Plan Review Details - Permit 15061448
Plan Review Stops For Permit 15061448
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-08-18 Cont ID  
Sent By jgomez Date 2015-08-18 Time 14:55 Rev Time 0.00
Received By jgomez Date 2015-08-18 Time 14:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-08-05 Cont ID  
Sent By jgomez Date 2015-08-05 Time 12:48 Rev Time 0.00
Received By jgomez Date 2015-08-05 Time 12:48 Sent To  
Notes
2015-08-05 12:49:00ROOF RECOVER, SECOND BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014)
  
 NOTE: PERMIT APPLICATION WAS SUBMITTED ON 6/30/15. THE
 NEW CODE TOOK EFFECT ON 6/30/15. THE CURRENT CODE IS
 FBC 5TH EDITION (2014).
  
 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9N-3 FOR THE RECOVERY SYSTEM TO BE INSTALLED. NOTE:
 COORDINATE WITH ITEM #3(D) BELOW. (REPEAT COMMENT. NOT
 ADDRESSED).
  
 2- PROVIDE COPY OF THE TESTING REQUIRED BY LIMITATION
 #5.9 OF THE PRODUCT APPROVAL FL10264 REFERENCED BY THE
 CBUCK ENGINEERING REPORT SUBMITTED FOR THE RECOVERY
 ASSEMBLY. (REPEAT COMMENT. NOT ADDRESSED).
  
 3- REVISE THE CBUCK ENGINEERING REPORT SUBMITTED:
 A) THE CURRENT CODE IS THE FBC-5TH EDITION (2014) NOT
 FBC-2010. (REPEAT COMMENT. NOT ADDRESSED).
  
 B) THE MEAN ROOF HEIGHT IS INCORRECT. AND, THERE ARE
 SEPARATE FLAT ROOFS IN THIS BUILDING. PROVIDE SKETCH
 SHOWING ALL ROOFS AND MEAN ROOF HEIGHTS. (OK. SKETCH
 PROVIDED).
  
 C) NOT ALL THE FLAT ROOF S IN THIS BUILDING HAVE A
 3'-0" HIGH PARAPET. PROVIDE SKETCH SHOWING ALL THE FLAT
 ROOFS THAT ARE INVOLVED IN THIS PERMIT AND . REVISE
 CALCULATIONS AS REQUIRED. SEC. 1609 OF FBC-5TH EDITION.
 (REPEAT COMMENT. NOT ADDRESSED. SKETCH WAS PROVIDED BUT
 CALCULATIONS WERE NOT REVISED).
  
 D) CURRENT ROOF COVERING FLORIDA PRODUCT APPROVAL IS
 FL10264-R12 NOT FL10264-R11. REVISE AS REQUIRED. DCA
 RULE 9N-3. (REPEAT COMMENT. NOT ADDRESSED).
  
 E) ENGINEER TO REVISE THE ROOF SYSTEM ENGINEERING DATA
 ON PAGE 3 OF REPORT. THE CONSTRUCTION TYPE IS NOT NEW
 OR REROOF. THE PROPOSED INSTALLATION IS A RECOVER
 ASSEMBLY. SEC. 107.2.1 CITY AMENDMENTS. (REPEAT
 COMMENT. NOT ADDRESSED).
  
  
 NOTE: ANY ROOFING EQUIPMENT REMOVAL REQUIRES SEPARATE
 PERMITS
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-07-02 Cont ID  
Sent By jgomez Date 2015-07-02 Time 17:24 Rev Time 0.00
Received By jgomez Date 2015-07-02 Time 16:26 Sent To  
Notes
2015-07-02 17:37:39ROOF RECOVER, BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014)
  
 NOTE: PERMIT APPLICATION WAS SUBMITTED ON 6/30/15. THE
 NEW CODE TOOK EFFECT ON 6/30/15. THE CURRENT CODE IS
 FBC 5TH EDITION (2014).
  
 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9N-3 FOR THE RECOVERY SYSTEM TO BE INSTALLED. NOTE:
 COORDINATE WITH ITEM #3(D) BELOW.
  
 2- PROVIDE COPY OF THE TESTING REQUIRED BY LIMITATION
 #5.9 OF THE PRODUCT APPROVAL FL10264 REFERENCED BY THE
 CBUCK ENGINEERING REPORT SUBMITTED FOR THE RECOVERY
 ASSEMBLY.
  
 3- REVISE THE CBUCK ENGINEERING REPORT SUBMITTED:
 A) THE CURRENT CODE IS THE FBC-5TH EDITION (2014) NOT
 FBC-2010.
  
 B) THE MEAN ROOF HEIGHT IS INCORRECT. AND, THERE ARE
 SEPARATE FLAT ROOFS IN THIS BUILDING. PROVIDE SKETCH
 SHOWING ALL ROOFS AND MEAN ROOF HEIGHTS.
  
 C) NOT ALL THE FLAT ROOF S IN THIS BUILDING HAVE A
 3'-0" HIGH PARAPET. PROVIDE SKETCH SHOWING ALL THE FLAT
 ROOFS THAT ARE INVOLVED IN THIS PERMIT AND . REVISE
 CALCULATIONS AS REQUIRED. SEC. 1609 OF FBC-5TH EDITION.
  
 D) CURRENT ROOF COVERING FLORIDA PRODUCT APPROVAL IS
 FL10264-R12 NOT FL10264-R11. REVISE AS REQUIRED. DCA
 RULE 9N-3.
  
 E) ENGINEER TO REVISE THE ROOF SYSTEM ENGINEERING DATA
 ON PAGE 3 OF REPORT. THE CONSTRUCTION TYPE IS NOT NEW
 OR REROOF. THE PROPOSED INSTALLATION IS A RECOVER
 ASSEMBLY. SEC. 107.2.1 CITY AMENDMENTS.
  
 NOTE: ANY ROOFING EQUIPMENT REMOVAL REQUIRES SEPARATE
 PERMITS
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-18 Cont ID  
Sent By jgomez Date 2015-08-18 Time 14:55 Rev Time 0.00
Received By jgomez Date 2015-08-17 Time 09:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-02 Cont ID  
Sent By jgomez Date 2015-07-02 Time 16:26 Rev Time 0.00
Received By jgomez Date 2015-07-02 Time 14:42 Sent To  
Notes
***NONE***