Plan Review Details - Permit 15061348
Plan Review Stops For Permit 15061348
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-10-27 Cont ID  
Sent By ccole Date 2015-10-27 Time 12:19 Rev Time 0.00
Received By ccole Date 2015-10-27 Time 12:19 Sent To  
Notes
2015-10-27 12:22:57PERMIT #15061348
 10/27/15
 PROVISO
  
 PRIOR TO FOOTING INSPECTION:
 ALTERRA ENGINEERING AND TESTING SHALL PROVIDE A
 DE-MUCKING AND DE-WATERING REPORT OF THE FOUNDATION
 SUBSURFACE, AND A DENSITY AND COMPACTION TEST REPORT
 FOR THE ENGINEERED FOUNDATION PAD.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-10-13 Cont ID  
Sent By ccole Date 2015-10-13 Time 15:24 Rev Time 0.00
Received By ccole Date 2015-10-13 Time 15:24 Sent To  
Notes
2015-10-13 15:54:482ND REVIEW: FBC 2010 BUILDING
 PERMIT #15061348
 10/13/15
  
 1) COMMENT #1 FROM THE 1ST REVIEW WAS NOT ADDRESSED. I
 AM REPRINTING IT HERE FOR REVIEW AND COMPLIANCE: (THE
 SUBMITTED SOIL TESTING AND ENGINEERING REPORT FROM
 ALTERRA IS INCOMPLETE (SUBJECT: DEMUCKING
 INTERVENTION). REFER TO PARAGRAPH 2 OF THE COVER LETTER
 AND SUBMIT COPIES OF THE FEBRUARY/2015 GEOTECHNICAL
 REPORT WHICH, ACCORDING TO THE LETTER, PROVIDES
 "RECOMMENDATIONS FOR BEARING-GRADE PREPARATION" OF THE
 SOIL. THE COMPLETE REPORT SHALL INCLUDE AMONG OTHER
 THINGS, A DIMENSIONED DRAWING OF THE AREA(S) OF THE LOT
 THAT WERE DEMUCKED (WAS THE POOL INCLUDED?), THE CLEAN
 SAND FILL AND COMPACTION PROCEDURE, AND ESTABLISH THE
 LOAD BEARING VALUE OF THE SOIL- REFER TO SECTIONS
 R401.4 AND R506 FBC-10 RESIDENTIAL).
 2) WHEN RE-SUBMITTING PLANS PLEASE REMOVE THE DEFICIENT
 PLANS AND INSERT THE CORRECTED PLANS INTO THE PLAN
 SETS. THE END RESULT SHOULD BE TWO COMPLETE SETS OF
 PLANS- CURRENTLY THERE ARE 8 PARTIAL SETS IN THE FILE.
 3) THERE ARE THREE DIFFERENT FINISHED FLOOR ELEVATION
 HEIGHTS SHOWN IN THE PLANS- SEE SHEETS SP-1, S-0, & S-1
 AND CORRECT
 4) SHEET S-2.1: THE REVISED PLANS INDICATE 42" DEEP
 LINTELS AND 8"X12" TIE BEAMS ABOVE THE GARAGE DOOR
 OPENINGS WITH A FINISHED WALL HEIGHT OF 10'0". THIS
 WOULD LEAVE THE GARAGE DOOR HEADER HEIGHTS AT 66" ABOVE
 FINISHED FLOOR FOR AN 8' HIGH DOOR. ADDITIONALLY, THE
 ELEVATION DRAWING INDICATES ARCHED OPENINGS AT THESE
 LOCATIONS. PLEASE CORRECT.
 5) S-3.4: AS PREVIOUSLY REQUESTED PROVIDE A DETAIL FOR
 L-28.
 6) A-4: AS PREVIOUSLY REQUESTED IN THE 1ST REVIEW,
 REFER TO SECTION R703.6.3: WATER-RESISTIVE BARRIERS.
 WATER-RESISTIVE BARRIERS SHALL BE INSTALLED AS REQUIRED
 IN SECTION R703.2 AND, WHERE APPLIED OVER WOOD-BASED
 SHEATHING, SHALL INCLUDE A WATER-RESISTIVE
 VAPOR-PERMEABLE BARRIER WITH A PERFORMANCE AT LEAST
 EQUIVALENT TO TWO LAYERS OF GRADE D PAPER. THE
 INDIVIDUAL LAYERS SHALL BE INSTALLED INDEPENDENTLY SUCH
 THAT EACH LAYER PROVIDES A SEPARATE CONTINUOUS PLANE
 AND ANY FLASHING INSTALLED IN ACCORDANCE WITH SECTION
 R703.8) INTENDED TO DRAIN TO THE WATER-RESISTIVE
 BARRIER IS DIRECTED BETWEEN THE LAYERS. THE PLAN IS
 INDICATING ONLY ONE LAYER OF GRADE D PAPER.
 7) COMMENT #21 FROM THE 1ST REVIEW WAS NOT ADDRESSED.
 A-4: PROVIDE ROUGH FRAMING AND EXTERIOR FINISH DETAILS
 FOR THE COVERED ENTRY AND OUTDOOR KITCHEN CEILINGS).
 8) COMMENT #23 FROM THE 1ST REVIEW NOT ADDRESS: E-1:
 CARBON MONOXIDE DETECTORS SHALL BE INSTALLED WITHIN 10'
 OF EACH BEDROOM- SECTION R315.1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-26 Cont ID  
Sent By ccole Date 2015-08-26 Time 07:33 Rev Time 0.00
Received By ccole Date 2015-08-25 Time 07:33 Sent To  
Notes
2015-08-26 08:14:241ST REVIEW: FBC 2010 RESIDENTIAL
 PERMIT #15061348
 8/26/15
  
