Plan Review Details - Permit 15061267
Plan Review Stops For Permit 15061267
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-10-31 Cont ID  
Sent By shill Date 2015-10-31 Time 11:46 Rev Time 0.00
Received By shill Date 2015-10-30 Time 17:51 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-27 Cont ID  
Sent By S. Hill Date 2015-08-27 Time 07:11 Rev Time 0.00
Received By shill Date 2015-08-27 Time 07:11 Sent To  
Notes
2015-08-27 07:39:34****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. VALUE IS TOO LOW. BASED ON PLANS AND VIOLATION,
 HOUSE HAS BEEN REWIRED, INTERIOR RENOVATION, NEW
 FRAMING AND DRYWALL, DECK, PLUMBING, VALUE TO DATE PER
 CONTRACTOR IS $14,600.
  
 PROVIDE AN ACCURATE MARKET VALUE OF ALL WORK. FBC 109.
  
 2. THERE ARE REFERENCES TO FBC R ON THE PLAN; THIS IS
 NOT APPLICABLE TO THIS STRUCTURE WHICH HAS THREE UNITS.
  
 3. REVISE PLAN TO INDICATE METHOD OF COMPLIANCE, FBC
 2010 EXISTING BUILDING 101.5, AND REVISE PLAN TO SHOW
 COMPLIANCE WITH ALL REQUIREMENTS. THIS APPEARS TO BE A
 LEVEL 3 ALTERATION. IT IS NOT POSSIBLE TO COMPLETE AN
 ACCURATE REVIEW WITHOUT THIS INFORMATION. ALSO DUE TO
 WORK DONE WITHOUT PERMITS IT IS NOT POSSIBLE TO
 DETERMINE WHAT IS ACTUALLY EXISTING AND WHAT WAS
 INSTALLED WITHOUT PERMIT WHICH IS NOW TO BE INCLUDED IN
 THIS RENOVATION.
  
