Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-07-21 Cont ID  
Sent By jwitmer Date 2015-07-21 Time 14:32 Rev Time 0.00
Received By jwitmer Date 2015-07-21 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-07-07 Cont ID  
Sent By jwitmer Date 2015-07-07 Time 14:59 Rev Time 0.00
Received By jwitmer Date 2015-07-07 Time   Sent To  
Notes
2015-07-07 14:59:45BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15061246
 ADD: 1100 W. TECHNOLOGY PLACE
 CONT: MGM EQUIPMENT
 TEL: (954)963-3995
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JULY 07/2015
 ACTION: DENIED
  
 1) DOCUMENTS SUBMITTED, SUPPORT STUCTURE FOR MECHANICAL
 EQUIPMENT FROM MWS ENGINEERING NOTE # 20 PROVIDES THE
 WIND DESIGN ;
 155 MPH VULT PLEASE CORRECT TO 170 VULT
 BUILDING RISK CATEGORY I PLEASE CORRECT TO: BUILD. RISK
 CATEGORY II
 EXPOSURE D PLEASE CORRECT TO EXPOSURE C
 ROOFTOP STRUCTURE. COMPLY WITH 1609.8 ROOFTOP
 STRUCTURES AND EQUIPMENT.
  
 2) THE SAME ROOF STAND PLEASE BE ADVISED TO TAKE YOUR
 VERTICAL MEASUREMENT FOR COMPLIANCE WITH 2010 FBC-B
 TABLE 1509.7 CLEARANCE BELOW RAISED ROOF MOUNTED
 MECHANICAL EQUIPMENT, THE VERTICAL MEASUREMENT IS TAKEN
 FROM THE LOWEST (BOTTOM) OF THE HORIZONTAL FRAMING
 MEMBER. SEE TABLE MINIMUM CLEAR REQUIRED HEIGHT TO THE
 BOTTOM OF THE LOWEST HORIZONTAL FRAMING MEMBER IS 30
 INCHES.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-07-21 Cont ID  
Sent By jwitmer Date 2015-07-21 Time 14:32 Rev Time 0.00
Received By jwitmer Date 2015-07-16 Time 16:45 Sent To  
Notes
2015-07-16 16:45:40ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date 2015-06-26 Time   Sent To  
Notes
2015-06-26 12:38:02MECH
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-07-01 Cont ID  
Sent By hmoser Date 2015-07-01 Time 15:07 Rev Time 0.00
Received By hmoser Date 2015-07-01 Time 13:44 Sent To B
Notes
***NONE***