| Plan Review Stops For Permit 15061339 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2016-02-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-02-05 |
Time |
14:27 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-02-05 |
Time |
12:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2016-01-19 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-01-19 |
Time |
13:49 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2016-01-19 |
Time |
13:05 |
Sent To |
|
|
| Notes |
| 2016-01-19 13:25:56 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 15061339 | | | ADD: 5209 BROADWAY | | | CONT: PROFESSIONAL FINISHES | | | TEL: ( 561)746-1517 | | | E-MAIL: [email protected] | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | DATE: TUES. JAN. 19/2016 | | | ACTION: DENIED | | | | | | 1) COMPLIED. | | | | | | 2) SHEET A-0.00 INDICATES NEW OPENINGS AND OR | | | REPLACEMENT OF : | | | 2.1) EXTERIOR DOORS, SUBMITTED, NOT REVIEWED BY THE | | | DESIGNER OF RECORD. | | | 2.2) OVERHEAD COUNTER ROLL UP WINDOW. SUBMITTED, NOT | | | REVIEWED BY THE DESIGNER OF RECORD. | | | 2. 3) GLASS BLOCKWINDOWS. SUBMITTED, NOT REVIEWED BY | | | THE DESIGNER OF RECORD. | | | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) | | | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT | | | WILL REQUIRE PRODUCT APPROVALS: | | | (31)(A) EXTERIOR DOORS. | | | (B) WINDOWS | | | | | | 3) 2ND REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS. | | | THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE | | | 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE | | | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING | | | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. | | | | | | 4) COMPLIED. WIND DESIGN CRITERIA . AND PRESSURES HAS | | | BEEN PROVIDED FOR THE NEW OR REPLACEMENT OPENINGS. | | | | | | | | | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2015-07-17 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-07-17 |
Time |
12:13 |
Rev Time |
|
| Received By |
jwitmer |
Date |
2015-07-17 |
Time |
|
Sent To |
|
|
| Notes |
| 2015-07-17 12:13:23 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 15061339 | | | ADD: 5209 BROADWAY | | | CONT: PROFESSIONAL FINISHES | | | TEL: ( 561)746-1517 | | | E-MAIL: [email protected] | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: FRI. JULY 17/2017 | | | ACTION: DENIED | | | | | | 1) SHEET 0.00 DETAIL # 6 SHOWS A 36 TALL SIGNAGE | | | STRUCTURE ATTACHED TO THE EXISITNG CONCRETE BEAM. | | | REFERS TO STRUCTURAL SHEET. SHEET S-1 DOES NOT HAVE ANY | | | SUCH DETAILS. 107.2.1.3 ADDITIONAL INFORMATION IS | | | EQUIRED FOR ATTACHMENT AND WIND LOADING, TYPE OF | | | MATERIALS. | | | | | | 2) SHEET A-0.00 INDICATES NEW OPENINGS AND OR | | | REPLACEMENT OF 1) EXTERIOR DOORS, 2) OVERHEAD COUNTER | | | ROLL UP WINDOW & 3) GLASS BLOCKWINDOWS. THIS REVIEW NO | | | SUCH PRODUCT APPROVALS WERE SUBMITTED. | | | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) | | | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT | | | WILL REQUIRE PRODUCT APPROVALS: | | | (31)(A) EXTERIOR DOORS. | | | (B) WINDOWS | | | | | | 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS | | | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | 4) NO WIND DESIGN CRITERIA AND PRESSURES HAS BEEN | | | PROVIDED FOR THE NEW OR REPLACEMENT OPENINGS. | | | | | | 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- | | | CHAPTER 6 OF ASCE 7-10. | | | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C | | | 1609.3 WIND SPEED CONVERSION | | | 4.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN | | | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 | | | | | | 4.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. | | | | | | 4.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN | | | ACCORDANCE WITH 1609.4 & ASCE 7-10 | | | | | | 4.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * | | | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. | | | | | | 4.5) COMPONENTS & CLADDING PRESSURES POSITIVE & | | | NEGATIVE TABLE 1609.2(2) . | | | | | | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2016-01-12 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2016-01-12 |
