Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-02-05 Cont ID  
Sent By jwitmer Date 2016-02-05 Time 14:27 Rev Time 0.00
Received By jwitmer Date 2016-02-05 Time 12:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-01-19 Cont ID  
Sent By jwitmer Date 2016-01-19 Time 13:49 Rev Time 0.00
Received By jwitmer Date 2016-01-19 Time 13:05 Sent To  
Notes
2016-01-19 13:25:56BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15061339
 ADD: 5209 BROADWAY
 CONT: PROFESSIONAL FINISHES
 TEL: ( 561)746-1517
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. JAN. 19/2016
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) SHEET A-0.00 INDICATES NEW OPENINGS AND OR
 REPLACEMENT OF :
 2.1) EXTERIOR DOORS, SUBMITTED, NOT REVIEWED BY THE
 DESIGNER OF RECORD.
 2.2) OVERHEAD COUNTER ROLL UP WINDOW. SUBMITTED, NOT
 REVIEWED BY THE DESIGNER OF RECORD.
 2. 3) GLASS BLOCKWINDOWS. SUBMITTED, NOT REVIEWED BY
 THE DESIGNER OF RECORD.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
  
 3) 2ND REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 4) COMPLIED. WIND DESIGN CRITERIA . AND PRESSURES HAS
 BEEN PROVIDED FOR THE NEW OR REPLACEMENT OPENINGS.
  
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-07-17 Cont ID  
Sent By jwitmer Date 2015-07-17 Time 12:13 Rev Time  
Received By jwitmer Date 2015-07-17 Time   Sent To  
Notes
2015-07-17 12:13:23BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15061339
 ADD: 5209 BROADWAY
 CONT: PROFESSIONAL FINISHES
 TEL: ( 561)746-1517
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JULY 17/2017
 ACTION: DENIED
  
 1) SHEET 0.00 DETAIL # 6 SHOWS A 36 TALL SIGNAGE
 STRUCTURE ATTACHED TO THE EXISITNG CONCRETE BEAM.
 REFERS TO STRUCTURAL SHEET. SHEET S-1 DOES NOT HAVE ANY
 SUCH DETAILS. 107.2.1.3 ADDITIONAL INFORMATION IS
 EQUIRED FOR ATTACHMENT AND WIND LOADING, TYPE OF
 MATERIALS.
  
 2) SHEET A-0.00 INDICATES NEW OPENINGS AND OR
 REPLACEMENT OF 1) EXTERIOR DOORS, 2) OVERHEAD COUNTER
 ROLL UP WINDOW & 3) GLASS BLOCKWINDOWS. THIS REVIEW NO
 SUCH PRODUCT APPROVALS WERE SUBMITTED.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
  
 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) NO WIND DESIGN CRITERIA AND PRESSURES HAS BEEN
 PROVIDED FOR THE NEW OR REPLACEMENT OPENINGS.
  
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 4.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 4.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 4.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 4.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-01-12 Cont ID  
Sent By albarran Date 2016-01-12 Time 10:15 Rev Time 0.00
Received By albarran Date 2016-01-12 Time 09:52 Sent To  
Notes
2016-01-12 10:16:41THOUGH THIS HAD PREVIOUSLY BEEN APPROVED WITH PROVISO.
 THE PROVISO CONCERNS HAVE BEEN ADDRESSED.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-07-23 Cont ID  
Sent By albarran Date 2015-07-23 Time 18:28 Rev Time 0.00
Received By albarran Date 2015-07-23 Time 17:34 Sent To I
Notes
2015-07-23 18:30:33IMPORTANT NOTICE: RACEWAYS EXPOSED TO VARYING
 TEMPERATURES AS IN THE COLD STORAGE AREAS SHALL BE
 SEALED TO PREVENT THE WARM AIR FROM CIRCULATING INTO
 THE COLDER SECTION OF THE RACEWAY.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2016-03-10 Cont ID  
Sent By shill Date 2016-03-10 Time 17:11 Rev Time 0.00
Received By shill Date 2016-03-10 Time 17:11 Sent To  
Notes
2016-03-10 17:12:10PROVISO
  
