON PLANS. REVISE AS REQUIRED TO MATCH PLANS. SEC.
 107.2.1 CITY AMENDMENTS. (2)PROVIDE EMBEDMENT DEPTH OR
 PROVIDE GEOTECHNICAL REPORT AS SPECIFIED ON THE DETAIL.
 SEC. R301. (3)PROVIDE MANUFACTURER'S SPECS FOR THE
 SPECIFIED HELICAL CONNECTORS.
  
 RESPONSE:
 PLANS SUBMITTED STILL HAVE THE OLD DRAWINGS. NO CHANGES
 DONE.
  
 D) PROVIDE ONLY THE DETAILS THAT APPLY TO THIS PROJECT
 TO AVOID CONFLICTS. SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 PLANS SUBMITTED STILL HAVE THE OLD DRAWINGS. NO CHANGES
 DONE.
  
 10- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) CONCRETE TILE ADHESIVE IF SPECIFIED BY THE DESIGNER
 OF RECORD. SEE CONCRETE TILE NOA FOR LISTED ADHESIVES.
  
 B) SLIDING GLASS DOORS AS SHOWN ON PLANS.
 RESPONSE: PROVIDE PRODUCT APPROVAL THAT MATCHES PLANS
 AND THAT MEETS THE DESIGN PRESSURES CALCULATED BY THE
 DESIGNER OF RECORD. FLORIDA PRODUCT APPROVAL FL15232-R1
 SUBMITTED DOESN'T MATCH DOORS SHOWN ON PLANS AND
 DOESN'T MEET THE DESIGN PRESSURES CALCULATED BY THE
 ENGINEER OF RECORD.
  
 C) NEW STORAGE DOORS AS SHOWN ON PLANS. REPEAT
 COMMENT..
  
 D) NEW CRAWL SPACE ACCESS DOOR AS SHOWN ON PLANS.
 REPEAT COMMENT.
  
 E) FLAT ROOF. AND CLEARLY IDENTIFY APPROVED ASSEMBLY TO
 BE INSTALLED. AND PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS IF REQUIRED BY THE PRODUCT APPROVAL
 SUBMITTED TO MEET THE CALCULATED DESIGN PRESSURES. SEC.
 R301.
 RESPONSE: (1) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY
 FROM NOA 13-0529.14 SUBMITTED IS GOING TO BE INSTALLED
 AND PROVIDE SIGNED AND SIGNED RAS 117 CALCULATIONS TO
 MEET THE DESIGN PRESSURES OF SEC. R301.
 (2) CLARIFY WHY SUBMITTING INSULATION ADHESIVE NOA
 12-0329.02. PLANS DON'T CALL FOR ANY INSULATED FLAT
 ROOF ASSEMBLY.
 (3) CLARIFY WHY SUBMITTING SHARKSKIN ROOF UNDERLAYMENT
 NOA 09-1123.02. WHERE IS THIS GOING TO BE INSTALLED?.
 WHICH PRODUCT APPROVAL IS LISTING THIS PRODUCT?. SEE
 GENERAL LIMITATIONS ON LAST PAGE OF NOA SUBMITTED FOR
 THE APPROVED USES OF THIS PRODUCT . THIS NOA EXPIRED ON
 07/14/15.
  
 F) CASEMENT WINDOW SIZE AS SHOWN ON PLANS AND WINDOW
 SCHEDULE FOR WINDOW W20. FLORIDA PRODUCT APPROVAL
 FL15190-R1 SUBMITTED DOESN'T COVER THIS WINDOW WIDTH.
 NOTE: EXTERIOR ELEVATION SHOWS WINDOW W20 TO BE DOUBLE
 CASEMENT. IF WINDOW IS DOUBLE CASEMENT, THEN PROVIDE
 PRODUCT APPROVAL FOR CASEMENT WINDOW WITHOUT MULLION IN
 THE MIDDLE. OTHERWISE, REVISE PLANS AS REQUIRED.
  
