| 2015-11-10 17:38:03 | NEW SINGLE FAMILY RESIDENCE (R3), SECOND BUILDING |
| | REVIEW CHECKLIST. |
| | CODE: 2010 FBC. |
| | |
| | |
| | NOTE: PACKAGE RE-SUBMITTED IS MISSING: |
| | A) THE PERMIT APPLICATION. |
| | B) THE ENERGY CALCULATIONS. |
| | C) THE SOIL TEST REPORT. |
| | |
| | |
| | 1- PLANS NEED TO BE SIGNED AND SEALED AND WITH ORIGINAL |
| | SEAL AND SIGNATURE BY THE ENGINEERS SHOWN ON THE TITLE |
| | BLOCK AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES WHEN |
| | SUBMITTING DRAWINGS FOR PUBLIC RECORDS. NOTE: THERE ARE |
| | TWO DIFFERENT PROFESSIONAL ENGINEERS ON THE TILE BLOCK |
| | OF DRAWINGS SUBMITTED. IT LOOKS LIKE THERE IS AN |
| | STRUCTURAL ENGINEER AND A MEP ENGINEER. DRAWINGS NEED |
| | TO BE SIGNED AND SEALED BY THE ENGINEER RESPONSIBLE FOR |
| | EACH DESIGN. |
| | RESPONSE: INFORMATION ON PLANS SUBMITTED SHOW WHITE |
| | OUT. PLANS WITH WHITE OUT ARE NOT ACCEPTABLE FOR PUBLIC |
| | RECORDS. ORIGINAL PLANS NEED TO BE REVISED SHOWING ONLY |
| | THE INFORMATION OF THE ENGINEER RESPONSIBLE FOR THE |
| | DESIGN. AND, SIGN AND SEAL NEW COPIES ACCORDINGLY. |
| | |
| | 2- SHEET A-1: |
| | A) REVISE THE DESIGN DATA SHOWN ON THE FOOTING NOTES. |
| | THIS BUILDING IS LOCATED IN EXPOSURE "D" NOT EXPOSURE |
| | "B". SEC. R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL. AND |
| | REVISE ALL THE DESIGN PRESSURES ON SHEET A-5 |
| | ACCORDINGLY. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. SHEET A-1 WAS |
| | NOT REVISED. |
| | |
| | B) REVISE THE PROJECT INFORMATION & DESIGN CRITERIA. |
| | THIS BUILDING IS LOCATED IN EXPOSURE "D" NOT EXPOSURE |
| | "C". SEC. R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL. AND |
| | REVISE ALL THE DESIGN PRESSURES ACCORDINGLY. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. SHEET A-1 WAS |
| | NOT REVISED. |
| | |
| | C) PROJECT INFORMATION & DESIGN CRITERIA: SPECIFY THE |
| | ULTIMATE WIND LOAD AND THE NOMINAL WIND LOAD. SEC. |
| | R301.2.1.3. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. SHEET A-1 WAS |
| | NOT REVISED. |
| | |
| | D) CLEARLY SPECIFY THE ATTIC LIVE LOAD ON THE PROJECT |
| | INFORMATION & DESIGN CRITERIA. SEE FOOTNOTES "B" AND |
| | "G" OF TABLE R301.5 AND REVISE DESIGN CRITERIA AS |
| | REQUIRED. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. SHEET A-1 WAS |
| | NOT REVISED. |
| | |
| | 3- TYPICAL WALL SECTION ON SHEET A-2: |
| | A) THERE ARE TWO DIFFERENT NAIL TYPES AND SPACING SPECS |
| | FOR THE ROOF SHEATHING FASTENING. REVISE AS REQUIRED. |
| | SEE SEC. R803.2.3.1. |
| | NOTE: ALSO, COORDINATE WITH ROOF SHEATHING |
| | SPECIFICATIONS SHOWN THE "ROOF SHEATHING DETAIL" AND " |
| | FLOOR & ROOF SHEATHING FASTENER DETAIL" ON SHEET A-4. |
| | |
| | RESPONSE: THERE IS NO COORDINATION BETWEEN INFORMATION |
| | SHOWN ON THE TYPICAL WALL SECTION AND INFORMATION SHOWN |
| | ON SHEET A-4. ALSO, NEED TO SPECIFY RING SHANK NAIL |
| | MIN. AS REQUIRED BY SEC. R803.2.3.1. |
| | |
| | B) PROVIDE SPECS FOR WALL FINISH. "TO MATCH EXIST. |