 PARKING LOT STRIPING, DUMPSTER ENCLOSURE REQUIRE
 SEPARATE PERMITS, REVIEWS AND FEES
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-01-06 Cont ID  
Sent By pleduc Date 2015-12-31 Time   Rev Time 0.00
Received By pleduc Date 2015-12-31 Time 08:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-07-09 Cont ID  
Sent By pleduc Date 2015-07-09 Time   Rev Time 0.00
Received By pleduc Date 2015-07-09 Time 13:54 Sent To  
Notes
2015-07-09 15:19:35THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE SUBMITTED WERE LOOSE, NOT ORGANIZED AND NOT
 BOUND PER SET. PLEASE BIND ON THE RESUBMITTAL.
  
 2) COVER SHEET - INDICATES INCORRECT CODES. THE
 PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE 5TH
 EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING THE
 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 3) SHEET A 0.00 & E2 - ADD TWO (2) EXIT SIGNS ON EACH
 SIDE OF THE MARKET PLACE TOWARDS THE CENTER LEADING AND
 DIRECTING OUT FROM THE BACK CORNER AND FROM THE CENTER
 LEADING AND DIRECTING TO THE REAR CORRIDOR AND EXIT.
  
 4) SHEET A1.01 - INDICATES TWO EXIT DOORS WITH PANIC
 HARDWARE AND SECURITY LOCKS. THEY SHALL COMPLY WITH
 NFPA 101, CHAPER 36, 36..2.2.2 AND CHAPTER 7.
 7.2.2.1.5.5 , THE DOOR HAVE HAVE AN INTERIOR KEYED DOOR
 LOCK (AND NO LATCH) WITH A READILY VISIBLE SIGN STATING
 THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING IS
 OCCUPIED. SIGN LETTERS SHALL BE AT LEAST 1 INCH IN
 HEIGHT. THE KEYED LOCK TO BE EQUIPPED WITH AN
 ?OPEN/LOCKED? INDICATOR WINDOW (SUCH AS ADAMS RITE 4089
 OR SIMILAR).

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-03-10 Cont ID  
Sent By shill Date 2016-03-10 Time 17:12 Rev Time 0.00
Received By shill Date 2016-01-29 Time 10:14 Sent To  
Notes
2016-02-01 10:16:30C03

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-01-19 Cont ID  
Sent By jwitmer Date 2016-01-19 Time 13:49 Rev Time 0.00
Received By jwitmer Date 2015-12-28 Time 14:59 Sent To  
Notes
2015-12-28 14:59:40C37

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-23 Cont ID  
Sent By albarran Date 2015-07-23 Time 18:31 Rev Time 0.00
Received By albarran Date 2015-06-29 Time 10:04 Sent To  
Notes
2015-07-23 18:34:507/23/15 - FAILED ALL BUT ELECTRICAL REVIEW. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT TO LARGE DENIED BIN "P". MA

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-02-08 Cont ID  
Sent By ccole Date 2016-02-08 Time 14:57 Rev Time 0.00
Received By ccole Date 2016-02-08 Time 14:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-01-07 Cont ID  
Sent By ccole Date 2016-01-07 Time 13:32 Rev Time 0.00
Received By ccole Date 2016-01-07 Time 13:32 Sent To  
Notes
2016-01-07 13:51:592ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15061339
 01/07/16
  
