| Plan Review Stops For Permit 15061437 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2016-01-25 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2016-01-25 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2016-01-25 |
Time |
12:53 |
Sent To |
|
|
| Notes |
| 2016-01-25 13:00:14 | BUILDING REVIEW APPROVED WITH PROVISO: | | | | | | 1- REVISE SIZE OF HEATING/COOLING UNIT FOR NEW BEDROOM: | | | SIZE OF HEATING AND COOLING WALL UNIT SHOWN ON PLANS IS | | | OVERSIZED FOR THE NEW BEDROOM. 8,000 BTU UNIT IS | | | OVERSIZED FOR A ROOM WITH LESS THAN 100S.F . PROVIDE | | | EQUIPMENT SIZING CALCULATIONS. SEC. C403.2.1 OF | | | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). EQUIPMENT | | | CAN NOT EXCEED THE CALCULATED LOADS. SEC. C403.2.2 OF | | | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2016-01-05 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2016-01-21 |
Time |
08:02 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2016-01-05 |
Time |
16:57 |
Sent To |
|
|
| Notes |
| 2016-01-05 17:04:18 | RESIDENTIAL (R2) ALTERATION, 4TH BUILDING REVIEW | | | CHECKLIST. | | | CODE: FBC-5TH EDITION (2014). | | | | | | 1- PLANS WERE REVISED AND NEW CASEMENT WINDOW WAS | | | SPECIFIED ON PLANS FOR THE NEW BEDROOM. THE CASEMENT | | | WINDOW COMPLIES WITH EGRESS. NEED TO PROVIDE PRODUCT | | | APPROVAL (2 COPIES) FOR THE CASEMENT WINDOW AS REQUIRED | | | BY FAC 61G20-3.002(3). | | | RESPONSE: PRODUCT APPROVAL NOA NO 15-0728.05 SUBMITTED | | | IS FOR "HORIZONTAL ROLLING WINDOW". ENGINEER DRAWING | | | A-2 SPECIFIES 37.5" X 50.625" CASEMENT WINDOW. THE | | | CASEMENT WINDOW SIZE SPECIFIED ON PLANS COMPLIES WITH | | | THE EGRESS REQUIREMENTS. THE HORIZONTAL ROLLING WINDOW | | | DOESN'T COMPLY. ENGINEER OF RECORD APPROVED NOA | | | SUBMITTED AND IT DOESN'T COMPLY. | | | | | | 2- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE | | | NEW TENANT SEPARATION WALL THAT MATCHES PROPOSED FLOOR | | | PLAN. SHOW COMPLIANCE WITH SEC. 420.2 FBC. 5TH EDITION. | | | RESPONSE: | | | A) TENANT SEPARATION WALL SUBMITTED IS "BEARING 1 HOUR | | | FIRE RATED WALL U.L. DESIGN NO U305". CLARIFY WHY THERE | | | IS ONLY ONE 2X4 TOP PLATE?. ALSO, WOOD FRAMED WALL | | | SUPPORTING CONCRETE SLAB NEED TO PROVIDE COMPLIANCE | | | WITH SEC. 2304.12 OF FBC FOR LONG TERM LOADING. | | | ENGINEER OF RECORD TO PROVIDE COMPLIANCE. | | | | | | B) PROVIDE UL COPY OF COMPLETE SPECIFICATIONS FOR THE | | | U.L. NO U305 ASSEMBLY SHOWING 1" GAP BETWEEN STUD AND | | | TOP RUNNER AS SHOWN ON WALL DETAIL SUBMITTED. . SHOW | | | GYPSUM BOARD FASTENING. SEC. 107.2.1 CITY AMENDMENTS. | | | | | | 3- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING | | | HOW THE EXTERIOR WALL DOOR OPENING IS GOING TO BE | | | CLOSED. SEC. 1609 FBC. | | | RESPONSE: DETAIL C/2 SUBMITTED IS NOT CLEAR. ENGINEER | | | NEEDS TO BE SPECIFIC WITH WHAT KIND OF 12" METAL STRAP | | | IS GOING TO BE USED. "12" METAL STRAP IS VERY GENERIC. | | | THERE ARE MANY TYPES AND MANUFACTURERS FOR 12" METAL | | | STRAPS. ALSO, PROVIDE COMPLETE DETAIL SHOWING HOW IS | | | THE 12" STRAP ATTACHED TO THE TOP AND BOTTOM PLATES. | | | SEC. 107.2.1 CITY AMENDMENTS. | | | | | | NOTE: INSPECTIONS WILL BE REQUIRED TO VERIFY EXISTING | | | TENANT SEPARATION WALLS, CEILINGS AND FLOORS. AND, | | | EXTERIOR WALLS. | | | | | | 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING | | | COMPLIANCE WITH THE TEMPERATURE CONTROL FOR THE NEW | | | BEDROOM AS REQUIRED BY SEC. 1204 FBC. | | | RESPONSE: SIZE OF HEATING AND COOLING WALL UNIT SHOWN | | | ON PLANS IS OVERSIZED FOR THE NEW BEDROOM. 