 4. PLANS SHOW AC, BUT NO MECHANICAL INFORMATION
 PROVIDED AND NO EVIDENCE OF A MECHANICAL PERMIT FOR
 THIS STRUCTURE, FBC 105.
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-02-19 Cont ID  
Sent By albarran Date 2016-02-19 Time 10:20 Rev Time 0.00
Received By albarran Date 2016-02-18 Time 15:42 Sent To I
Notes
2016-02-19 10:21:10ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 SATISFACTORILY ADDRESSED. I SPOKE WITH THE DESIGN
 PROFESSIONAL TO CORRECT THE PANEL LABELS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-11-17 Cont ID  
Sent By albarran Date 2015-11-17 Time 21:14 Rev Time 0.00
Received By albarran Date 2015-11-17 Time 20:11 Sent To I
Notes
2015-11-17 21:15:15THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1. PLEASE NOTE THAT THE USE OF A CO DETECTOR IS NOT A
 VIOLATION. THOUGH IT IS NOT A REQUIREMENT BECAUSE THERE
 ARE NO ATTACHED GARAGES OR GAS APPLIANCES, THE EXTRA
 PROTECTION IS WELL WORTH THE EFFORT.
 2. PREVIOUSLY YOU REFERRED TO ?ROMEX? NOW YOU REFER TO
 ?BX? PLEASE NOTE THAT THESE ARE NOT APPROVED WIRING
 METHODS. THE CODE DOES NOT RECOGNIZE ROMEX OR BX.
 CORRECT YOUR NOTE ACCORDINGLY.
 3. INDICATE HOW THE REAR STAIRS ARE BEING ILLUMINATED
 AND SWITCHED. A WALL SCONCE ON THE EXTERIOR DOOR IS NOT
 SUFFICIENT TO ILLUMINATE THE COMPLETE STAIRWAY.
 FURTHERMORE, SHOW THE AUTOMATIC/REMOTE SWITCHING.
 4. CORRECT THE WET LOCATION NOTES AS THE QUOTED CODE
 SECTION EITHER DO NOT EXIST OR ARE INAPPLICABLE.
 5. NEC REQUIRES A LIGHT ON THE OUTSIDE OF THE FRONT
 DOOR OF THE BLDG.
 6. ALL PANELS ARE LABELED ?C?, CORRECT ACCORDINGLY.
 7. THE NOTES CALL FOR A 100 AMP HOUSE PANEL AND THE
 PLANS SHOW A 150 AMP PANEL WITH A CONNECTED LOAD OF 150
 AMP. CORRECT ACCORDINGLY.
 8. PROVIDE LOAD CALCS AS REQUIRED BY NEC.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-07-23 Cont ID  
Sent By D Hayes Date 2015-07-23 Time 17:30 Rev Time 0.00
Received By albarran Date 2015-07-23 Time 16:28 Sent To  
Notes
2015-08-20 12:53:28SHILL'S DESK
2015-07-23 17:20:55PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 1. ROMEX, AS MENTIONED IN YOUR NOTES IS INTENDED AS A
 CABLE TYPE, ROMEX IS A BRAND NAME AND NOT A TYPE OF
 LISTED CABLE; USE OF NM, NMC OR NMS ETC.
 2. YOU SHALL PROVIDE SMOKE DETECTORS AS PER FBC-R 314.
 3. DISCONNECTS FOR AHU SHALL BE MADE ACCESSIBLE.
 4. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMPHOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB.
 5. REAR STAIRS SHALL HAVE THE REQUIRED ILLUMINATION AND
 BE SWITCHED FROM BOTH THE TOP AND BOTTOM OF STAIRS.
 6. PROVIDE A HOUSE METER & PANEL FOR COMMON LOADS SUCH
 AS HOUSE LIGHTING (CORRIDORS AND STAIRS, EMERGENCY
 LIGHTING AND SERVICE OUTLETS FOR CONDENSING UNITS.)
 7. CORRECT RISER DIAGRAM TO CONFIRM MAIN SERVICE
 DISCONNECTS ARE GROUPED TOGETHER AND NEXT TO THE
 ELECTRIC SERVICE METERS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-10-28 Cont ID  
Sent By pleduc Date 2015-10-28 Time   Rev Time 0.00
Received By pleduc Date 2015-10-28 Time 09:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-06-30 Cont ID  
Sent By pleduc Date 2015-06-30 Time   Rev Time 0.00
Received By pleduc Date 2015-06-30 Time 14:56 Sent To  
Notes
2015-06-30 15:52:51THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. PROVIDE STAIR AND RAILING DETAIL FOR BOTH STAIRS.
 EXISTING STAIRS SHALL COMPLY WITH NFPA 101, CHAPTER 31,
 CHAPTER 7, 7.2.2.2.1.1 (2).
  
 2. THERE APPEARS TO BE CLOSETS UNDER THE LANDING OF THE
 EXIT STAIR.
  
 7.2.2.5.3 USABLE SPACE
  
 ENCLOSED, USABLE SPACE SHALL BE PERMITTED UNDER STAIRS,
 PROVIDED THAT ALL OF THE FOLLOWING CRITIERIA ARE MET:
  
 (1) THE SPACE SHALL BE SEPARATED FROM THE ENCLOSURE BY
 THE SAME FIRE RESISTANCE AS THE EXIT ENCLOSURE.
  
 (2) ENTRANCE TO THE ENCLOSED, USABLE SPACE SHALL NOT BE
 FROM WITHIN THE STAIR ENCLOSURE.
  
 (3) THE SPACE IS NOT USED FOR STORAGE OF FLAMMABLE, OR
 OTHERWISE HAZARDOUS MATERIALS.
  
 3. FOR THE DOORS WITHIN THE EXIT STAIRWAY AND EXIT PATH
 (2ND FL) PROVIDE A DOOR SCHEDULE INCLUDING HARDWARE
 MEETING THE REQUIREMENTSOF NFPA 31, 31.2.2.1.2
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2015-10-07 Cont ID  
Sent By fmittner Date 2015-10-07 Time 08:46 Rev Time 0.00
Received By fmittner Date 2015-10-07 Time 08:46 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2015-07-21 Cont ID  
Sent By fmittner Date 2015-07-21 Time 16:32 Rev Time 0.00
Received By fmittner Date 2015-07-21 Time 16:32 Sent To  
Notes
2015-07-21 16:33:10NEED INFORMATION IF ANY OPENING CHANGES ARE OCCURING ON
 WINDOWS. PLANS INDICATE WINDOWS WILL BE PERMITTED
 SEPERATELY BUT FRAMING WILL BE COMPLETED UNDER THIS
 PERMIT. NEEDS BETTER COORDINATION. QUESTIONS CONTACT
 FRIEDERIKE MITTNER AT 8221457.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-02-19 Cont ID  
Sent By albarran Date 2016-02-19 Time 10:21 Rev Time 0.00
Received By albarran Date 2016-02-12 Time 09:54 Sent To  
Notes
2016-02-19 10:22:272/19/16 PASSED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 OUT FRONT TO PICK UP PERMIT. SENT DIRECTLY TO SP. MA
2016-02-16 09:55:12RESUB OF REVISION ROUTED TO MALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-11-17 Cont ID  
Sent By albarran Date 2015-11-17 Time 21:15 Rev Time 0.00
Received By albarran Date 2015-10-05 Time 12:39 Sent To  
Notes
2015-11-17 21:16:1511/17/15 FAILED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT TO SHILL'S DESK. MA
2015-10-05 12:39:37C37