 11- A)DESIGNER OF RECORD TO APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 B) PLEASE PROVIDE REVIEW STAMP ON COVER SHEET NOT ON
 THE BACK OF THE COVER SHEET.. REVIEW STAMP ON BACK OF
 COVER SHEET DOESN'T ALLOW PROPER SCANNING AND FILING
 FOR THE RECORD RETENTION. SEC. 107.2.1.4 CITY
 AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
 SUBMIT OLD COPIES FOR REFERENCE. PLEASE REMOVE VOID
 SHEETS FROM STAPLED SETS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-26 Cont ID  
Sent By jgomez Date 2015-08-26 Time 16:21 Rev Time 0.00
Received By jgomez Date 2015-08-26 Time 15:59 Sent To E
Notes
2015-08-26 16:31:13RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- THE FBC 5TH EDITION (2014) WENT INTO EFFECT ON JUNE
 30TH OF 2015. THE PERMIT APPLICATION WAS SUBMITTED ON
 JUNE 30TH 2015. THEREFORE, THE CODE IN EFFECT AT TIME
 OF PERMIT APPLICATION IS THE 2014 CODE. NEED TO REVISE
 ALL PLANS AND NOTES REFERENCING THE FBC 5TH EDITION
 (2014).
  
 3- DRAWINGS TITLE BLOCK MUST HAVE THE FIRM LICENSE
 NUMBER FOR ROY & POSEY ARCHITECTURE LANDSCAPE INTERIORS
 AS REQUIRED BY FAC SEC. 61G1-16.004.
  
 4- SHEET A.03:
 A) MAIN HOUSE ENTRY DOOR: CLARIFY NOTE "REVERSE DOOR
 SWING". WAS THIS DOOR AN OUTSWING DOOR AND NOW IT'S
 REVERSED TO INSWING?. IF SO, PROVIDE COMPLETE DETAILS/
 SPECIFICATIONS AND ENGINEERING SHOWING HOW THE DOOR
 COMPLIES WITH THE WIND PRESSURES OF SEC. R301 OF FBC-
 5TH EDITION (2014)-RESIDENTIAL.
  
 B) WALL TYPE LEGEND AND WALL HATCHED ON THE FLOOR PLAN
 DON'T MATCH. SEC. 107.2.1 CITY AMENDMENTS. ALSO, WALL
 LEGEND IS NOT LEGIBLE. TYPE OF WALL LETTERING IS
 OVERLAPPING. REVISE AS REQUIRED. SEC. 107.2.1.4 CITY
 AMENDMENTS.
  
 5- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF USING
 SCREWS/NAILS, THEN SPECIFY SIZE AND NUMBER.
  
 6- SPECIFY CARBON MONOXIDE ALARMS BY ALL SLEEPING ROOM
 AS REQUIRED BY SEC. R315.
  
 7- SPECIFY TYPE AND SIZE OF EXISTING BEDROOM WINDOWS
 AND TYPE AND SIZE OF PROPOSED WINDOWS TO VERIFY
 COMPLIANCE WITH EGRESS REQUIREMENTS OF SEC. 704 OF FBC-
 EXISTING BUILDING -5TH EDITION (2014).
 NOTE: BEDROOM #2 USED TO HAVE A DOOR LEADING TO AN
 STAIRWAY. THIS BEDROOM MUST HAVE AT LEAST ONE EGRESS
 WINDOW THAT COMPLIES WITH SEC. R310.
  
 8- SHEET A.04 AND SHEET A.05; CLEARLY SPECIFY ROOF
 DRAINAGE FOR ALL NEW FLAT ROOFS (CARRIAGE HOUSE AND
 COVERED PORCH) AS REQUIRED BY SEC. R903.4 .
 ALSO, SPECIFY OVERFLOW DRAINS OR SCUPPERS AS REQUIRED
 BY SEC. R903.4.1.
  