 1) THE RE-SUBMITTED PLANS INDICATE A NEW AC SYSTEM FOR
 THE STAGING AREA: A) PROVIDE AC COOLING AND HEATING
 CALCULATIONS- SECTION 503.2.1 FBC-10 ENERGY
 CONSERVATION. B) PROVIDE ENERGY CALCULATIONS- SECTION
 101.5 FBC-10 ENERGY CONSERVATION.
 2) SHOW THE CONDENSATE PIPING RUN AND DISCHARGE
 LOCATION- SECTION 307.2.1 FBC-10 MECHANICAL.
 3) HOW IS MAKE-UP AIR BEING PROVIDED FOR THE BATH
 EXHAUST SYSTEM- SECTION 501.3 FBC-10 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-07-10 Cont ID  
Sent By ccole Date 2015-07-10 Time 14:19 Rev Time 0.00
Received By ccole Date 2015-07-10 Time 14:25 Sent To  
Notes
2015-07-10 14:28:451ST REVIEW: FBC 2010 MECHANICAL
  
 1) THE PLAN SETS SUBMITTED ARE LOOSE AND NOT BOUND
 TOGTHER PROPERLY FOR REVIEWING: PLEASE CORRECT- SECTION
 107.2.1.4 WPB AMENDENTS TO THE FLORIDA BUILDING CODE-
 2010.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-01-08 Cont ID  
Sent By gjohnson Date 2016-01-08 Time 15:49 Rev Time 0.00
Received By gjohnson Date 2016-01-08 Time 15:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-07-23 Cont ID  
Sent By tklarge Date 2015-07-23 Time 04:48 Rev Time 0.00
Received By tklarge Date 2015-07-23 Time 03:59 Sent To  
Notes
2015-07-23 04:37:311) SHOW THE INSIDE CLEAR DIMENSIONS (LXW) OF THE TOILET
 ROOM. A MINIMUM OF 85 INCHES IN WIDTH IS REQUIRED. 2010
 FBC-ACCESSIBILITY SEC.604.3, FBC-PLUMBING SEC. 405.3.1.
 2) SHT.A-1.01 - THE GRAB BARS SHALL BE MEASURED TO THE
 TOP OF GRIPPING SURFACE, NOT TO THE CENTERLINE FROM THE
 FINISH FLOOR PER 2010 FBC-ACCESSIBILITY SEC. 609.4.
 3) SHT. A-1.01 - THE TOILET PAPER DISPENSER SHALL BE
 LOCATED 7-9 INCHES IN FRONT OF THE WATER CLOSET PER
 2010 FBC -ACCESSIBILITY SEC.604.7.
 4) SHT. P-2 - A SHUTOFF VALVE IS REQUIRED ON THE HOSE
 BIBB. 2010 FBC-PLUMBING SEC.606.2.
 5) SUBMIT 2 COPIES OF MANUFACTURER'S SPECIFICATIONS FOR
 THE EEMAX TANKLESS WATER HEATER. WPB AMEND. TO 2010 FBC
 SEC. 107.2.1.
 6) WHAT IS THE PURPOSE OF THE 3-COMPARTMENT SINK? IS
 THE SINK NEW OR EXISTING? WHAT IS BEING DISCHARGED INTO
 THE FIXTURE? IS THERE AN EXISTING GREASE TRAP FOR THIS
 STORE? IF ANY TYPE OF GREASY WASTE IS BEING DISCHARGED
 INTO THE 3 COMPARTMENT SINK, A GREASE TRAP OR GREASE
 INTERCEPTOR MAY BE REQUIRED. IF THERE IS AN EXISTING
 GREASE TRAP, SHOW THE LOCATION ON THE SITE PLAN. 2010
 FBC -PLUMBING, SEC.1003.3.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2016-02-09 Cont ID  
Sent By dkittred Date 2016-02-09 Time 10:31 Rev Time 0.00
Received By dkittred Date 2016-02-09 Time 08:45 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2016-01-05 Cont ID  
Sent By dkittred Date 2016-01-05 Time 14:55 Rev Time 0.00
Received By dkittred Date 2015-12-31 Time 11:39 Sent To  
Notes
2016-01-05 14:55:20PLANNING AND ZONING COMMENTS: ***FAILED***
  
 1/5/16
  
 1. SIGNED AND SEALED SURVEY WAS NOT INCLUDED IN THE
 RESUBMITTAL AS INDICATED IN THE RESUBMITTAL LETTER.
  
 2. SEPARATE PERMIT SUBMITTAL IS REQUIRED FOR
 LANDSCAPING. LANDSCAPE PERMIT CAN NOT BE REVIEWED AND
 ISSUED UNDER THE PERMIT FOR BUILDING IMPROVEMENTS.
  