 1) THE SUBMITTED SOIL TESTING AND ENGINEERING REPORT
 FROM ALTERRA IS INCOMPLETE (SUBJECT: DEMUCKING
 INTERVENTION). REFER TO PARAGRAPH 2 OF THE COVER LETTER
 AND SUBMIT COPIES OF THE FEBRUARY/2015 GEOTECHNICAL
 REPORT WHICH, ACCORDING TO THE LETTER, PROVIDES
 "RECOMMENDATIONS FOR BEARING-GRADE PREPARATION" OF THE
 SOIL. THE COMPLETE REPORT SHALL INCLUDE AMONG OTHER
 THINGS, A DIMENSIONED DRAWING OF THE AREA(S) OF THE LOT
 THAT WERE DEMUCKED (WAS THE POOL INCLUDED?), THE CLEAN
 SAND FILL AND COMPACTION PROCEDURE, AND ESTABLISH THE
 LOAD BEARING VALUE OF THE SOIL- REFER TO SECTIONS
 R401.4 AND R506 FBC-10 RESIDENTIAL
 2) REFER TO SECTION R802.1.6.1 AND SUBMIT TWO COPIES OF
 THE ROOF TRUSS DESIGN DRAWINGS.
 3) REFER TO TABLE R301.2(2) AND CORRECT THE COMPONENT
 AND CLADDING WIND PRESSURES (ULTIMATE DESIGN WIND
 SPEED). PLEASE INCLUDE THE MEAN ROOF HEIGHT.
 4) SHEET S-0: PROVIDE NOTES AND DETAILS FOR
 FIREBLOCKING AND DRAFTSTOPPING- REFER TO SECTIONS
 R302.11 & R302.12.
 5) SHEET S-1: REFER TO THE SURVEY AND PROVIDE THE
 FINISH FLOOR ELEVATION ON THE DRAWING.
 6) S-1: REFER TO SECTION R506.2.3 AND INDICATE THE TYPE
 AND THICKNESS OF THE SLAB VAPOR BARRIER.
 7) S-1: REFER TO SECTION R506.2.5 AND INDICATE THE TYPE
 OF SLAB REINFORCEMENT TO BE INSTALLED. IF WIRE MESH IS
 TO BE INSTALLED PROVIDE DETAILS INDICATING THE TYPE AND
 SIZE OF WIRE, AND HOW THE WIRE WILL BE SUPPORTED AND
 LAPPED.
 8) INDICATE THE AREAS OF THE SLAB WHERE CRACK BARS WILL
 ME INSTALLED AND PROVIDE DETAILS IF APPLICABLE.
 9) S-1: & S3.: PROVIDE A DETAIL AND SYMBOL FOR THE
 RECESSED SHOWER SLABS.
 10) S-2.1: THE 8"X12" TB #2 OVER THE 18'0" GARAGE DOOR
 OPENING IS OVERSPANNED PER TABLE R611.8. PLEASE
 CORRECT.
 11) S-3.3: THE WINDOW AND DOOR BUCK ATTACHMENT DETAILS
 SHOW BEVELED BUCKS WHICH ARE NOT PERMITTED PER SECTION
 R612.10.2.1. PLEASE CORRECT.
 12) S-3.3, TYPICAL WALL SECTION: PROVIDE THE SLOPE OF
 THE GRADE AT THE FOUNDATION PER SECTION R401.3.
 13) S-3.4: PROVIDE A DETAIL FOR L-28 AS SHOWN ON SHEET
 S-2.1.
 14) A-1: INDICATE THE LOCATION OF THE REQUIRED ATTIC
 HATCH, AND PROVIDE A DETAIL FOR INSTALLATION- SECTION
 R807.1.
 15) A-1: PROVIDE ROUGH FRAMING AND INTERIOR FINISH
 DETAILS FOR THE COFFERED CEILINGS.
 16) A-1: "F" TYPE WINDOWS ARE SHOWN AT THE MASTER BATH,
 HOWEVER THEY ARE NOT INCLUDED IN THE SCHEDULE ON A7.
 PLEASE NOTE THAT THE F AND B TYPE WINDOWS SHALL HAVE
 TEMPERED GLASS -SECTION R308.4.
 17) A-1: PROVIDE A SEDCTION DETAIL FOR THE
 GARAGE/LIVING SEPARATION WALL- SECTION R302.6.
 18) A-1 & A-7: INDICATE WHICH BATHROOM DOOR IS MEETING
 THE MINIMUM 29 INCH CLEAR WIDTH OPENING REQUIRED BY
 SECTION R320.1.1.
 19) A-1 & A-7: PROVIDE A COMPLETE WINDOW SCHEDULE THAT
 INCLUDES THE TYPES OF WINDOWS TO BE INSTALLED- IMPACT
 OR NON-IMPACT, WINDOW FRAME MATERIALS, WIDTH AND
 HEIGHT, AND THICKNESSES AND EFFICIENCY RATINGS OF THE
 GLASS. EGRESS WINDOWS AND THEIR CLEAR OPENING SIZES
 SHALL BE SHOWN IN THE SCHEDULE.- REFER TO SECTION
 R310.1.