| | FINISH" DOESN'T APPLY. THERE IS NOT EXISTING FINISH. |
| | THIS IS A NEW HOUSE. SEC. R701. |
| | RESPONSE: FINISH SPECIFICATIONS WERE NOT REVISED. |
| | |
| | C) ENGINEER OF RECORD TO PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS FOR THE STONE VENEER AS REQUIRED BY SEC. |
| | R703.7 OF 2010 FBC-RESIDENTIAL. SPECIFY ALL THE |
| | FASTENERS, ETC. |
| | |
| | 4- SHEET A-3: |
| | A) FLOOR PLAN IS NOT LEGIBLE. IT'S TOO DARK LETTERING |
| | AND NUMBERS ARE HARD TO READ. PLAN IS NOT CLEAR FOR |
| | SCANNING AND FILING PURPOSES. REVISE AS REQUIRED. SEC. |
| | 107.2.1.4 CITY AMENDMENTS. |
| | RESPONSE: SAME DRAWING WAS RE-SUBMITTED. NEW CLEAR AND |
| | LEGIBLE DRAWING WAS NOT SUBMITTED AND THERE IS WHITE |
| | OUT OVER THE PREVIOUS ENGINEER INFORMATION. WHITE OUT |
| | IS NOT ACCEPTABLE ON ANY DRAWING. |
| | |
| | B) SIZE OF ATTIC ACCESS SHOWN BY THE LAUNDRY AREA |
| | DOESN'T COMPLY WITH SEC. R807. REVISE AS REQUIRED. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | C) PROVIDE A BATHROOM WITH A DOOR SIZE THAT COMPLIES |
| | WITH SEC. R320.1.1. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | D) ENGINEER OF RECORD TO SPECIFY ANCHOR FASTENING |
| | SPACING OF THE GARAGE DOOR STRUCTURAL BUCK. IT'S NOT |
| | THE MANUFACTURER'S SPECIFICATIONS. SEC. R301. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 5- ROOF FRAMING PLAN ON SHEET A-4: PROVIDE COMPLETE |
| | ROOF FRAMING PLAN. SPECIFY ALL BEAMS AND LINTELS. |
| | SPECIFY ALL ROOF FRAMING MEMBERS AND CONNECTORS. SEC. |
| | R301. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 6- SHEET A-5: |
| | A) CODE ANALYSIS INFORMATION SHOWN ON TOP OF THE SHEET |
| | IS INCORRECT. SEC. 107.2.1 CITY AMENDMENTS. REVISE AS |
| | REQUIRED. THE 2010 FBC EXISTING BUILDING CODE AND |
| | ALTERATION LEVEL 2 DON'T APPLY. THIS IS NEW |
| | CONSTRUCTION. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | SCREENED PORCH SHOWING COMPLIANCE WITH SEC. R301. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 7- ENERGY CALCULATIONS SUBMITTED: |
| | NOTE: ENERGY CALCULATIONS ARE MISSING FROM THE |
| | RE-SUBMITTAL PACKAGE. UNABLE TO VERIFY IF REVISIONS |
| | WERE DONE. |
| | |
| | A) CONDITIONED AREA DOESN'T MATCH PLANS . REVISE AS |
| | REQUIRED. SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | B) COORDINATE TYPE OF DOORS WITH PLANS AND PRODUCT |
| | APPROVALS SUBMITTED. SEC. 103.2.2 OF 2010 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | 8- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.0002(33) FOR: |
| | A) GARAGE DOORS THAT MEETS THE DESIGN PRESSURES FOR |
| | EXPOSURE "D" AS REQUIRED BY ITEM #2 ABOVE. |
| | RESPONSE: ENGINEER DIDN'T REVISE THE DESIGN PRESSURES |
| | FOR EXPOSURE "D". NEED REVISED DESIGN PRESSURES TO |
| | CHECK PRODUCT APPROVAL SUBMITTED. |
| | |
| | B) WINDOW MULLIONS AS SHOWN ON PLANS. ENGINEER OF |
| | RECORD TO REVISE DESIGN PRESSURES REQUIRED BY ITEM #2 |
| | ABOVE. |
| | RESPONSE: ENGINEER DIDN'T REVISE THE DESIGN PRESSURES |