 3. PROVIDE SCREENING AROUND GROUND MOUNTED A/C UNIT.
  
  
 GENERAL COMMENTS:
  
 A. WHEN SEPARATE PERMIT IS PULLED FOR FENCING, SOLID
 OPAQUE FENCE WILL BE REQUIRED ALONG THE WEST PROPERTY
 LINE.
  
 B. NOTES HAVE BEEN ADDED TO THE SITE PLAN DEPICTING
 MINIMUM BICYCLE PARKING SPACING.
  
 C. NOTES ADDED TO PLAN AND STANDARD DETAIL FOR PARKING
 STRIPING HAS BEEN ADDED TO THE PLAN.
  
 D. DUMPSTER PICK-UP/ACCESS TO BE APPROVED BY
 ENGINEERING & PUBLIC WORKS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2015-07-10 Cont ID  
Sent By dkittred Date 2015-07-10 Time 16:12 Rev Time 0.00
Received By dkittred Date 2015-07-10 Time 14:43 Sent To  
Notes
2015-07-10 15:51:24PLANNING AND ZONING COMMENTS: ***FAILED***
  
 7/10/15
  
 1. DIMENSION BUILDING HEIGHT AND MAXIMUM OVERALL HEIGHT
 OF THE STRUCTURE WITH THE ADDITION OF THE AC SCREENING
 PANELS.
  
 2. SURVEY SUBMITTED WILL NEED TO BE A SIGNED AND SEALED
 SURVEY.
  
 3. SEPARATE PERMIT REQUIRED FOR LANDSCAPING. THE VALUE
 OF THE CONSTRUCTION EXCEEDS 50% OF THE STRUCTURE'S
 VALUE ($38,566) ACCORDING TO THE P.B.C. PROPERTY
 APPRAISER'S OFFICE; THEREFORE, PURSUANT TO SECTION
 94-441(C)(2) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE
 IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. PLEASE REVIEW SITE TO SEE
 WHERE LANDSCAPE ISLAND(S) AND/OR FOUNDATIONS PLANTINGS
 CAN BE ADDED AND ALSO ADJUST SITE PLAN ACCORDINGLY.
  
 4. SEPARATE PERMIT IS REQUIRED FOR SIGNAGE. PLEASE
 REVIEW ZLDR SEC. 94-221(E) FOR BMUD TYPE II SIGN
 STANDARDS AS WELL AS ZLDR SEC. 94-402(B) DESCRIBING
 PROHIBITED TYPES OF SIGNAGE AND RELATED EQUIPMENT.
  
 5. SEPARATE PERMIT REQUIRED FOR FENCE. PLEASE INDICATE
 THE TYPE OF FENCE MATERIAL BEING USED FOR THE 6 FOOT
 PERIMETER FENCE.
  
 6. WHILE SCOPE OF THE PROJECT DOES NOT TRIGGER
 COMPLIANCE WITH BICYCLE PARKING REQUIREMENTS, IT IS
 STRONGLY ENCOURAGED THAT BICYCLE PARKING BE PROVIDED
 ON-SITE AND ADDED TO THE SITE PLAN. IF ADDING BICYCLE
 PARKING, PLEASE BE SURE TO INCLUDE THE RACK STYLE (WAVE
 STYLE IS NOT PERMITTED) AND INDICATE BICYCLE PARKNG
 DIMENSIONS (WHICH I CAN PROVIDE IF NEEDED).
  
 7. FENCING AROUND DUMPSTER ENCLOSURE WILL NEED TO BE OF
 AN OPAQUE MATERIAL. PLEASE CLARIFY ON PLAN AS IT IS
 ONLY THE GATES ARE CLEARLY SHOWN AS BEING OPAQUE.
  