 9- FRONT ENTRY STAIR DETAIL 3/A.06: RAILING TO COMPLY
 WITH SEC. R311.7.8.
  
 10- SPECIFY ROOF VENTILATION FOR THE NEW CARRIAGE HOUSE
 AND FOR NEW FLORIDA ROOM (COVERED PORCH) DETAIL 3/A.11
 AS REQUIRED BY SEC. R806.
  
 11- TABLE R702.1(1) REQUIRES 7/8" STUCCO THICKNESS (NOT
 3/4"). REVISE SPECIFICATIONS ON ALL WALL SECTIONS AND
 ALL DETAILS AS REQUIRED.
  
 12- PROVIDE ENERGY CALCULATIONS FOR THE NEW CARRIAGE
 HOUSE AS REQUIRED BY SEC. 1106 OF FBC-EXISTING
 BUILDING, 5TH EDITION (2014). NOTE: PLANS AND ENERGY
 CALCULATIONS TO BE COORDINATED TO AVOID CONFLICTS OR
 DELAYS.
  
 13- SHEET S-1:
 A) CODE IN EFFECT AS OF JUNE 30TH 2015 IS THE FBC-5TH
 EDITION (2014). REVISE PLANS AS REQUIRED.
  
 B) DETAIL 8/S-1: PROVIDE COMPLETE DETAIL THAT MATCHES
 EXTERIOR ELEVATIONS. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR THE FRAMING OF THE PARAPET WALLS.
 ALSO, REVISE SIZE OF ROOF TRUSSES TO MATCH: 12" OR 16"
 TRUSSES?. SEC. R301.
  
 C) REVISE ROOF SHEATHING SPECIFICATIONS SHOWN ON THE
 MAIN HOUSE COVERED PORCH ROOF FRAMING PLAN. NEED TO
 SPECIFY MIN. 8D RING SHANK NAILS AS REQUIRED BY SEC.
 R803.2.3.1 OR PROVIDE ENGINEERING ANALYSIS SHOWING THAT
 10D COMMON NAILS ARE EQUIVALENT TO THE 8D RING SHANK
 NAILS. SEC. 107.2.1.3 CITY AMENDMENTS. NOTE: THIS
 APPLIES TO THE CARRIAGE HOUSE ALSO.
  
 D) PROVIDE COMPLETE DOOR AND WINDOW FRAMING DETAILS FOR
 ALL NEW DOORS AND WINDOWS. SPECIFY ALL FRAMING MEMBERS
 AND CONNECTORS. SEC. R301.
  
 E) WALL SECTIONS: SPECIFY 6" MIN. CLEARANCE FROM GRADE
 AS REQUIRED BY SEC. R404.1.6.
 NOTE: COORDINATE WITH FOOTING SIZE MF-1.
  
 F) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ALL
 COLUMNS CONNECTIONS AT TOP AND BOTTOM. SPECIFY ALL
 PLATES SIZES, LENGTH AND NUMBER OF ANCHORS AND ALL TOP
 CONNECTORS. SEC. R301.
  
 G) COVERED PORCH ROOF FRAMING PLAN: SPECIFY CONNECTORS
 AT THE ENDS OF ALL WOOD BEAMS AND GIRDER TRUSS SHOWN
 NEXT TO THE EXISTING WALL. SEC. R301.
  
 14- SHEET S-2:
 A) UPDATE THE "BASIS OF DESIGN" INFORMATION. REFER TO
 CURRENT CODE 2014. REVISE BUILDING EXPOSURE AND THE
 WIND VELOCITY. SEC. R301.
  
 B) OUTRIGGER DETAIL: SPECIFY ALL FRAMING MEMBERS AND
 CONNECTORS. SEC. R301.
  
