Plan Review Details - Permit 15061430
Plan Review Stops For Permit 15061430
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-10-15 Cont ID  
Sent By jwitmer Date 2015-10-15 Time 10:49 Rev Time 0.00
Received By jwitmer Date 2015-10-15 Time 10:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-07-24 Cont ID  
Sent By jwitmer Date 2015-07-24 Time 15:57 Rev Time 0.00
Received By jwitmer Date 2015-07-24 Time 15:30 Sent To  
Notes
2015-07-24 15:57:18BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15061430
 ADD: 2301 CENTREPARK WEST DRIVE SUITE # 150
 CONT: WOOLEMS INC.
 TEL: (561)835-0401
 E-MAIL: ?????????
  
 2014 FLORIDA BUILDING CODE W
 * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JULY 24/ 2015
 ACTION: DENIED
  
 1) THE PLANS SUBMITTED ON JUNE 30/ 2015 IS THE 1ST DAY
 OF THE 2014 FBC ADOPTED STATEWIDE. PLEASE UPDATE PLANS.
  
 2) SHEET A-1 INDICATES A EXECUTIVE BATHROOM ROOM # 108.
 PLEASE NOTE BOTH SECTION IN THE 2014 FBC-ACCESSIBILITY
 CODE 603.2.3 & 608.3 FOR THIS BATHROOM TO BE CONSIDERED
 A PRIVATE OFFICE THE OCCUPANT HAS TO GO THROUGH THE
 PRIVATE OFFICE AND NOT FOR COMMON USE.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2015-10-13 Cont ID  
Sent By albarran Date 2015-10-13 Time 14:17 Rev Time 0.00
Received By albarran Date   Time   Sent To  
Notes
2015-10-13 14:19:35THIS WAS WAS ALREADY APPROVED BY PHIL ON 9/1/15. NO
 ADDITIONAL ELECTRICAL REVIEW REQUIRED UNLESS CHANGES TO
 THE ORIGINAL HAVE BEEN MADE, AND THEN A FULL REVISION
 REVIEW WILL BE REQUIRED.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-09-01 Cont ID  
Sent By ppetty Date 2015-09-01 Time 11:19 Rev Time 0.00
Received By ppetty Date 2015-09-01 Time 10:28 Sent To  
Notes
2015-09-01 11:24:24PASSED
 IN LARGE DENIED BIN W

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2015-10-20 Cont ID  
Sent By fstallwo Date 2015-10-20 Time   Rev Time 0.00
Received By fstal Date 2015-10-20 Time 13:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-09-15 Cont ID  
Sent By fstal Date 2015-09-15 Time   Rev Time 0.00
Received By fstal Date   Time   Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-07-07 Cont ID  
Sent By pleduc Date 2015-07-07 Time   Rev Time 0.00
Received By pleduc Date 2015-07-07 Time 16:21 Sent To  
Notes
2015-07-07 16:31:48THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE SUBMITTED PLAN SHEETS ARE NOT BOUND, ORGANIZED OR
 ORDERLY. A PROPER REVIEW CAN NOT BE CONDUCTED. PLEASE
 ORGANIZED AND BIND EACH SET TOGETHER AND RESUBMIT.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-10-21 Cont ID  
Sent By tklarge Date 2015-10-21 Time 03:39 Rev Time 0.00
Received By tklarge Date 2015-10-13 Time 11:10 Sent To  
Notes
2015-10-14 11:11:08C25

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-14 Cont ID  
Sent By lmarchan Date 2015-10-13 Time 11:10 Rev Time 0.00
Received By lmarchan Date 2015-09-10 Time 08:49 Sent To  
Notes
2015-09-11 08:49:18C08

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-01 Cont ID  
Sent By ppetty Date 2015-09-01 Time 11:24 Rev Time 0.00
Received By ppetty Date 2015-06-30 Time 14:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-09-21 Cont ID  
Sent By ccole Date 2015-09-21 Time 13:36 Rev Time 0.00
Received By ccole Date 2015-09-21 Time 13:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-07-16 Cont ID  
Sent By ccole Date 2015-07-16 Time 12:02 Rev Time 0.00
Received By ccole Date 2015-07-16 Time 12:02 Sent To  
Notes
2015-07-16 12:33:091ST REVIEW: FBC 2014 MECHANICAL
 7/16/15
  
