| Plan Review Stops For Permit 15061210 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2016-08-25 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2016-08-25 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2016-08-25 |
Time |
11:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2015-11-06 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2015-11-06 |
Time |
15:15 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2015-11-06 |
Time |
15:15 |
Sent To |
|
|
| Notes |
| 2015-11-06 15:38:11 | CHRISTOPHER S. THROOP, C.B.O. | | | BLDG. PLANS EXAMINER ? PX3169 | | | (561) 805-6718 | | | [email protected] | | | | | | PLEASE PROVIDE THE FOLLOWING FASTENER SCHEDULES: | | | BASE PLATE TO FOUNDATION | | | TOP PLATE TO TRUSS | | | ROOF SHEATHING | | | | | | PLEASE PROVIDE EXTERIOR WALL DETAIL (STRUCTURAL PLAN | | | REQUIRES 5/8" CDX, ENGINEERED PLANS REQUIRE 1/2" CDX) | | | | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN | | | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE | | | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE | | | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT | | | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | | DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND | | | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM | | | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, | | | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE | | | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, | | | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE | | | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS | | | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | | INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | | SECTION 107.3.5). | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2015-08-19 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-08-19 |
Time |
10:13 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-08-19 |
Time |
08:29 |
Sent To |
|
|
| Notes |
| 2015-08-19 08:36:39 | 1ST REVIEW: FBC 2010 | | | | | | CURRENTLY UNDER REVIEW: | | | | | | THE PLANS LACK DETAIL AND CLARITY: | | | | | | FBC 107.2.1 CONSTRUCTION DOCUMENTS SHALL BE OF | | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT | | | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | | DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND | | | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM | | | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, | | | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE | | | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, | | | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE | | | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS | | | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | | INFORMATION. A COMPLETE REVIEW CANNOT BE PERFORMED. | | | | | | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE ROOFING, WINDOW, AND DOOR | | | SUBMITTALS. | | | | | | R401.4 SOIL TESTS - PROVIDE A SOILS ANALYSIS | | | | | | FBC 107 & FBCR 601 - WALL CONSTRUCTION; PROVIDE DETAILS | | | TO CLARIFY OR SPECIFY THE FOLLOWING: HEADERS, | | | TRIMMER/CRIPPLE STUDS, A WALL SHEATHING NAILING | | | SCHEDULE. PROVIDE A DETAIL TO TERMINATE THE STUCCO AT | | | THE FOUNDATION TO DEMONSTRATE COMPLIANCE WITH FBCR704, | | | TERMITE INSPECTION. PROVIDE WINDOW AND DOOR | | | INSTALLATION DETAILS TO MEET ANCHORAGE OF FBCR 612.10 . | | | DESIGN PRESSURES FOR WINDOW #3 APPEAR LOW AS THEY ARE | | | LOCATED IN ZONE 5. R703.6.3 TWO LAYERS OF WATER | | | RESISTANT BARRIER ARE REQUIRED. | | | | | | FBC 107 & FBCR 801 - ROOF CONSTRUCTION - PROVIDE | | | DETAILS TO CLARIFY OR SPECIFY THE FOLLOWING: ROOF | | | VENTILATION PER R806, ROOF DRAINAGE, NOTE: THE ROOF | | | FRAMING DETAIL AND ROOF FRAMING PLAN ARE IN CONFLICT AS | | | TO THE DIRECTION OF RUN OF THE MAIN ROOF TRUSSES. YOU | | | SHOULD PROVIDE THE ROOF TRUSS ENGINEERING NOW AND THE | | | DESIGNER SHOULD EVALUATE THE ROOF FRAMING PLAN VS. THE | | | TRUSS DESSIGN. SPECIFY THE ROOF SHEATHING NAIL LENGTH | | | AND SHANK TYPE. FURTHER SPECIFT THE PARAPET | | | CONSTRUCTION. | | | | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2016-07-11 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-07-11 |
Time |
17:49 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-07-11 |
Time |
17:49 |
Sent To |
|
|
| Notes |
| 2016-07-11 17:50:11 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | PASSED WITH THE FOLLOWING PROVISO | | | | | | - NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE | | | PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE | | | EQUIPMENT, SWITCHBOARDS, PANELBOARDS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2015-11-19 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2015-11-19 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2015-11-19 |
Time |
10:13 |
Sent To |
|
|
| Notes |
| 2015-11-19 10:33:50 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6700 | | | [email protected] | | | | | | | | | | | | FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 | | | FEET OF EACH SLEEPING ROOM. | | | NEC 210.12B - OUTLETS TO BE AFCI PROTECTED. | | | NEC 220.82 A AMPACITY OF 100 AMPS OR GREATER/ COULD | | | ONLY FILL BREAKER 80 % OF LOAD | | | PROVIDE GROUNTING ELECTRODE IN ATTACHED BUILDING PER | | | NEC 250 | | | FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE | | | SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE | | | LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON | | | FLOOR PLAN. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2015-08-19 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-08-19 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-08-19 |