 C) SITE WALL DETAIL. (1)THERE ARE TWO DIFFERENT HEIGHTS
 SHOWN ON PLANS. REVISE AS REQUIRED TO MATCH PLANS. SEC.
 107.2.1 CITY AMENDMENTS. (2)PROVIDE EMBEDMENT DEPTH OR
 PROVIDE GEOTECHNICAL REPORT AS SPECIFIED ON THE DETAIL.
 SEC. R301. (3)PROVIDE MANUFACTURER'S SPECS FOR THE
 SPECIFIED HELICAL CONNECTORS.
  
 D) PROVIDE ONLY THE DETAILS THAT APPLY TO THIS PROJECT
 TO AVOID CONFLICTS. SEC. 107.2.1 CITY AMENDMENTS.
  
 15- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ALL FRENCH DOORS AS SHOWN ON PLANS. NEED PRODUCT
 APPROVAL FOR 2014 CODE VERSION. FLORIDA PRODUCT
 APPROVAL FL16521 SUBMITTED IS FOR 2010 CODE VERSION.
 NOTE: CLEARLY IDENTIFY ON PRODUCT APPROVAL LOCATION OF
 DOOR. FOR EXAMPLE LIVING ROOM, NEW CARRIAGE LIVING
 AREA, ETC.
  
 B) ALL FRENCH DOORS AS SHOWN ON PLANS. NEED PRODUCT
 APPROVAL FOR 2014 CODE VERSION. FLORIDA PRODUCT
 APPROVAL FL15916 SUBMITTED IS FOR 2010 CODE VERSION.
 NOTE: CLEARLY IDENTIFY ON PRODUCT APPROVAL LOCATION OF
 DOOR. FOR EXAMPLE LIVING ROOM, NEW CARRIAGE LIVING
 AREA, ETC.
  
 C) ALL FIXED WINDOWS AS SHOWN ON PLANS. NEED PRODUCT
 APPROVAL FOR 2014 CODE VERSION. FLORIDA PRODUCT
 APPROVAL FL15189-R1 SUBMITTED IS FOR 2010 CODE VERSION.
 NOTE: CLEARLY IDENTIFY ON PRODUCT APPROVAL LOCATION OF
 WINDOW . FOR EXAMPLE LIVING ROOM, NEW CARRIAGE LIVING
 AREA, ETC.
  
 D) ALL CASEMENT WINDOWS AS SHOWN ON PLANS. NEED PRODUCT
 APPROVAL FOR 2014 CODE VERSION. FLORIDA PRODUCT
 APPROVAL FL15190 SUBMITTED IS FOR 2010 CODE VERSION.
 NOTE: CLEARLY IDENTIFY ON PRODUCT APPROVAL LOCATION OF
 CASEMENT WINDOW. FOR EXAMPLE LIVING ROOM, NEW CARRIAGE
 LIVING AREA, ETC.
  
 E) CONCRETE TILE ADHESIVE IF SPECIFIED BY THE DESIGNER
 OF RECORD. SEE CONCRETE TILE NOA FOR LISTED ADHESIVES.
  
 F) SLIDING GLASS DOORS AS SHOWN ON PLANS.
  
 G) NEW STORAGE DOORS AS SHOWN ON PLANS.
  
 H) NEW CRAWL SPACE ACCESS DOOR AS SHOWN ON PLANS.
  
 I) FLAT ROOF. AND CLEARLY IDENTIFY APPROVED ASSEMBLY TO
 BE INSTALLED. AND PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS IF REQUIRED BY THE PRODUCT APPROVAL
 SUBMITTED TO MEET THE CALCULATED DESIGN PRESSURES. SEC.
 R301.
  
 J) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND ALL DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR. OR DESIGNER OF RECORD TO LIST THE FLORIDA
 PRODUCT APPROVAL NUMBER NEXT TO THE SPECIFIED
 CONNECTOR.
  