 20) A-4: COVERED PATIO- A BOND BREAK SHALL BE PROVIDED
 BETWEEN THE WATER RESISTIVE BARRIER AND THE STUCCO-
 REFER TO SECTION R703.6.3 AND CHOOSE ONE OF THE THREE
 METHODS SHOWN. PLEASE NOTE THAT HIGH RIB LATH (3/8") IS
 REQUIRED FOR CEILING INSTALLATIONS PER THE ASTM C1063
 STANDARD.
 21) A-4: PROVIDE ROUGH FRAMING AND EXTERIOR FINISH
 DETAILS FOR THE COVERED ENTRY AND OUTDOOR KITCHEN
 CEILINGS.
 22) A- 6: PROVIDE ATTIC VENTILATION CALCULATIONS IN
 ACCORDANCE WITH SECTIONS R806.1 & R806.2.
 23) E-1: CARBON MONOXIDE DETECTORS SHALL BE INSTALLED
 WITHIN 10' OF EACH BEDROOM- SECTION R315.1.
 24) PRODUCT APPROVALS REQUIRED BUT NOT INCLUDED IN THE
 SUBMITTAL PACKAGE:
 A) ROOF TILE AND INSTALLATION COMPONENTS- UNDERLAYMENT,
 FOAM ADHESIVE- IF TO BE USED.
 B) #1 FOYER DOOR.
 C) #12 MASTER BEDRM WOOD FRAME ENTRY DOOR.
 D) #17 BREAKFAST WOOD FRAME ENTRY DOOR.
 E) #20 CABANA WOOD FRAME ENTRY DOOR.
 F) #30 GARAGE METAL FRAME ENTRY DOOR.
 PLEASE NOTE IN REGARD TO THE SUBMITTAL PACKAGE: A) ALL
 SUBMITTALS FOR WINDOWS AND DOORS ARE PGT "ALUMINUM"
 WHICH IS IN CONFLICT WITH THE SCHEDULES- PLEASE
 CORRECT. B) DUPLICATE COPIES OF THE WINDOW AND DOOR
 PRODUCT APPROVALS (EXCEPT GARAGE) WERE NOT SUBMITTED.
 C) ALL PRODUCT APPROVALS OR NOA'S MUST BE REVIEWED AND
 APPROVED BY THE DESIGN PROFESSIONAL RECORD WHO SHALL
 CIRCLE, HIGHLIGHT, OR OTHERWISE MARK ALL APPLICABLE
 INSTALLATION NOTES AND DETAILS, FRAME AND GLASS TYPES,
 DESIGN PRESSURES, ANCHORS ETC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-11-09 Cont ID  
Sent By albarran Date 2015-11-09 Time 13:32 Rev Time 0.00
Received By albarran Date 2015-11-03 Time 17:01 Sent To I
Notes
2015-11-09 13:31:53AFTER A CONVERSATION WITH MR. BASSETT. I NOTICED THAT
 THE CONFUSION WITH SHEET E2 MISSING WAS BECAUSE THE
 "DELTA 2" REVISION MARKING HAD NOT BEEN PLACED ON THE
 TITLE BLOCK AND THE PAGE HAD FOR THAT REASON
 INADVERTENTLY MARKED AS VOID.
2015-11-09 11:53:38A NARRATIVE WAS PROVIDED AND IT ADDRESSES CORRECTIONS
 TO BOTH SHEETS E1 & E2, BUT SHEET E2 HAS NOT BEEN
 PLACED INTO THE PLAN SET. I CALLED THE ARCHITECT, MR.
 BESSETTE TO ADVISE.
2015-11-03 17:20:17THIS ELECTRICAL PLAN HAS WAY TOO MANY DEFICIENCIES TO
 TO REVIEW WITHOUT A NARRATIVE ADDRESSING THE MANY
 ISSUES. I PLACED A CALL TO THE NUMBER ON THE
 RE-SUBMITTAL FORM ASKING FOR A CALL BACK FROM THE
 DESIGN PROFESSIONAL OR THE PERSON RESPONSIBLE FOR THE
 ELECTRICAL DRAWINGS. IN THE MEANTIME WHILE I WAIT FOR
 THE NARRATIVE, THIS FILE WILL REMAIN ON MY DESK.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-10-28 Cont ID  
Sent By albarran Date 2015-10-28 Time 17:19 Rev Time 0.00
Received By albarran Date 2015-10-28 Time 14:56 Sent To I
Notes
2015-10-28 17:22:04FAILURE TO SUBMIT THE REQUIRED NARRATIVE PROMPTED ME TO
 PERFORM A COMPLETE REVIEW OF THE PLANS FOR THE ABOVE
 MENTIONED PERMIT APPLICATION FOR COMPLIANCE WITH THE
 2008 EDITION OF THE NEC, (NATIONAL ELECTRICAL CODE);
 2010 EDITION OF THE FBC, (FLORIDA BUILDING CODE) AS
 APPLICABLE AND BELOW ARE THE DEFICIENCIES NOTED.
  
