Plan Review Details - Permit 15061209
Plan Review Stops For Permit 15061209
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-08-13 Cont ID  
Sent By skennedy Date 2015-08-13 Time 13:25 Rev Time 0.00
Received By skennedy Date 2015-08-13 Time 13:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-01 Cont ID  
Sent By skennedy Date 2015-08-01 Time 15:36 Rev Time 0.00
Received By skennedy Date 2015-08-01 Time 15:36 Sent To  
Notes
2015-08-01 15:37:491ST REVIEW: FBC 2010
  
 FBC 107 PROVIDE SITE PLAN/SURVEY WITH FLOOD
 INFORMATION.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING,
 WINDOW, AND DOOR SUBMITTALS.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-08-13 Cont ID  
Sent By skennedy Date 2015-08-13 Time 09:40 Rev Time 0.00
Received By skennedy Date 2015-08-13 Time 09:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-07-16 Cont ID  
Sent By albarran Date 2015-07-16 Time 17:58 Rev Time 0.00
Received By albarran Date 2015-07-16 Time 15:47 Sent To  
Notes
2015-07-16 17:59:38PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 1. GENERAL ELECTRICAL NOTES CORRECTIONS REQUIRED:
 A) #7, THE INTENT OF THE WORD ?ROMEX? AS USED IN THIS
 NOTE IS TO IDENTIFY A TYPE OF CABLE. ROMEX IS A BRAND
 NAME AND NOT A TYPE OF CABLE, REFER TO CABLE TYPES
 ?NM?, ?NMC? OR ?NMS?.
 B) #23, TO REFER TO FBC-R314 & 315. R-313 REFERS TO
 FIRE SPRINKLERS.
 2. INCLUDE A NOTE ADDRESSING THE NEC 314.27 REQUIREMENT
 FOR CEILING OUTLETS FOR LUMINAIRES BEING LISTED TO
 SUPPORT 50LBS.
 3. THE FLOOR PLAN REFLECTS TWO PANELS AND A POOL PANEL.
 ONE ADJACENT TO THE METER SOCKET, THE OTHER IN THE
 KITCHEN AND THE POOL PANEL OUTSIDE OF THE GARAGE. YET
 YOUR ELECTRICAL RISER DIAGRAM REFLECTS ONLY A NEW PANEL
 AND THE EXISTING POOL PANEL. CLARIFY THIS SO THEY ALL
 MATCH.
 4. INCLUDE SITE SPECIFIC ELECTRICAL LOAD CALCS AS
 INDICATED IN NEC 220.16 & NEC 220.82.
 5. THE NEW AHU AND WH ARE MISSING THE REQUIRED
 DISCONNECTS.
 6. NEC 210.52(E) REQUIRES THAT THERE BE A GFCI OUTLET
 IN THE FRONT OF THE RESIDENCE. IF ONE IS ALREADY THERE,
 INDICATE IT ON THE DRAWING AS EXISTING OTHERWISE
 INCLUDE IN THE NEW DRAWING.
 7. THE LOCATION OF THE EXISTING ELECTRIC METER AND POOL
 PANEL LEAD ME TO BELIEVE THAT THERE MAY BE A CODE/LIFE
 SAFETY VIOLATION WITH THE SERVICE DROP ENCROACHING THE
 MINIMUM SEPARATION REQUIREMENTS OF THE POOL. PROVIDE A
 SITE PLAN SHOWING THE LOCATION OF THE UTILITY POLE,
 SERVICE DROP TO METER WITH RELATION TO THE POOL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-13 Cont ID  
Sent By skennedy Date 2015-08-13 Time 13:26 Rev Time 0.00
Received By skennedy Date 2015-08-13 Time 09:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-01 Cont ID  
Sent By skennedy Date 2015-08-01 Time 15:37 Rev Time 0.00
Received By skennedy Date 2015-06-25 Time 16:27 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2015-08-13 Cont ID  
Sent By skennedy Date 2015-08-13 Time 09:38 Rev Time 0.00
Received By skennedy Date 2015-08-13 Time 09:37 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-08-01 Cont ID  
Sent By skennedy Date 2015-08-01 Time 15:17 Rev Time 0.00
Received By skennedy Date 2015-08-01 Time 15:17 Sent To  
Notes
2015-08-01 15:18:581ST REVIEW: FBC 2010
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-08-01 Cont ID  
Sent By skennedy Date 2015-08-01 Time 15:19 Rev Time 0.00
Received By skennedy Date 2015-08-01 Time 15:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-08-13 Cont ID  
Sent By skennedy Date 2015-08-13 Time 09:41 Rev Time 0.00
Received By skennedy Date 2015-08-13 Time 09:40 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-07-21 Cont ID  
Sent By skennedy Date 2015-07-21 Time 11:22 Rev Time 0.00
Received By skennedy Date 2015-07-21 Time 11:22 Sent To  
Notes
2015-07-21 11:25:231ST REVIEW: FBC 2010
  
 FBC 107.3.5.3; PROVIDE PLUMBING RISER DIAGRAM.
  
 FBCR-P 3108.1; LAUNDRY & WASHING MACHINE MUST TIE IN
 DOOWNSTREAM OF BATHGROUP.
  
 CLARIFY NOTE ON SHEET A-5 "REMOVE/CAP UNUSED
 WASTELINES." ARE YOU RUNNING NEW WASTELINES FOR
 EXISTING BATHROOMS?
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 [email protected]
 561 805 6711

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2015-08-13 Cont ID  
Sent By skennedy Date 2015-08-13 Time 13:25 Rev Time 0.00
Received By skennedy Date 2015-08-13 Time 13:25 Sent To  
Notes
2015-08-13 13:26:53THE ROOFING SUBMITTAL IS DEFERRED.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2015-08-01 Cont ID  
Sent By skennedy Date 2015-08-01 Time 15:34 Rev Time 0.00
Received By skennedy Date 2015-08-01 Time 15:34 Sent To  
Notes
2015-08-01 15:35:581ST REVIEW: FBC 2010
  
 PROVIDE ROOF COVERING PRODUCT APPROVAL, SEE BUILDING
 COMMENTS.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2015-08-13 Cont ID  
Sent By sgraham Date 2015-08-13 Time 10:42 Rev Time 0.00
Received By sgraham Date 2015-08-13 Time 10:42 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2015-06-30 Cont ID  
Sent By sgraham Date 2015-06-30 Time 16:02 Rev Time 0.00
Received By sgraham Date 2015-06-30 Time 16:02 Sent To  
Notes
2015-06-30 16:03:256/30/15 ZONING FAILED
  