 16- DESIGNER OF RECORD TO APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 107.3.4.1 CITY AMENDMENTS.
 NOTE: PRODUCT APPROVALS SUBMITTED HAVE A REVIEW STAMP
 FROM "MESA ARCHITECTURE ". THIS IS NOT THE FIRM ON THE
 TILTE BLOCK AND IT'S BLANK. IT WAS NOT SIGNED BY THE
 ARCHITECT OR ENGINEER OF RECORD EITHER.
  
 17- CARRIAGE HOUSE: PROVIDE INFORMATION SHOWING
 COMPLIANCE WITH THE HEATING REQUIREMENTS OF SEC.
 R303.9.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
 SUBMIT OLD COPIES FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By ppetty Date 2015-10-27 Time 09:17 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-10-19 Cont ID  
Sent By ppetty Date 2015-10-19 Time 11:24 Rev Time 0.00
Received By ppetty Date 2015-10-19 Time 11:14 Sent To  
Notes
2015-10-19 11:23:50225.32 SHOW LOCATIONS OF MAINS AND PANELS
 RISER DIAGRAM AND PLANS DO NOT MATCH METER LOCATION
 250.32 GES ON SEPARATE BUILDING REQUIRED PLEASE SHOW
 PLEASE COMPLETE PLAN PHIL PETTY 561-644-7305

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-09-14 Cont ID  
Sent By ppetty Date 2015-09-14 Time 10:33 Rev Time 0.00
Received By ppetty Date 2015-09-14 Time 09:43 Sent To  
Notes
2015-09-14 10:33:16210.52 (A THRU E)
 250.50 ALL PRESENT+SEPARATE BLDG
 A/C SYSTEM INFORMATION
 LOCATION OF MAINS
 IN SMALL BIN M
 PHIL PETTY

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2015-10-21 Cont ID  
Sent By fmittner Date 2015-10-21 Time 14:09 Rev Time 0.00
Received By fmittner Date 2015-10-21 Time 14:09 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2015-08-05 Cont ID  
Sent By fmittner Date 2015-08-05 Time 11:25 Rev Time 0.00
Received By fmittner Date 2015-08-05 Time 11:25 Sent To  
Notes
2015-08-05 11:26:23SHALL RETAIN ORIGINAL WINDOW BY FRONT DOOR.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-10-27 Cont ID  
Sent By jgomez Date 2015-10-27 Time 13:57 Rev Time 0.00
Received By jgomez Date 2015-10-27 Time 13:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-23 Cont ID  
Sent By jgomez Date 2015-10-23 Time 13:30 Rev Time 0.00
Received By jgomez Date 2015-10-02 Time 11:27 Sent To  
Notes
2015-10-05 11:27:59R29

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-14 Cont ID  
Sent By skennedy Date 2015-09-14 Time 10:35 Rev Time 0.00
Received By skennedy Date 2015-06-30 Time 14:57 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2015-10-27 Cont ID  
Sent By jgomez Date 2015-10-27 Time 15:38 Rev Time 0.00
Received By jgomez Date 2015-10-27 Time 15:38 Sent To  
Notes
2015-10-27 15:39:34NO FEES. MU-2015-25297.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-10-21 Cont ID  
Sent By jgomez Date 2015-10-21 Time 16:19 Rev Time 0.00
Received By jgomez Date 2015-10-21 Time 16:19 Sent To  
Notes
2015-10-21 16:20:091- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-08-26 Cont ID  
Sent By jgomez Date 2015-08-26 Time 16:19 Rev Time 0.00
Received By jgomez Date 2015-08-26 Time 16:19 Sent To  
Notes
2015-08-26 16:21:341- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-10-27 Cont ID  
Sent By jgomez Date 2015-10-27 Time 15:36 Rev Time 0.00
Received By jgomez Date 2015-10-27 Time 15:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-10-23 Cont ID  
Sent By jgomez Date 2015-10-22 Time 07:51 Rev Time 0.00
Received By jgomez Date 2015-10-22 Time 07:51 Sent To  
Notes
2015-10-22 07:51:48RESIDENTIAL (R3) ADDITION/ALTERATION SECOND MECHANICAL
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- REVISE EQUIPMENT SIZING CALCULATIONS SUBMITTED. SEE
 BUILDING COMMENTS FOR REVISIONS REQUIRED ON THE ENERGY
 CALCULATIONS. NEED TO REVISE THE WALL TYPE AND NUMBER
 OF PEOPLE FOR A 1 BEDROOM UNIT. SEC. R403.6.1 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 NOTE: COORDINATE WITH THE ENERGY CALCULATIONS TO AVOID
 CONFLICTS AND DELAYS.
  