8,000 BTU | | | UNIT IS OVERSIZED FOR A ROOM WITH LESS THAN 100S.F . | | | PROVIDE EQUIPMENT SIZING CALCULATIONS. SEC. C403.2.1 OF | | | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). EQUIPMENT | | | CAN NOT EXCEED THE CALCULATED LOADS. SEC. C403.2.2 OF | | | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). | | | | | | NOTE: | | | ENGINEER OF RECORD TO PAY FOUR TIMES THE PLAN REVIEW | | | FEE AS REQUIRED BY FLORIDA STATUTE 553.80(2)(B) FOR | | | PLANS REJECTED MORE THAN 3 TIMES. | | | PLANS WILL BE SUBMITTED TO THE BOARD OF ENGINEERS FOR | | | REVIEW. | | | | | | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2015-12-16 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2015-12-17 |
Time |
13:32 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2015-12-16 |
Time |
11:07 |
Sent To |
E |
|
| Notes |
| 2015-12-16 11:07:58 | RESIDENTIAL (R2) ALTERATION, THIRD BUILDING REVIEW | | | CHECKLIST. | | | CODE: FBC-5TH EDITION (2014). | | | | | | NOTE: | | | ENGINEER OF RECORD WILL BE CHARGED FOUR TIMES THE PLAN | | | REVIEW FEE AS REQUIRED BY FLORIDA STATUTE 553.80(2)(B) | | | IF PLANS ARE REJECTED ONE MORE TIME. | | | | | | 1- PLANS WERE REVISED AND NEW CASEMENT WINDOW WAS | | | SPECIFIED ON PLANS FOR THE NEW BEDROOM. THE WINDOW NOW | | | COMPLIES WITH EGRESS. NOW NEED TO PROVIDE PRODUCT | | | APPROVAL (2 COPIES) FOR THE CASEMENT WINDOW AS REQUIRED | | | BY FAC 61G20-3.002(3). | | | | | | 2- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE | | | NEW TENANT SEPARATION WALL THAT MATCHES PROPOSED FLOOR | | | PLAN. SHOW COMPLIANCE WITH SEC. 420.2 FBC. 5TH EDITION. | | | RESPONSE: (A) THE NEW TENANT SEPARATION WALL ASSEMBLY | | | U474 SUBMITTED IS FOR AN EXTERIOR WALL. NEED TENANT | | | SEPARATION WALL ASSEMBLY FOR AN INTERIOR APPLICATION AS | | | SHOWN ON PLANS. SEC. 107.2.1 CITY AMENDMENTS. | | | | | | (B) THE NEW TENANT SEPARATION WALL DETAIL SUBMITTED | | | DOESN'T MATCH FLOOR PLAN. FLOOR PLAN SHOWS TWO WALLS. | | | CLARIFY/REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY | | | AMENDMENTS. | | | | | | 3- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING | | | HOW THE EXTERIOR WALL DOOR OPENING IS GOING TO BE | | | CLOSED WITH "DRYWALL" TO SHOW COMPLIANCE WITH THE | | | DESIGN PRESSURES OF SEC. 1609 FBC. | | | RESPONSE: BLOCK-UP DETAIL IS INCOMPLETE. MISSING A LOT | | | OF INFORMATION. PROVIDE A COMPLETE WALL ASSEMBLY THAT | | | MATCHES FLOOR PLAN. FLOOR PLAN SHOWS TWO WALLS. | | | CLARIFY/REVISE AS REQUIRED TO MATCH. CLEARLY SPECIFY | | | ALL CONNECTORS. METAL STRAPS IS NOT ENOUGH INFORMATION. | | | ALSO, THIS IS AN EXTERIOR WALL. INFORMATION SUBMITTED | | | DON'T COMPLY FOR AN EXTERIOR WALL ASSEMBLY. CLEARLY | | | PROVIDE SPECIFICATIONS FOR THE INTERIOR SIDE AND | | | EXTERIOR SIDE. SEC. 107.2.1 CITY AMENDMENTS. | | | | | | 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING | | | COMPLIANCE WITH THE TEMPERATURE CONTROL FOR THE NEW | | | BEDROOM AS REQUIRED BY SEC. 1204 FBC. | | | RESPONSE: FLOOR PLAN SHOWS NEW WALL AC. THIS DOESN'T | | | SATISFY THE HEATING REQUIREMENT. PLANS CALL ONLY FOR | | | AC. ALSO, THERE IS NO DEDICATED OUTLET SHOWN FOR THE | | | HEATING UNIT.. NOTE: HEATING IS MANDATORY, COOLING IS | | | NOT. THE UNIT MAY BE AN A/C UNIT WITH HEAT.BUT, PLANS | | | NEED TO SPECIFY IT AND CORRESPONDENT DEDICATED OUTLET | | | IS REQUIRED. PROVIDE MANUFACTURER'S SPECS FOR SELECTED | | | A/C WITH HEAT AND REVISE PLANS AS REQUIRED. | | | | | | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2015-10-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2015-10-05 |
Time |
13:46 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2015-10-05 |
Time |
13:46 |
Sent To |
P |
|
| Notes |