Time |
10:15 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2016-01-12 |
Time |
09:52 |
Sent To |
|
|
| Notes |
| 2016-01-12 10:16:41 | THOUGH THIS HAD PREVIOUSLY BEEN APPROVED WITH PROVISO. | | | THE PROVISO CONCERNS HAVE BEEN ADDRESSED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2015-07-23 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-07-23 |
Time |
18:28 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-07-23 |
Time |
17:34 |
Sent To |
I |
|
| Notes |
| 2015-07-23 18:30:33 | IMPORTANT NOTICE: RACEWAYS EXPOSED TO VARYING | | | TEMPERATURES AS IN THE COLD STORAGE AREAS SHALL BE | | | SEALED TO PREVENT THE WARM AIR FROM CIRCULATING INTO | | | THE COLDER SECTION OF THE RACEWAY. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2016-03-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-03-10 |
Time |
17:11 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-03-10 |
Time |
17:11 |
Sent To |
|
|
| Notes |
| 2016-03-10 17:12:10 | PROVISO | | | | | | PARKING LOT STRIPING, DUMPSTER ENCLOSURE REQUIRE | | | SEPARATE PERMITS, REVIEWS AND FEES | | | | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2016-01-06 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2015-12-31 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2015-12-31 |
Time |
08:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2015-07-09 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2015-07-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2015-07-09 |
Time |
13:54 |
Sent To |
|
|
| Notes |
| 2015-07-09 15:19:35 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THE SUBMITTED WERE LOOSE, NOT ORGANIZED AND NOT | | | BOUND PER SET. PLEASE BIND ON THE RESUBMITTAL. | | | | | | 2) COVER SHEET - INDICATES INCORRECT CODES. THE | | | PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE 5TH | | | EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING THE | | | 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER | | | APPLICABLE CODES OR STANDARDS. | | | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF | | | NFPA 241, 2009 EDITION. | | | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS | | | OF NFPA 10, 2010 EDITION. | | | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. | | | | | | 3) SHEET A 0.00 & E2 - ADD TWO (2) EXIT SIGNS ON EACH | | | SIDE OF THE MARKET PLACE TOWARDS THE CENTER LEADING AND | | | DIRECTING OUT FROM THE BACK CORNER AND FROM THE CENTER | | | LEADING AND DIRECTING TO THE REAR CORRIDOR AND EXIT. | | | | | | 4) SHEET A1.01 - INDICATES TWO EXIT DOORS WITH PANIC | | | HARDWARE AND SECURITY LOCKS. THEY SHALL COMPLY WITH | | | NFPA 101, CHAPER 36, 36..2.2.2 AND CHAPTER 7. | | | 7.2.2.1.5.5 , THE DOOR HAVE HAVE AN INTERIOR KEYED DOOR | | | LOCK (AND NO LATCH) WITH A READILY VISIBLE SIGN STATING | | | THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING IS | | | OCCUPIED. SIGN LETTERS SHALL BE AT LEAST 1 INCH IN | | | HEIGHT. THE KEYED LOCK TO BE EQUIPPED WITH AN | | | ?OPEN/LOCKED? INDICATOR WINDOW (SUCH AS ADAMS RITE 4089 | | | OR SIMILAR). |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2016-03-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-03-10 |
Time |
17:12 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-01-29 |
Time |
10:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-01-19 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2016-01-19 |