 2- DRAWING M.01 SUBMITTED NEEDS TO HAVE THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN AS
 REQUIRED BY SEC. 107.2.1 CITY AMENDMENTS. REPEAT
 COMMENT.
  
 3- THE BEDROOM NEEDS TO COMPLY WITH THE BALANCED RETURN
 AIR SEC. M1602.4 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014). MECHANICAL PLAN INDICATES A LOUVERED DOOR FOR
 THE BEDROOM. LOUVERED DOOR IS NOT SPECIFIED BY THE
 ARCHITECT FOR THE BEDROOM. BESIDES, A LOUVERED DOOR FOR
 THE BEDROOM IS NOT VERY PRACTICAL AND MAY BE REPLACED.
 THEREFORE IS NOT ACCEPTABLE. THE BALANCED RETURN AIR IS
 TYPICAL DONE BY INSTALLING TRANSFER GRILLS OR TRANSFER
 DUCTS. SEE SEC. M1602.4 AND REVISE AS REQUIRED. REPEAT
 COMMENT.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
 SUBMIT OLD COPIES FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-09-10 Cont ID  
Sent By jgomez Date 2015-09-10 Time 17:59 Rev Time 0.00
Received By jgomez Date 2015-09-10 Time 14:33 Sent To  
Notes
2015-09-10 18:00:22RESIDENTIAL (R3) ADDITION/ALTERATION MECHANICAL REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS FOR
 THE CARRIAGE HOUSE AS REQUIRED BY SEC. R403.6.1 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 NOTE: COORDINATE WITH THE ENERGY CALCULATIONS TO AVOID
 CONFLICTS AND DELAYS.
  
 2- DRAWING M.01 SUBMITTED NEEDS TO HAVE THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN AS
 REQUIRED BY SEC. 107.2.1 CITY AMENDMENTS.
  
 3- THE BEDROOM NEEDS TO COMPLY WITH THE BALANCED RETURN
 AIR SEC. M1602.4 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014). MECHANICAL PLAN INDICATES A LOUVERED DOOR FOR
 THE BEDROOM. LOUVERED DOOR IS NOT SPECIFIED BY THE
 ARCHITECT FOR THE BEDROOM. BESIDES, A LOUVERED DOOR FOR
 THE BEDROOM IS NOT VERY PRACTICAL AND MAY BE REPLACED.
 THEREFORE IS NOT ACCEPTABLE. THE BALANCED RETURN AIR IS
 TYPICAL DONE BY INSTALLING TRANSFER GRILLS OR TRANSFER
 DUCTS. SEE SEC. M1602.4 AND REVISE AS REQUIRED.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
 SUBMIT OLD COPIES FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-10-14 Cont ID  
Sent By gjohnson Date 2015-10-13 Time 09:32 Rev Time 0.00
Received By gjohnson Date 2015-10-13 Time 09:32 Sent To  
Notes
2015-10-14 13:01:14CONTRACTOR BROUGHT IN MISSING SHEETS AND INSERTED THEM
 IN PLAN SET 10/14/15
2015-10-13 09:36:052ND REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  
  
 PLUMBING COMMENTS:
  
 1.ONE SET OF PLANS STILL MISSING SHEET P.01 2ND
 REQUEST.