Time |
10:14 |
Sent To |
|
|
| Notes |
| 2015-08-19 10:29:02 | 1ST REVIEW: FBC 2010 | | | | | | REVISE PLAN TO INDICATE COMPLIANCE WITH THE FOLLOWING: | | | | | | NEC 210.52(A)(1)&(2) OUTLET SPACING, IT APPEARS SOME | | | POINTS ALONG THE WALL EXCEED 6? FROM AN OUTLET | | | | | | NEC 210.52 (B) (3) - KITCHEN COUNTER TOP RECEPTACLES | | | SHALL BE SUPPLIED BY NO FEWER THAN TWO SMALL APPLIANCE | | | BRANCH CIRCUITS. | | | | | | NEC 210.63 - PROVIDE A GFI SERVICE OUTLET FOR WITHIN | | | 25? OF MECHANICAL EQUIPMENT | | | | | | NEC 406.11- PROVIDE TAMPER RESISTANT RECEPTACLES. | | | | | | FBC 1006.1.1 PER FBC-R, T-E3403 | | | ILLUMINATION OF MEANS OF EGRESS SHALL BE PROVIDED IN | | | ACCORDANCE WITH THIS SECTION FOR EVERY BUILDING AND | | | STRUCTURE, BEDROOM EXIT.. | | | | | | ADDITIONALLY, NO CIRCUIT OR DICCONNECT IS SHOWN FOR THE | | | A/C EQUIPMET OR THE WATER HEATER, THE LOAD CALCULATION | | | DOES NOT ACCOUNT FOR THESE LOADS. | | | | | | INDICATE THE LOCATION OF THE SERVICE. IS THE 60AMP | | | PANEL FOR THE ACCESSORY STRUCTURE FED FROM THE SERVICE | | | TO THE HOUSE OR IS THERE TO BE A SEPARATE SERVICE. IS | | | THIS AN ACCESSORY BUILDING OR A SEPARATE DWELLING UNIT? | | | PROVIDE AN ACCURATE SERVICE RISER DIAGRAM,. ACCURATE | | | LOAD CALCULATIONS, AND PANEL SCHEDULES. | | | | | | NOTE, A COMPLETE REVIEW CANNOT BE PERFORMED DUE TO THE | | | LACK OF INFORMATION PROVIDED. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
4 |
Status |
P |
Date |
2016-08-31 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2016-08-31 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2016-08-31 |
Time |
14:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
3 |
Status |
F |
Date |
2016-07-08 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2016-07-08 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2016-07-08 |
Time |
14:57 |
Sent To |
|
|
| Notes |
| 2016-07-08 14:58:43 | SOUTH FACING WINDOW DOES NOT MATCH PROPORATIONS/STYLE | | | OF WHAT HPB REVIEWED. SHALL BE VERTICALLY ORIENTED WITH | | | PENT ROOF. QUESTIONS PLEASE CONTACT FRIEDERIKE MITTNER | | | AT 822-1457. |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
P |
Date |
2015-11-17 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-11-09 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2015-11-17 |
Time |
11:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2015-07-21 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2015-07-21 |
Time |
09:42 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2015-07-21 |
Time |
09:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2016-10-31 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2016-10-31 |
Time |
08:55 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2016-10-27 |
Time |
13:22 |
Sent To |
|
|
| Notes |
| 2016-10-28 13:23:12 | RESUB ROUTED TO CTHROOP |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2016-10-28 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2016-10-28 |
Time |
13:22 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2016-10-14 |
Time |
07:24 |
Sent To |
|
|
| Notes |
| 2016-10-17 07:26:06 | JVALIDO'S DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2016-08-25 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2016-08-25 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2016-06-16 |
Time |
12:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2015-11-19 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2015-11-19 |
Time |
10:50 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2015-09-10 |
Time |
12:40 |
Sent To |
|
|
| Notes |
| 2015-09-10 12:40:55 | RESUB ROUTED TO SKENNEDY |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-08-19 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-08-19 |
Time |
10:29 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-06-25 |
Time |
16:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2016-10-31 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2016-10-31 |
Time |
08:55 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2016-10-31 |
Time |
08:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2015-08-19 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-08-19 |
Time |
08:05 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-08-19 |
Time |
08:05 |
Sent To |
|
|
| Notes |
| 2015-08-19 08:07:08 | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | | 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND | | | TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED | | | WITH A COPY OF RECEIPT AS APPLICABLE. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2016-10-17 |
|
|
Cont ID |
|
| Sent By |
jvalido |
Date |
2016-10-17 |
Time |
17:54 |
Rev Time |
0.00 |
| Received By |
jvalido |
Date |
2016-10-17 |
Time |
17:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2016-08-18 |
|
|
Cont ID |
|
| Sent By |
jvalido |
Date |
2016-08-18 |
Time |
19:25 |
Rev Time |
0.00 |
| Received By |
jvalido |
Date |
2016-08-18 |
Time |
18:57 |
Sent To |
|
|
| Notes |
| 2016-08-18 19:17:44 | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA | | | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION | | | | | | 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS | | | | | | R403.6.1 - HEATING AND COOLING EQUIPMENT SHALL BE SIZED | | | IN ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT | | | LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR | | | OTHER APPROVED HEATING AND COOLING CALCULATION | | | METHODOLOGIES, BASED ON BUILDING LOADS FOR THE | | | DIRECTIONAL ORIENTATION OF THE BUILDING. THE | | | MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR | | | UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH | | | THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN | | | CONDITIONS DESCRIBED IN SECTION R302.1. THIS CODE DOES | | | NOT ALLOW DESIGNER SAFETY FACTORS, PROVISIONS FOR | | | FUTURE EXPANSION OR OTHER FACTORS WHICH AFFECT | | | EQUIPMENT SIZING. SYSTEM SIZING CALCULATIONS SHALL NOT | | | INCLUDE LOADS CREATED BY LOCAL INTERMITTENT MECHANICAL | | | VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM | | | EXHAUST SYSTEMS. | | | | | | (1) PROVIDE EQUIPMENT SCHEDULE AS PER R403.6.1. | | | (2) PROVIDE EQUIPMENT INFORMATION ON EXHAUST FAN IN | | | BATHROOM. | | | (3) PROVIDE TIE DOWN DETAIL ON PLANS OR MANUFACTURER | | | DATA INFORMATION FOR THE SPECIFIC TIE DOWN DEVICES | | | BEING USED. | | | | | | FLORIDA ENERGY CODE FBC 2014 | | | | | | (4) PROVIDE AHRI | | | | | | JORGE VALIDO | | | WPB MECHANICAL INSPECTOR/PLANS EXAMINER | | | [email protected] | | | 561-805-6716 | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2015-11-09 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-11-09 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-11-09 |
Time |
10:33 |
Sent To |
HIST |
|
| Notes |
| 2015-11-09 10:37:37 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15061210 | | | 11/9/15 | | | | | | 1) SHEET 3: PLEASE SHOW THE LOCATION OF THE AC | | | CONDENSER ON THE PLANS, AND PROVIDE STRUCTURAL DETAILS | | | FOR THE PAD AND TIE DOWN OF THE UNIT- SEE SECTION | | | M1307.2.1 FBC-10 RESIDENTIAL. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2015-08-19 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-08-19 |
Time |
10:08 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-08-19 |
Time |
10:08 |
Sent To |
|
|
| Notes |
| 2015-08-19 10:13:44 | 1ST REVIEW: FBC 2010 | | | | | | PROVIDE PRODUCT INFORMATION FOR THE MECHANICAL | | | EQUIPMENT TO INCLUDE AN AHRI & INSTALLATION DETAILS. | | | DEMONSTRATE ANY ELECTRICAL, WALL FRAMING, AND OUTDOOR | | | UNIT SUPPORT REQUIREMENTS. | | | | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2016-07-22 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-07-22 |
Time |
17:49 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-07-22 |
Time |
17:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2015-09-11 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-09-11 |
Time |
05:23 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-09-11 |
Time |
04:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2015-07-16 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-07-16 |
Time |
02:40 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-07-16 |
Time |
02:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2016-08-25 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2016-08-25 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2016-08-25 |
Time |
11:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2015-11-06 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2015-11-06 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2015-11-06 |
Time |
15:38 |
Sent To |
E |
|
| Notes |
| 2015-11-06 15:41:19 | CHRISTOPHER S. THROOP, C.B.O. | | | BLDG. PLANS EXAMINER ? PX3169 | | | (561) 805-6718 | | | [email protected] | | | | | | PLEASE PROVIDE ROOF SYSTEM FASTENER SCHEDULE PER NOTE 7 | | | OF NOA 14-0224.03 | | | | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN | | | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE | | | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE | | | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT | | | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | | DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND | | | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM | | | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, | | | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE | | | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, | | | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE | | | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS | | | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | | INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | | SECTION 107.3.5). | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2015-08-19 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-08-19 |
Time |
08:07 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-08-19 |
Time |
08:07 |
Sent To |
|
|
| Notes |
| 2015-08-19 08:25:44 | 1ST REVIEW: FBC 2010 | | | | | | FBC 107 - FURTHER SPECIFY THE ROOFING SYSTEM TO BE USED | | | FOR THE FLAT ROOF . DEMONSTRATE COMPLIANCE WITH THE | | | REQUIREMENTS OF FBCR 905.9 EG: PROVIDE TIN TAG SPACING | | | FOR 30# UNDERLAYMENT INCLUDING ENHANCED FASTENING FOR | | | ZONES 2 & 3, NUMBER OF PLYS AND MATERIAL AND | | | APPLICATION. SHOW THE ROOF DRAINAGE METHOD. | | | ALTERNATIVELY, PROVIDE ROOF COVERING PRODUCT APPROVALS | | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD, INCLUDE THE SYSTEM FOR TNE TYPE "S" TILE ROOF | | | OVERHANG.. | | | | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2016-07-08 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2016-07-08 |
Time |
14:58 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2016-07-08 |
Time |
14:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2015-11-17 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2015-11-17 |
Time |
11:48 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2015-11-17 |
Time |
11:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2015-07-21 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2015-07-21 |
Time |
09:42 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2015-07-21 |
Time |
09:42 |
Sent To |
|
|
| Notes |
|
|