 1. PADDLE FAN OUTLET BOXES SHALL COMPLY W/NEC 314.27(D)
 AND SUPPORT THE SPECIFIC WEIGHT.
 2. FBC-ENERGY CONSERVATION CODE SECTION 402.4.5
 RECESSED LIGHTING INSTALLED IN THE BUILDING THERMAL
 ENVELOPE SHALL BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACES. ALL RECESSED
 LUMINAIRES SHALL BE IC-RATED AND SEALED TO REDUCE
 TRANSMISSION OF AIR BETWEEN IT AND THE CEILING SURFACE.
 3. BATHROOM 3 LIGHT SHOULD ALSO BE CONTROLLED FROM THE
 BEDROOM ENTRY DOOR ON A 3 WAY SWITCH.
 4. ALL LUMINAIRE OUTLETS ON WALLS OR CEILINGS SHALL
 ABIDE BY THE REQUIREMENTS OF NEC 314.27.
 5. AS PER NEC 210.52(A) THERE IS A MISSING OUTLET ON
 ONE OF THE KITCHEN WALLS.
 6. NEC 210.70(A)(3) REQUIRES A LIGHT INSIDE THE AUX.
 CLOSET ADJACENT TO THE MASTER WATER CLOSET (TOILET) FOR
 SERVICING THE EQUIPMENT INSIDE.
 7. MARK THE LOCATION OF THE METER, MAIN DISCONNECT AND
 PANELS A & B ON THE FLOOR PLAN.
 8. MARK THE LOCATION OF THE WATER HEATERS ON THE FLOOR
 PLAN.
 9. MASTER BATHROOM SPA OUTLET SHALL BE MARKED ON THE
 FLOOR PLAN AND BE ON A GFCI PROTECTED CIRCUIT AND BE
 ACCESSIBLE. REMEMBER THAT THERE SHALL BE AN ACCESS
 OPENING LARGE ENOUGH TO REMOVE THE PUMP MOTOR W/O
 HAVING TO TEAR ANY OF THE WALL.
 10. THE CENTRAL VACUUM CLEANER SYSTEM SHALL BE MARKED
 ON THE FLOOR PLAN. EVERY OUTLET SHALL BE INDICATED ON
 THE PLANS AND BE CONNECTED TO THE EQUIPMENT GROUND AS
 INDICATED IN NEC 422.15
 11. MAIN DISCONNECT SHALL HAVE LUGS LISTED FOR
 MULTI-CONDUCTOR AS STATED IN NEC 110.14.
 12. INTER-SYSTEM BONDING LUGS AS INDICATED IN NEC
 250.94 SHALL BE PROVIDED.
 13. CORRECT FEEDER LABELS TO PANELS A & B. 3 3/0 & 1 #4
 IN EACH, AS THERE IS A FEEDER FOR EACH PANEL. THIS
 WORDING IS MISLEADING; INDICATIVE OF FEEDERS TO PANEL A
 AND THEN FEEDING B FROM IT. YET THE DIAGRAM SHOWS ONE
 TO EACH.
 14. POOL AND ALL ASSOCIATED ELECTRIC SHALL BE UNDER A
 SEPARATE PERMIT WITH A SEPARATE SUBMITTAL PACKAGE.
 15. CORRECT CONDUCTOR INSULATION NOTE. CONDITIONS AND
 NOT SIZING DICTATE CONDUCTOR INSULATION REQUIREMENTS.
 16. NOTE 16 STATES THAT GAS APPLIANCES ARE IN USE. THIS
 IS CONTRARY TO INDICATIONS IN ELECTRICAL PANEL
 SCHEDULES. CORRECT ACCORDINGLY.
 17. RECEPTACLE OUTLETS SHALL BE TAMPER-RESISTANT ?TR?
 AS INDICATED IN NEC 406.11.
 18. ARC-FAULT REQUIREMENTS ARE DICTATED IN NEC 210.12.
 19. YOU SHALL SUBMIT LOAD CALCS FOR EACH PANEL.
  
 THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN
 MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED
 FOR ANOTHER REVIEW.
 WHEN RESUBMITTING, YOU ARE REQUIRED TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ACCOMPANIED WITH
 THE STANDARD CITY RE-SUBMITTAL FORM.
 PLEASE, ADDITIONALLY, INSERT CORRECTED PAGES INTO THE
 SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY
 APPRECIATED.
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-08-31 Cont ID  
Sent By ppetty Date 2015-08-31 Time 08:45 Rev Time 0.00
Received By albarran Date 2015-08-31 Time 07:58 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2015-11-09 Cont ID  
Sent By albarran Date 2015-11-09 Time 13:33 Rev Time 0.00
Received By albarran Date   Time   Sent To  
Notes
2015-11-09 13:36:1511/9/15 PASSED ELECTRICAL REVIEW. ARCHITECT NOTIFIED
 VIA EMAIL. SENT TO LARGE READY BIN "S". MA

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-11-09 Cont ID  
Sent By albarran Date 2015-11-09 Time 13:32 Rev Time 0.00
Received By albarran Date 2015-11-03 Time 10:22 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-10-28 Cont ID  
Sent By albarran Date 2015-10-28 Time 17:24 Rev Time 0.00
Received By albarran Date 2015-10-26 Time 12:55 Sent To  
Notes
2015-10-28 17:28:5210/28/15 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT TO LARGE DENIED BIN "S". MA
2015-10-26 12:55:12RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-13 Cont ID  
Sent By ccole Date 2015-10-13 Time 17:10 Rev Time 0.00
Received By ccole Date 2015-10-08 Time 16:03 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-31 Cont ID  
Sent By lmarchan Date 2015-08-31 Time 08:59 Rev Time 0.00
Received By lmarchan Date 2015-06-30 Time 07:33 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2015-11-12 Cont ID  
Sent By ccole Date 2015-11-12 Time 11:57 Rev Time 0.00
Received By ccole Date 2015-11-12 Time 11:57 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2015-10-27 Cont ID  
Sent By ccole Date 2015-10-27 Time 12:25 Rev Time 0.00
Received By ccole Date 2015-10-27 Time 12:25 Sent To  
Notes
2015-10-27 12:27:46PERMIT #15061348
 10/27/15
  