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-27 Cont ID  
Sent By shill Date 2015-08-27 Time 07:39 Rev Time  
Received By shill Date 2015-06-26 Time   Sent To  
Notes
2015-06-29 10:02:14SENT TO C38.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-10-21 Cont ID  
Sent By ccole Date 2015-10-21 Time 10:06 Rev Time 0.00
Received By ccole Date 2015-10-21 Time 10:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-07-09 Cont ID  
Sent By C Cole Date 2015-07-09 Time 10:34 Rev Time 0.00
Received By ccole Date 2015-07-09 Time 10:33 Sent To  
Notes
2015-07-09 10:40:571ST REVIEW: FBC 2010 MECHANICAL
 7/9/15
  
 1) PROVIDE DRYER EXHAUST PLANS FOR THE LAUNDRY
 APPLIANCES ON THE PORCH AND IN THE APT. CLOSETS. SHOW
 THE TYPE AND SIZE OF EXHAUST DUCTS, DUCT RUN AND TOTAL
 LENGTH MEASUREMENTS, AND TERMINATION LOCATIONS- SEE
 SECTION 504 FBC-10 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-10-21 Cont ID  
Sent By tklarge Date 2015-10-21 Time 03:00 Rev Time 0.00
Received By tklarge Date 2015-10-21 Time 02:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-07-22 Cont ID  
Sent By TKL Date 2015-07-22 Time 05:06 Rev Time 0.00
Received By tklarge Date 2015-07-22 Time 04:46 Sent To  
Notes
2015-07-22 04:32:441) THE PLANS SHOW THE WASHER/DRYERS ON A PORCH. IS THIS
 PORCH OPEN TO THE ELEMENTS? IF SO, SUBMIT APPLIANCE
 SPECIFICATIONS/INSTALLATION MANUAL THAT SHOWS THAT THEY
 CAN BE INSTALLED IN THIS TYPE OF ENVIRONMENT. WPB
 AMEND. TO FBC SEC. 107.2.1.
 2) SUBMIT A SANITARY AND WATER RISER FOR THE ADDITION
 OF THE WASHING MACHINES.WPB AMEND. TO FBC SEC.
 107.3.5.1.3.
 3) THIS STRUCTURE DOES NOT FALL UNDER THE RESIDENTIAL
 BUILDING CODE SO THE WASHING MACINE STANDPIPE SHALL
 CONNECT TO A 3" STACK PER THE 2010 FBC-PLUMBING,
 SEC.406.3.
 4) SUBMIT MANUFACTURER SPECIFICATIONS FOR THE TANKLESS
 WATER HEATERS TO BE INSTALLED.THEY ARE ALSO SHOWN AS
 BEING LOCATED ON THE PORCH. IF THE PORCH IS OPEN TO THE
 ELEMENTS, SUBMIT DOCUMENTATION FROM THE MANUFACTURER
 THAT THE UNIT CAN BE INSTALLED EXPOSED TO THE ELEMENTS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2015-10-07 Cont ID  
Sent By fmittner Date 2015-10-07 Time 08:46 Rev Time 0.00
Received By fmittner Date 2015-10-07 Time 08:46 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-07-21 Cont ID  
Sent By FMittner Date 2015-07-21 Time 16:33 Rev Time 0.00
Received By fmittner Date 2015-07-21 Time 16:33 Sent To  
Notes
***NONE***