Plan Review Details - Permit 15061434
Plan Review Stops For Permit 15061434
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-08-05 Cont ID  
Sent By wjolin Date 2015-08-05 Time 09:11 Rev Time 0.00
Received By wjolin Date 2015-08-05 Time 09:08 Sent To  
Notes
2015-08-05 09:11:43MECHANICAL ENGINEER OF RECORD SUBMITTED LETTER
 INDICATING RESPONSIBILITY AND COMPLIANCE WITH NFPA 96
 AS WELL AS AN INFORMAL "WHITE PAPER" FROM NFPA 13
 COMMITTEE MEMBER RUSSELL FLEMING, PE INDICATING
 SPRINKLERS ARE NOT INTENDED FOR GREASE DUCTWORK OVER 75
 FEET IN LENGTH AND PROTECTED BY LISTED GREASE
 EXTRACTORS IN ACCORDANCE WITH UL300.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-07-14 Cont ID  
Sent By wjolin Date 2015-07-14 Time 15:35 Rev Time 0.00
Received By wjolin Date 2015-07-14 Time 15:15 Sent To  
Notes
2015-07-14 15:35:32600 OKEECHOBEE BOULEVARD
 PERMIT #15061434
 MASTER #14050111
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PER NFPA 96 SECTION 7.1.2 ALL DUCTS SHALL LEAD DIRECTLY
 TO THE EXTERIOR OF THE BUILDING, SO AS NOT TO UNDULY
 INCREASE ANY FIRE HAZARD. DUCTWORK APPEARS TO BE ROUTED
 HORIZONTALLY APPROXIMATELY 125 FEET. RECOMMEND A MORE
 DIRECT VERTICAL ROUTE OR INSTALLING WET PIPE SPRINKLERS
 IN DUCTWORK PER NFPA 13.
  
 HAVE CONCERNS: THE HORIZONTAL GREASE DUCTWORK BEING
 ROUTED ALONG THE FIRST FLOOR CEILING CREATES A UNIQUE
 SITUATION WHERE THE FIRE MAY ACTUALLY BE LOCATED IN THE
 FIRST FLOOR CEILING; HOWEVER, THE FIRE ALARM WILL
 INDICATE THE FIRE IS ACTUALLY IN THE KITCHEN HOOD
 LOCATED IN THE BASEMENT LEVEL.
  
 GREASE DUCT PLANS ARE VERY DIFFICULT TO READ THE DUCT
 SIZES, THE CLEANOUT LOCATIONS AND SIZES, ETC.
  
 PERMIT APPLICATION INDICATES THE SCOPE OF WORK IS ONLY
 FOR THE INSTALLATION OF 8 TYPE I COMMERCIAL KITCHEN
 HOODS; HOWEVER, THE HOODS, DUCTWORK AND FANS NEED TO BE
 REVIEWED TOGETHER TO FULLY UNDERSTAND THE SYSTEM AS A
 WHOLE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-09 Cont ID  
Sent By hmoser Date 2015-07-09 Time 14:46 Rev Time 0.00
Received By hmoser Date 2015-06-30 Time 15:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-07-09 Cont ID  
Sent By hmoser Date 2015-07-09 Time 14:45 Rev Time 0.00
Received By hmoser Date 2015-07-09 Time 14:45 Sent To FIRE
Notes
***NONE***