| Notes |
| 2015-07-01 07:33:38 | 1ST REVIEW: FBC 2014 MECHANICAL | | | | | | 1) ACCORDING TO WEST PALM BEACH PLANNING AND ZONING | | | RECORDS, THE TWO STORY GUEST HOUSE WAS ORIGINALLY BUILT | | | AS A GARAGE/APARTMENT. I HAVE NOT BEEN ABLE TO FIND A | | | PERMIT IN THE PUBLIC RECORDS FOR THE CHANGE IN | | | OCCUPANCY OF GARAGE TO GUEST HOUSE. PLEASE CLARIFY IF | | | THIS PERMIT APPLICATION IS A SUB-PERMIT OF A MASTER | | | PERMIT FOR THE GARAGE CONVERSION, OR IF SUBMITTAL OF A | | | PERMIT APPLICATION AND PLANS ARE PENDING. | | | 2) IN REGARD TO THE PROPOSED AC SYSTEM, PREVIOUSLY | | | UNCONDITIONED BUILDINGS NOW BEING CONDITIONED SHALL BE | | | IN COMPLIANCE WITH THE FLORIDA ENERGY CONSERVATION CODE | | | 2014. PLEASE SEE SECTIONS R101.4.3, R101.4.8, AND | | | R101.5. IN ACCORDANCE WITH SECTION R101.5.1.1 PLEASE | | | SUBMIT TWO COPIES OF EITHER FORM R402, R405, OR A | | | FLORIDA RESCHECK COMPUTER PRINTOUT TO DEMONSTRATE | | | COMPLIANCE. | | | 3) PROVIDE STRUCTURAL DETAILS FOR INSTALLATION OF THE | | | CONDENSER PAD AND TIE-DOWN ENGINEERING FOR MOUNTING THE | | | CONDENSER. | | | 4) PROVIDE AN ELECTRICAL PLAN. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
|