| Plan Review Stops For Permit 15061209 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2015-08-13 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-08-13 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-08-13 |
Time |
13:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2015-08-01 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-08-01 |
Time |
15:36 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-08-01 |
Time |
15:36 |
Sent To |
|
|
| Notes |
| 2015-08-01 15:37:49 | 1ST REVIEW: FBC 2010 | | | | | | FBC 107 PROVIDE SITE PLAN/SURVEY WITH FLOOD | | | INFORMATION. | | | | | | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY | | | FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING, | | | WINDOW, AND DOOR SUBMITTALS. | | | | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2015-08-13 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-08-13 |
Time |
09:40 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-08-13 |
Time |
09:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2015-07-16 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-07-16 |
Time |
17:58 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-07-16 |
Time |
15:47 |
Sent To |
|
|
| Notes |
| 2015-07-16 17:59:38 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE | | | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. | | | | | | 1. GENERAL ELECTRICAL NOTES CORRECTIONS REQUIRED: | | | A) #7, THE INTENT OF THE WORD ?ROMEX? AS USED IN THIS | | | NOTE IS TO IDENTIFY A TYPE OF CABLE. ROMEX IS A BRAND | | | NAME AND NOT A TYPE OF CABLE, REFER TO CABLE TYPES | | | ?NM?, ?NMC? OR ?NMS?. | | | B) #23, TO REFER TO FBC-R314 & 315. R-313 REFERS TO | | | FIRE SPRINKLERS. | | | 2. INCLUDE A NOTE ADDRESSING THE NEC 314.27 REQUIREMENT | | | FOR CEILING OUTLETS FOR LUMINAIRES BEING LISTED TO | | | SUPPORT 50LBS. | | | 3. THE FLOOR PLAN REFLECTS TWO PANELS AND A POOL PANEL. | | | ONE ADJACENT TO THE METER SOCKET, THE OTHER IN THE | | | KITCHEN AND THE POOL PANEL OUTSIDE OF THE GARAGE. YET | | | YOUR ELECTRICAL RISER DIAGRAM REFLECTS ONLY A NEW PANEL | | | AND THE EXISTING POOL PANEL. CLARIFY THIS SO THEY ALL | | | MATCH. | | | 4. INCLUDE SITE SPECIFIC ELECTRICAL LOAD CALCS AS | | | INDICATED IN NEC 220.16 & NEC 220.82. | | | 5. THE NEW AHU AND WH ARE MISSING THE REQUIRED | | | DISCONNECTS. | | | 6. NEC 210.52(E) REQUIRES THAT THERE BE A GFCI OUTLET | | | IN THE FRONT OF THE RESIDENCE. IF ONE IS ALREADY THERE, | | | INDICATE IT ON THE DRAWING AS EXISTING OTHERWISE | | | INCLUDE IN THE NEW DRAWING. | | | 7. THE LOCATION OF THE EXISTING ELECTRIC METER AND POOL | | | PANEL LEAD ME TO BELIEVE THAT THERE MAY BE A CODE/LIFE | | | SAFETY VIOLATION WITH THE SERVICE DROP ENCROACHING THE | | | MINIMUM SEPARATION REQUIREMENTS OF THE POOL. PROVIDE A | | | SITE PLAN SHOWING THE LOCATION OF THE UTILITY POLE, | | | SERVICE DROP TO METER WITH RELATION TO THE POOL. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2015-08-13 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-08-13 |
Time |
13:26 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-08-13 |
Time |
09:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-08-01 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-08-01 |
Time |
15:37 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-06-25 |
Time |
16:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2015-08-13 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-08-13 |
Time |
09:38 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-08-13 |
Time |
09:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2015-08-01 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-08-01 |
Time |
15:17 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-08-01 |
Time |
15:17 |
Sent To |
|
|
| Notes |
| 2015-08-01 15:18:58 | 1ST REVIEW: FBC 2010 | | | | | | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | | 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND | | | TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED | | | WITH A COPY OF RECEIPT AS APPLICABLE. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2015-08-01 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-08-01 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-08-01 |
Time |
15:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2015-08-13 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-08-13 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-08-13 |
Time |
09:40 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2015-07-21 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-07-21 |
Time |
11:22 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-07-21 |
Time |
11:22 |
Sent To |
|
|
| Notes |
| 2015-07-21 11:25:23 | 1ST REVIEW: FBC 2010 | | | | | | FBC 107.3.5.3; PROVIDE PLUMBING RISER DIAGRAM. | | | | | | FBCR-P 3108.1; LAUNDRY & WASHING MACHINE MUST TIE IN | | | DOOWNSTREAM OF BATHGROUP. | | | | | | CLARIFY NOTE ON SHEET A-5 "REMOVE/CAP UNUSED | | | WASTELINES." ARE YOU RUNNING NEW WASTELINES FOR | | | EXISTING BATHROOMS? | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | [email protected] | | | 561 805 6711 |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2015-08-13 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-08-13 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-08-13 |
Time |
13:25 |
Sent To |
|
|
| Notes |
| 2015-08-13 13:26:53 | THE ROOFING SUBMITTAL IS DEFERRED. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2015-08-01 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-08-01 |
Time |
15:34 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-08-01 |
Time |
15:34 |
Sent To |
|
|
| Notes |
| 2015-08-01 15:35:58 | 1ST REVIEW: FBC 2010 | | | | | | PROVIDE ROOF COVERING PRODUCT APPROVAL, SEE BUILDING | | | COMMENTS. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2015-08-13 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2015-08-13 |
Time |
10:42 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2015-08-13 |
Time |
10:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2015-06-30 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2015-06-30 |
Time |
16:02 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2015-06-30 |
Time |
16:02 |
Sent To |
|
|
| Notes |
| 2015-06-30 16:03:25 | 6/30/15 ZONING FAILED | | | | | | 1. SUBMIT TWO COPIES OF AN UP TO DATE SURVEY |
|
|