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-07-25 Cont ID  
Sent By tklarge Date 2015-07-25 Time 11:03 Rev Time 0.00
Received By tklarge Date 2015-07-25 Time 10:32 Sent To  
Notes
2015-07-25 10:36:28ONE SET OF PLANS IS MISSING PLUMBING SHEET P.01.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2015-10-27 Cont ID  
Sent By jgomez Date 2015-10-27 Time 15:41 Rev Time 0.00
Received By jgomez Date 2015-10-27 Time 15:41 Sent To  
Notes
2015-10-27 15:41:55APPROVED WITH PROVISO:
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) CONCRETE TILE ADHESIVE IF SPECIFIED BY THE DESIGNER
 OF RECORD. SEE CONCRETE TILE NOA FOR LISTED ADHESIVES.
  
 B) FLAT ROOF. AND CLEARLY IDENTIFY APPROVED ASSEMBLY TO
 BE INSTALLED. AND PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS IF REQUIRED BY THE PRODUCT APPROVAL
 SUBMITTED TO MEET THE CALCULATED DESIGN PRESSURES. SEC.
 R301.
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2015-10-23 Cont ID  
Sent By jgomez Date 2015-10-23 Time 13:07 Rev Time 0.00
Received By jgomez Date 2015-10-23 Time 13:06 Sent To  
Notes
2015-10-23 13:08:511- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) CONCRETE TILE ADHESIVE IF SPECIFIED BY THE DESIGNER
 OF RECORD. SEE CONCRETE TILE NOA FOR LISTED ADHESIVES.
  
 B) FLAT ROOF. AND CLEARLY IDENTIFY APPROVED ASSEMBLY TO
 BE INSTALLED. AND PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS IF REQUIRED BY THE PRODUCT APPROVAL
 SUBMITTED TO MEET THE CALCULATED DESIGN PRESSURES. SEC.
 R301.
  
 RESPONSE: (1) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY
 FROM NOA 13-0529.14 SUBMITTED IS GOING TO BE INSTALLED
 AND PROVIDE SIGNED AND SIGNED RAS 117 CALCULATIONS TO
 MEET THE DESIGN PRESSURES OF SEC. R301.
 (2) CLARIFY WHY SUBMITTING INSULATION ADHESIVE NOA
 12-0329.02. PLANS DON'T CALL FOR ANY INSULATED FLAT
 ROOF ASSEMBLY.
 (3) CLARIFY WHY SUBMITTING SHARKSKIN ROOF UNDERLAYMENT
 NOA 09-1123.02. WHERE IS THIS GOING TO BE INSTALLED?.
 WHICH PRODUCT APPROVAL IS LISTING THIS PRODUCT?. SEE
 GENERAL LIMITATIONS ON LAST PAGE OF NOA SUBMITTED FOR
 THE APPROVED USES OF THIS PRODUCT . THIS NOA EXPIRED ON
 07/14/15.
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2015-08-27 Cont ID  
Sent By jgomez Date 2015-08-27 Time 16:03 Rev Time 0.00
Received By jgomez Date 2015-08-27 Time 07:49 Sent To  
Notes
2015-08-27 16:05:331- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
  
 A) CONCRETE TILE ADHESIVE IF SPECIFIED BY THE DESIGNER
 OF RECORD. SEE CONCRETE TILE NOA FOR LISTED ADHESIVES.
  
 B) FLAT ROOF. AND CLEARLY IDENTIFY APPROVED ASSEMBLY TO
 BE INSTALLED. AND PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS IF REQUIRED BY THE PRODUCT APPROVAL
 SUBMITTED TO MEET THE CALCULATED DESIGN PRESSURES. SEC.
 R301.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2015-10-21 Cont ID  
Sent By fmittner Date 2015-10-21 Time 14:09 Rev Time 0.00
Received By fmittner Date 2015-10-21 Time 14:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-08-05 Cont ID  
Sent By fmittner Date 2015-08-05 Time 11:26 Rev Time 0.00
Received By fmittner Date 2015-08-05 Time 11:26 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved