Plan Review Details - Permit 15061245
Plan Review Stops For Permit 15061245
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-07-07 Cont ID  
Sent By albarran Date 2015-07-07 Time 17:02 Rev Time 0.00
Received By albarran Date 2015-07-07 Time 16:40 Sent To P
Notes
2015-07-07 17:22:40NEC 680.62(A)(1) ADDRESSES LISTED UNITS, AS I WAS
 UNABLE TO FIND A "UL" LISTING ON ANY OF THE COMPONENTS
 OR THE UNIT AS A WHOLE. THEREFORE THE PROPOSED OUTLET
 SHALL BE GFCI PROTECTED. ALL METAL COMPONENTS OF THIS
 SYSTEM OR WITHIN 5' OF THE WATER'S EDGE SHALL BE
 CONNECTED TO THE EQUIPMENT GROUNDING CONDUCTOR AS
 DESCRIBED IN 680.62(D). SEE NEC 680 PART VI FOR
 ADDITIONAL REQUIREMENTS.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-09 Cont ID  
Sent By ndaniels Date 2015-07-09 Time 16:25 Rev Time 0.00
Received By ndaniels Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By tklarge Date 2015-07-09 Time 06:30 Sent To  
Notes
***NONE***