Time |
13:49 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-12-28 |
Time |
14:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-07-23 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-07-23 |
Time |
18:31 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-06-29 |
Time |
10:04 |
Sent To |
|
|
| Notes |
| 2015-07-23 18:34:50 | 7/23/15 - FAILED ALL BUT ELECTRICAL REVIEW. CONTRACTOR | | | NOTIFIED VIA EMAIL. SENT TO LARGE DENIED BIN "P". MA |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2016-02-08 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-02-08 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-02-08 |
Time |
14:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2016-01-07 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-01-07 |
Time |
13:32 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-01-07 |
Time |
13:32 |
Sent To |
|
|
| Notes |
| 2016-01-07 13:51:59 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15061339 | | | 01/07/16 | | | | | | 1) THE RE-SUBMITTED PLANS INDICATE A NEW AC SYSTEM FOR | | | THE STAGING AREA: A) PROVIDE AC COOLING AND HEATING | | | CALCULATIONS- SECTION 503.2.1 FBC-10 ENERGY | | | CONSERVATION. B) PROVIDE ENERGY CALCULATIONS- SECTION | | | 101.5 FBC-10 ENERGY CONSERVATION. | | | 2) SHOW THE CONDENSATE PIPING RUN AND DISCHARGE | | | LOCATION- SECTION 307.2.1 FBC-10 MECHANICAL. | | | 3) HOW IS MAKE-UP AIR BEING PROVIDED FOR THE BATH | | | EXHAUST SYSTEM- SECTION 501.3 FBC-10 MECHANICAL. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2015-07-10 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-07-10 |
Time |
14:19 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-07-10 |
Time |
14:25 |
Sent To |
|
|
| Notes |
| 2015-07-10 14:28:45 | 1ST REVIEW: FBC 2010 MECHANICAL | | | | | | 1) THE PLAN SETS SUBMITTED ARE LOOSE AND NOT BOUND | | | TOGTHER PROPERLY FOR REVIEWING: PLEASE CORRECT- SECTION | | | 107.2.1.4 WPB AMENDENTS TO THE FLORIDA BUILDING CODE- | | | 2010. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2016-01-08 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-01-08 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-01-08 |
Time |
15:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2015-07-23 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-07-23 |
Time |
04:48 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-07-23 |
Time |
03:59 |
Sent To |
|
|
| Notes |
| 2015-07-23 04:37:31 | 1) SHOW THE INSIDE CLEAR DIMENSIONS (LXW) OF THE TOILET | | | ROOM. A MINIMUM OF 85 INCHES IN WIDTH IS REQUIRED. 2010 | | | FBC-ACCESSIBILITY SEC.604.3, FBC-PLUMBING SEC. 405.3.1. | | | 2) SHT.A-1.01 - THE GRAB BARS SHALL BE MEASURED TO THE | | | TOP OF GRIPPING SURFACE, NOT TO THE CENTERLINE FROM THE | | | FINISH FLOOR PER 2010 FBC-ACCESSIBILITY SEC. 609.4. | | | 3) SHT. A-1.01 - THE TOILET PAPER DISPENSER SHALL BE | | | LOCATED 7-9 INCHES IN FRONT OF THE WATER CLOSET PER | | | 2010 FBC -ACCESSIBILITY SEC.604.7. | | | 4) SHT. P-2 - A SHUTOFF VALVE IS REQUIRED ON THE HOSE | | | BIBB. 2010 FBC-PLUMBING SEC.606.2. | | | 5) SUBMIT 2 COPIES OF MANUFACTURER'S SPECIFICATIONS FOR | | | THE EEMAX TANKLESS WATER HEATER. WPB AMEND. TO 2010 FBC | | | SEC. 107.2.1. | | | 6) WHAT IS THE PURPOSE OF THE 3-COMPARTMENT SINK? IS | | | THE SINK NEW OR EXISTING? WHAT IS BEING DISCHARGED INTO | | | THE FIXTURE? IS THERE AN EXISTING GREASE TRAP FOR THIS | | | STORE? IF ANY TYPE OF GREASY WASTE IS BEING DISCHARGED | | | INTO THE 3 COMPARTMENT SINK, A GREASE TRAP OR GREASE | | | INTERCEPTOR MAY BE REQUIRED. IF THERE IS AN EXISTING | | | GREASE TRAP, SHOW THE LOCATION ON THE SITE PLAN. 2010 | | | FBC -PLUMBING, SEC.1003.3.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2016-02-09 |
|
|
Cont ID |
|
| Sent By |
dkittred |
Date |
2016-02-09 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
dkittred |
Date |
2016-02-09 |
Time |
08:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2016-01-05 |
|
|
Cont ID |
|
| Sent By |
dkittred |
Date |
2016-01-05 |
Time |
14:55 |
Rev Time |
0.00 |
| Received By |
dkittred |
Date |
2015-12-31 |
Time |
11:39 |
Sent To |
|
|
| Notes |
| 2016-01-05 14:55:20 | PLANNING AND ZONING COMMENTS: ***FAILED*** | | | | | | 1/5/16 | | | | | | 1. SIGNED AND SEALED SURVEY WAS NOT INCLUDED IN THE | | | RESUBMITTAL AS INDICATED IN THE RESUBMITTAL LETTER. | | | | | | 2. SEPARATE PERMIT SUBMITTAL IS REQUIRED FOR | | | LANDSCAPING. LANDSCAPE PERMIT CAN NOT BE REVIEWED AND | | | ISSUED UNDER THE PERMIT FOR BUILDING IMPROVEMENTS. | | | | | | 3. PROVIDE SCREENING AROUND GROUND MOUNTED A/C UNIT. | | | | | | | | | GENERAL COMMENTS: | | | | | | A. WHEN SEPARATE PERMIT IS PULLED FOR FENCING, SOLID | | | OPAQUE FENCE WILL BE REQUIRED ALONG THE WEST PROPERTY | | | LINE. | | | | | | B. NOTES HAVE BEEN ADDED TO THE SITE PLAN DEPICTING | | | MINIMUM BICYCLE PARKING SPACING. | | | | | | C. NOTES ADDED TO PLAN AND STANDARD DETAIL FOR PARKING | | | STRIPING HAS BEEN ADDED TO THE PLAN. | | | | | | D. DUMPSTER PICK-UP/ACCESS TO BE APPROVED BY | | | ENGINEERING & PUBLIC WORKS. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT: | | | | | | DANIELLE J. KITTREDGE, AICP | | | SENIOR PLANNER | | | PLANNING & ZONING DIVISION | | | PHONE: (561)-822-1443 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2015-07-10 |
|
|
Cont ID |
|
| Sent By |
dkittred |
Date |
2015-07-10 |
Time |
16:12 |
Rev Time |
0.00 |
| Received By |
dkittred |
Date |
2015-07-10 |
Time |
14:43 |
Sent To |
|
|
| Notes |
| 2015-07-10 15:51:24 | PLANNING AND ZONING COMMENTS: ***FAILED*** | | | | | | 7/10/15 | | | | | | 1. DIMENSION BUILDING HEIGHT AND MAXIMUM OVERALL HEIGHT | | | OF THE STRUCTURE WITH THE ADDITION OF THE AC SCREENING | | | PANELS. | | | | | | 2. SURVEY SUBMITTED WILL NEED TO BE A SIGNED AND SEALED | | | SURVEY. | | | | | | 3. SEPARATE PERMIT REQUIRED FOR LANDSCAPING. THE VALUE | | | OF THE CONSTRUCTION EXCEEDS 50% OF THE STRUCTURE'S | | | VALUE ($38,566) ACCORDING TO THE P.B.C. PROPERTY | | | APPRAISER'S OFFICE; THEREFORE, PURSUANT TO SECTION | | | 94-441(C)(2) OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE | | | IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN | | | ARTICLE XIV OF THE ZLDR. PLEASE REVIEW SITE TO SEE | | | WHERE LANDSCAPE ISLAND(S) AND/OR FOUNDATIONS PLANTINGS | | | CAN BE ADDED AND ALSO ADJUST SITE PLAN ACCORDINGLY. | | | | | | 4. SEPARATE PERMIT IS REQUIRED FOR SIGNAGE. PLEASE | | | REVIEW ZLDR SEC. 94-221(E) FOR BMUD TYPE II SIGN | | | STANDARDS AS WELL AS ZLDR SEC. 94-402(B) DESCRIBING | | | PROHIBITED TYPES OF SIGNAGE AND RELATED EQUIPMENT. | | | | | | 5. SEPARATE PERMIT REQUIRED FOR FENCE. PLEASE INDICATE | | | THE TYPE OF FENCE MATERIAL BEING USED FOR THE 6 FOOT | | | PERIMETER FENCE. | | | | | | 6. WHILE SCOPE OF THE PROJECT DOES NOT TRIGGER | | | COMPLIANCE WITH BICYCLE PARKING REQUIREMENTS, IT IS | | | STRONGLY ENCOURAGED THAT BICYCLE PARKING BE PROVIDED | | | ON-SITE AND ADDED TO THE SITE PLAN. IF ADDING BICYCLE | | | PARKING, PLEASE BE SURE TO INCLUDE THE RACK STYLE (WAVE | | | STYLE IS NOT PERMITTED) AND INDICATE BICYCLE PARKNG | | | DIMENSIONS (WHICH I CAN PROVIDE IF NEEDED). | | | | | | 7. FENCING AROUND DUMPSTER ENCLOSURE WILL NEED TO BE OF | | | AN OPAQUE MATERIAL. PLEASE CLARIFY ON PLAN AS IT IS | | | ONLY THE GATES ARE CLEARLY SHOWN AS BEING OPAQUE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT: | | | | | | DANIELLE J. KITTREDGE, AICP | | | SENIOR PLANNER | | | PLANNING & ZONING DIVISION | | | PHONE: (561)-822-1443 | | | EMAIL: [email protected] | | | |
|
|