| 2015-10-05 13:53:22 | RESIDENTIAL (R2) ALTERATION, BUILDING REVIEW COMMENTS. | | | CODE: FBC-5TH EDITION (2014). | | | | | | NOTE: ON 10/6/15 TALKED TO ART LANGE (BLDG. INSPECTOR | | | WHO RE-TAGGED THE JOB). THERE IS A LOT OF WORK DONE | | | WITHOUT PERMITS ON SEVERAL UNITS. PLANS NEED TO SHOW | | | ALL THE SCOPE OF WORK ON ALL UNITS. | | | | | | 1- THERE ARE SEVERAL BUILDINGS IN THIS PARCEL. PROVIDE | | | A KEY PLAN SHOWING SPECIFIC BUILDING WHERE WORK IS | | | TAKEN PLACE. SEC. 107.2.1 CITY AMENDMENTS. | | | | | | RESPONSE: | | | AREA OF WORK SHOWN ON DRAWING 1 OF 2 SUBMITTED DOESN'T | | | MATCH FLOOR PLAN SHOWN ON DRAWING 2 OF 2. THE FLOOR | | | PLAN SHOWN ON DRAWING 2 OF 2 LOOKS LIKE AN END UNIT, | | | WHILE AREA OF WORK SHOWN ON DRAWING 1 OF 2 IS SOMEWHERE | | | IN THE MIDDLE OF THE BUILDING. REVISE AS REQUIRED TO | | | MATCH. | | | | | | 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | | LOW. VALUATION TO INCLUDE ALL LABOR , MATERIALS, | | | CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN | | | PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY | | | AMENDMENTS. . REVISE VALUATION AND PROVIDE COPY OF | | | SIGNED CONTRACT THAT SHOWS ALL THE SCOPE OF WORK. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | 3- NEW BEDROOM WAS CREATED. SPECIFY COMPLIANCE WITH THE | | | EMERGENCY EGRESS REQUIREMENTS OF SEC. 1029 FBC. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE | | | NEW TENANT SEPARATION WALL THAT MATCHES PROPOSED FLOOR | | | PLAN. SHOW COMPLIANCE WITH SEC. 420.2 FBC. 5TH EDITION. | | | NOTE: VERIFY THAT EXISTING TENANT SEPARATION WALL IS | | | CONCRETE BLOCK WALL. MOST LIKELY IS NOT. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | 5- PROVIDE COMPLETE DETAILS AN SPECIFICATIONS FOR THE | | | NEW DRYWALL PARTITION THAT MATCHES PROPOSED FLOOR PLAN | | | AT THE PERIMETER OF THE DWELLING UNIT AND BETWEEN | | | EXISTING BEDROOM AND EXISTING LIVING/DINING AREA. SEC. | | | 107.2.1 CITY AMENDMENTS. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | 6- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING | | | HOW THE EXTERIOR WALL DOOR OPENING IS GOING TO BE | | | CLOSED WITH "DRYWALL" TO SHOW COMPLIANCE WITH THE | | | DESIGN PRESSURES OF SEC. 1609 FBC. | | | | | | RESPONSE: | | | BLOCK-UP DETAIL IS INCOMPLETE. MISSING A LOT OF | | | INFORMATION. PROVIDE A COMPLETE WALL ASSEMBLY. ALSO, | | | LETTERING IS TOO SMALL AND IS NOT LEGIBLE. CLEARLY | | | SPECIFY THE TOP AND BOTTOM WOOD STUD CONNECTORS. | | | | | | 7- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING | | | COMPLIANCE WITH THE TEMPERATURE CONTROL FOR THE NEW | | | BEDROOM AS REQUIRED BY SEC. 1204 FBC. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2015-08-27 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2015-08-26 |
Time |
13:06 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2015-08-26 |
Time |
12:40 |
Sent To |
|
|
| Notes |
| 2015-08-26 13:08:30 | RESIDENTIAL (R2) ALTERATION, BUILDING REVIEW COMMENTS. | | | CODE: FBC-5TH EDITION (2014). | | | | | | 1- THE 2014 FBC TOOK EFFECT ON JUNE 30TH, 2015. PERMIT | | | APPLICATION WAS SUBMITTED ON JUNE 30TH, THEREFORE THE | | | CODE IN EFFECT IS THE 2014 FBC. ENGINEER TO REVISE | | | PLANS AS REQUIRED. | | | | | | 2- THERE ARE SEVERAL BUILDINGS IN THIS PARCEL. PROVIDE | | | A KEY PLAN SHOWING SPECIFIC BUILDING WHERE WORK IS | | | TAKEN PLACE. SEC. 107.2.1 CITY AMENDMENTS. | | | | | | 3- THIS IS AN APARTMENT BUILDING WITH MORE THAN 2 | | | UNITS. THIS IS NOT OCCUPANCY GROUP R3. SEE SEC. 310.3 | | | FBC AND REVISE AS REQUIRED. | | | | | | 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | | LOW. VALUATION TO INCLUDE ALL LABOR , MATERIALS, | | | CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN | | | PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY | | | AMENDMENTS. . REVISE VALUATION AND PROVIDE COPY OF | | | SIGNED CONTRACT THAT SHOWS ALL THE SCOPE OF WORK. | | | | | | 5- NEED NOC. SEC. 713 F.S. | | | | | | 6- NEW BEDROOM WAS CREATED. SPECIFY COMPLIANCE WITH THE | | | EMERGENCY EGRESS REQUIREMENTS OF SEC. 1029 FBC. | | | | | | 7- WALL TYPES. ACCORDING TO CITY RECORDS, THE EXTERIOR | | | WALL OF THIS BUILDING IS NOT WOOD FRAME. REVISE AS | | | REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. | | | | | | 8- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE | | | NEW TENANT SEPARATION WALL THAT MATCHES PROPOSED FLOOR | | | PLAN. SHOW COMPLIANCE WITH SEC. 420.2 FBC. | | | | | | 9- PROVIDE COMPLETE DETAILS AN SPECIFICATIONS FOR THE | | | NEW DRYWALL PARTITION THAT MATCHES PROPOSED FLOOR PLAN | | | AT THE PERIMETER OF THE DWELLING UNIT AND BETWEEN | | | EXISTING BEDROOM AND EXISTING LIVING/DINING AREA. SEC. | | | 107.2.1 CITY AMENDMENTS. | | | | | | 10- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING | | | HOW THE EXTERIOR WALL DOOR OPENING IS GOING TO BE | | | CLOSED WITH "DRYWALL" TO SHOW COMPLIANCE WITH THE | | | DESIGN PRESSURES OF SEC. 1609 FBC. | | | | | | 11- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING | | | COMPLIANCE WITH THE TEMPERATURE CONTROL FOR THE NEW | | | BEDROOM AS REQUIRED BY SEC. 1204 FBC. | | | | | | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2016-01-28 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-01-28 |
Time |
14:55 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-01-28 |
Time |
14:55 |
Sent To |
|
|
| Notes |
| 2016-01-25 16:31:58 | NEW DRAWINGS SUBMITTED. JG. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2016-01-20 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-01-20 |
Time |
16:00 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-01-20 |
Time |
16:00 |
Sent To |
|
|
| Notes |
| 2016-01-05 17:05:08 | NEW DRAWINGS SUBMITTED. JG. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2015-12-17 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2015-12-17 |
Time |
11:36 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2015-12-17 |
Time |
11:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2015-10-06 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-10-06 |
Time |
08:53 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-10-06 |
Time |
08:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2015-09-10 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-09-10 |
Time |
15:30 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-09-10 |
Time |
15:30 |
Sent To |
|
|
| Notes |
| 2015-09-10 15:42:57 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011 RESIDENTIAL 5TH | | | ED. | | | | | | PLEASE REVISE PLAN TO CITE THEAPPLICABLE CODE IN EFFECT | | | ABOVE. | | | | | | NOTE THE PLANS MUST BE SPECIFIC AS TO THE WORK TO BE | | | INCLUDED IN THE SCOPE. SHOW NEW AND CORECTED WORK. | | | | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN | | | UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS | | | SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING | | | OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT | | | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF | | | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL | | | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT | | | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED | | | BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND | | | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM | | | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, | | | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE | | | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, | | | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE | | | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS | | | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | | INFORMATION. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2016-01-08 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2016-01-08 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2016-01-08 |