 1) THE PLANS ARE UNACCEPTABLE BECAUSE THE SHEETS WERE
 SUBMITTED LOOSELY AND UNBOUND- REFER TO SECTION
 107.2.1.4 WPB AMENDEMENTS TO THE FLORIDA BUILDING CODE.
 2) DESIGN CRITERIA: THE FLORIDA BUILDING CODES-2014
 FIFTH EDITION WENT INTO EFFECT JUNE 30, 2015. PLEASE
 PROVIDE ON THE PLANS A LIST OF CURRENT CODES AND
 STANDARDS USED IN THE DESIGN OF THE PROJECT, AND UPDATE
 THE 2010 REFERENCE UNDER THE O/A CALCULATION TABLE ON
 SHEET M0.1.
 3) M1.1: THE RETURN AIR TRANFER FROM JIM'S OFFICE TO
 THE CORRIDOR IS NOT PERMITTED- REFER TO SECTION 601.2
 FBC-14 MECHANICAL.
 4) M1.1: SHOW THE DUCT CONNECTIONS TO THE RELOCATED
 ERV.
 5) AC LOAD CALCULATIONS HAVE BEEN SUBMITTED FOR AHU'S
 1-6, HOWEVER THERE ARE NO AC EQUIPMENT SCHEDULES ON THE
 PLANS TO COMPARE THE CALCS TO. PLEASE PROVIDE THE
 SCHEDULES ON THE PLAN.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-10-21 Cont ID  
Sent By tklarge Date 2015-10-21 Time 03:39 Rev Time 0.00
Received By tklarge Date 2015-10-21 Time 03:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-09-28 Cont ID  
Sent By tklarge Date 2015-09-28 Time 11:27 Rev Time 0.00
Received By tklarge Date 2015-09-28 Time 11:17 Sent To  
Notes
2015-09-28 11:26:271) THE ARCHITECTURAL FLOOR PLAN ON SHEET A-1 DOES NOT
 CORRELATE WITH THE FLOOR PLAN ON SHT. P1.1. ROOM NAMES
 ARE DIFFERENT,THE FLOOR PLAN IS DIFFERENT.THE EXECUTIVE
 BATHROOM IS SHOWN ON A-1 BUT IT IS SHOWN AS A STORAGE
 ROOM WITH THE PLUMBING FIXTURES DELETED ON P1.1. SUBMIT
 PLANS THAT MATCH. WPB AMEND. TO FBC SEC. 107.2.1.
 2) WATER HEATER DETAIL #2. A PAN DRAIN IS REQD. FOR THE
 EWH.
 3) THE BREAK ROOM SINK SHALL COMPLY WITH THE
 FBC-ACCESSIBILITY SEC.212.3. SHOW COMPLIANCE ON THE
 PLANS. 2ND. REQUEST.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-07-25 Cont ID  
Sent By tklarge Date 2015-07-25 Time 10:28 Rev Time 0.00
Received By tklarge Date 2015-07-25 Time 09:45 Sent To  
Notes
2015-08-31 14:53:26PPETTY'S DESK
2015-07-25 10:07:031) THE BREAK ROOM SINK SHALL COMPLY W/2014 FAC
 SEC.212.1, 606.2, 606.3.
 2) THE URINAL IS SHOWN IN TOILET ROOM #106 ON SHT.A-1
 AND IT IS SHOWN IN TOILET ROOM # 105 ON SHT.P1.1.
 CLARIFY.
 3) EXECUTIVE BATHROOM #108 SHALL FULLY COMPLY WITH THE
 2010 FAC SEC.213.2.IN ORDER TO NOT HAVE TO FULLY COMPLY
 WITH THE FAC, THE BATH ROOM MUST BE ACCESSIBLR THROUGH
 A PRIVATE OFFICE. AS DESIGNED, IT DOES NOT COMPLY WITH
 THE EXCEPTION IN THE CODE.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  