 1) 3RD REQUEST!!!
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-10-27 Cont ID  
Sent By ccole Date 2015-10-13 Time 12:23 Rev Time 0.00
Received By ccole Date 2015-10-13 Time 17:14 Sent To  
Notes
2015-10-13 17:15:3110/13/15
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-08-26 Cont ID  
Sent By skennedy Date 2015-08-26 Time 12:03 Rev Time 0.00
Received By skennedy Date 2015-08-26 Time 12:03 Sent To  
Notes
2015-08-26 12:03:36PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-08-26 Cont ID  
Sent By ccole Date 2015-08-26 Time 11:55 Rev Time 0.00
Received By ccole Date 2015-08-26 Time 11:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-10-09 Cont ID  
Sent By ccole Date 2015-10-13 Time 17:10 Rev Time 0.00
Received By gjohnson Date 2015-10-09 Time 15:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-07-22 Cont ID  
Sent By gjohnson Date 2015-07-22 Time 08:44 Rev Time 0.00
Received By gjohnson Date 2015-07-22 Time 08:44 Sent To  
Notes
2015-07-22 08:54:197/22/15 PLUMBING REVIEW DENIED
  
  
 FBC 2010
  
 1.LAUNDRY SINK AND WASHING MACHINE MUST TIE INTO
 BUILDING DRAIN DOWN STREAM OF BATHROOM GROUP. FBCR
 P3108.1
  
 2. WATER CLOSET AND BIDET IN MASTER BATHROOM NOT VENTED
 MUST TIE INTO BATHROOM GROUP. FBC P3105.1
  
 3.ALL SINKS AND LAVATORY'S MUST BE VENTED. FBC
 P3101.2.1
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 561-805-6611
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2015-07-08 Cont ID  
Sent By sgraham Date 2015-07-08 Time 14:37 Rev Time 0.00
Received By sgraham Date 2015-07-08 Time 14:37 Sent To  
Notes
***NONE***