Time |
12:27 |
Sent To |
|
|
| Notes |
| 2016-01-05 17:05:49 | NEW DRAWINGS SUBMITTED. JG. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2015-09-18 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2015-09-18 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2015-09-18 |
Time |
08:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2015-08-31 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2015-08-31 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2015-08-31 |
Time |
11:00 |
Sent To |
|
|
| Notes |
| 2015-08-31 11:19:08 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF | | | THE 5TH EDITION OF FLORIDA FIRE PREVENTION CODE | | | INCLUDING THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND | | | ALL OTHER APPLICABLE CODES OR STANDARDS. | | | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. | | | | | | 2) PROVIDE CORRECT ADDRESS OR APARTMENT NUMBER. | | | | | | 3) ALL FIRE ALARM WORK SHALL BE DONE UNDER SEPARATE | | | SHOP DRAWINGS. | | | | | | 4) ADDRESS BUILDING COMMENTS. | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2016-01-28 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2016-01-28 |
Time |
17:34 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2016-01-22 |
Time |
08:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2016-01-21 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2016-01-21 |
Time |
08:02 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2015-12-23 |
Time |
15:32 |
Sent To |
B |
|
| Notes |
| 2016-01-07 12:03:48 | 1/7/16 NEW PLANS SUBMITTED. SENT TO B33 SHELF FOR | | | REVIEW. JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2015-12-17 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2015-12-17 |
Time |
13:32 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2015-12-11 |
Time |
09:10 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2015-10-06 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-10-06 |
Time |
08:53 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-09-16 |
Time |
13:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-09-10 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-09-10 |
Time |
15:43 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-06-30 |
Time |
09:58 |
Sent To |
|
|
| Notes |
| 2015-08-27 09:57:20 | 8/27/15 SENT TO B33 SHELF FOR REVIEW. THIS APPLICATION | | | IS FOR APARTMENT BUILDING NOT R3. JG. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2016-01-26 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-01-26 |
Time |
12:43 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-01-26 |
Time |
12:43 |
Sent To |
|
|
| Notes |
| 2016-01-25 16:32:25 | NEW DRAWINGS SUBMITTED. JG. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2016-01-13 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-01-13 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-01-13 |
Time |
15:10 |
Sent To |
|
|
| Notes |
| 2016-01-05 17:07:24 | NEW DRAWINGS SUBMITTED. JG. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2015-10-05 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2015-10-05 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2015-10-05 |
Time |
16:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2015-08-27 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2015-07-22 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2015-08-26 |
Time |
13:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|