| | FOR EXPOSURE "D". NEED REVISED DESIGN PRESSURES TO |
| | CHECK PRODUCT APPROVAL SUBMITTED. |
| | |
| | C) FIXED WINDOWS AS SHOWN ON PLANS. |
| | RESPONSE: ENGINEER DIDN'T REVISE THE DESIGN PRESSURES |
| | FOR EXPOSURE "D". NEED REVISED DESIGN PRESSURES TO |
| | CHECK PRODUCT APPROVAL SUBMITTED. |
| | |
| | D) GARAGE SIDE DOOR AS SHOWN ON PLANS. |
| | RESPONSE: ENGINEER DIDN'T REVISE THE DESIGN PRESSURES |
| | FOR EXPOSURE "D". NEED REVISED DESIGN PRESSURES TO |
| | CHECK PRODUCT APPROVAL SUBMITTED. |
| | |
| | E) PRECAST LINTELS AS SHOWN ON PLANS. |
| | RESPONSE: INFORMATION SUBMITTED IS NOT AN APPROVED |
| | PRODUCT APPROVAL. |
| | |
| | F) ALL TRUSS STRUCTURAL CONNECTORS SPECIFIED ON PLANS.. |
| | NOTE: PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER |
| | PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR |
| | ENGINEER OF RECORD TO LIST THE FLORIDA PRODUCT APPROVAL |
| | NEXT TO THE SPECIFIED CONNECTOR. |
| | RESPONSE: COMMENT NOT ADDRESSED. |
| | |
| | G) ENTRY DOORS AS SHOWN ON PLANS. |
| | RESPONSE: ENGINEER DIDN'T REVISE THE DESIGN PRESSURES |
| | FOR EXPOSURE "D". NEED REVISED DESIGN PRESSURES TO |
| | CHECK PRODUCT APPROVAL SUBMITTED. |
| | |
| | H) SLIDING GLASS DOORS AS SHOWN ON SHEET A-3 BY THE |
| | DINING ROOM AREA. THERE IS NOT PRODUCT APPROVAL FOR |
| | SLIDING GLASS DOORS IN THE RE-SUBMITTED PACKAGE. |
| | |
| | I) SINGLE HUNG WINDOWS. INFORMATION FROM JELD-WEN |
| | SUBMITTED DOESN'T HAVE A FLORIDA PRODUCT APPROVAL |
| | NUMBER. PROVIDE THE FLORIDA PRODUCT APPROVAL NUMBER |
| | THAT CORRESPONDS TO PACKAGE SUBMITTED. |
| | |
| | 9- ENGINEER OF RECORD TO APPROVE ABOVE PRODUCT |
| | APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY |
| | AMENDMENTS. |
| | |
| | 10- PROVIDE 2 COPIES OF THE SOIL TEST REPORT AS |
| | REQUIRED BY SEC. R401.4 OF 2010 FBC-RESIDENTIAL. |
| | |
| | 11- TRUSS ENGINEER TO REVISE TRUSS PACKAGE SUBMITTED: |
| | A) THE DESIGN CRITERIA IS INCORRECT. THIS BUILDING IS |
| | LOCATED IN EXPOSURE "D" NOT EXPOSURE "B". REVISE |
| | COMPLETE TRUSS PACKAGE AS REQUIRED. SEC. R301.2.1.4.3 |
| | OF 2010 FBC-RESIDENTIAL. |
| | |
| | B) TRUSS PACKAGE COVER SHEET DOESN'T COMPLY WITH SEC. |
| | 61G15-31.003 OF FLORIDA ADMINISTRATIVE CODE: MISSING |
| | ENGINEER OF RECORD INFORMATION, THE BUILDING WAS |
| | DESIGNED BASED ON THE 2010 FBC NOT 2014 FBC, |
| | |
| | C) ALL INDIVIDUAL TRUSS DRAWINGS NEED A TITLE BLOCK |
| | WITH THE ENGINEER NAME, ADDRESS AND LICENSE NUMBER AND |
| | THE DATE OF THE DRAWING AS REQUIRED BY 1G15-31.003 OF |
| | FLORIDA ADMINISTRATIVE CODE. |
| | |
| | D) REVISE THE ATTIC LIVE LOAD TO COMPLY WITH FOOTNOTES |
| | "B" AND "G" OF TABLE R301.5 OF 2010 FBC-RESIDENTIAL. |
| | |
| | **** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | **** PLEASE REMOVE ANY REVISED SHEET. SUBMIT OLD COPIES |
| | FOR REFERENCE. DON"T STAPLE OLD COPIES TO NEW REVISED |
| | SET. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | (561)805-6712 |
| | [email protected] |