Plan Review Details - Permit 15061203
Plan Review Stops For Permit 15061203
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-10-29 Cont ID  
Sent By ccole Date 2015-10-29 Time 09:22 Rev Time 0.00
Received By ccole Date 2015-10-29 Time 09:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-09-24 Cont ID  
Sent By ccole Date 2015-09-24 Time 12:52 Rev Time 0.00
Received By ccole Date 2015-09-24 Time 12:52 Sent To  
Notes
2015-09-24 12:55:462ND REVIEW: FBC 2010 BUILDING
 PERMIT #15061203
 9/24/15
  
 SEVERAL COMMENTS FROM THE 1ST REVIEW OF THE PROPOSED
 SINGLE FAMILY HOME PROJECT WERE NOT ADDRESSED AND STILL
 EXIST. THOSE COMMENTS WILL BE REFERENCED AND REPRINTED
 BELOW ALONG WITH ADDITIONAL REMARKS.
 PLEASE NOTE THAT THE WCI REPONSE NARRATIVE SENT WITH
 THE REVISED PLANS ADDRESSSED ONLY COMMENTS 2 & 11.
 PLEASE PROVIDE A COMPLETE NARRATIVE RESPONSE TO THIS
 REVIEW.
  
 1) COMMENT #2: "GEOTECHNICAL EVALUATION REQUIRED FOR
 CONSTRUCTION OF THE BUILDING. SUBMIT TWO COPIES OF A
 SOIL TEST AND REPORT SIGNED AND SEALED BY A FLORIDA
 LICENSED GEOTECHNICAL ENGINEER- SECTION R401.4 FBC-10
 RESIDENTIAL." IN RESPONSE TO THIS COMMENT I RECEIVED A
 DENSITY REPORT FOR THE BUILDING PAD. PLEASE PROVIDE THE
 REQUESTED SOIL REPORT, AND ALSO CLARIFY HOW A DENSITY
 TEST CAN BE PERFORMED BEFORE A BUILDING PERMIT IS
 ISSUED AND A FOUNDATION PAD HAS BEEN DUG OUT?
 2) COMMENT #6: "S-1A: THE SPACINGS OF THE #5 VERTICAL
 REINFORCEMENT BARS (REBAR) ON THE MAIN HOUSE AND GARAGE
 EXTERIOR MASONRY WALLS ARE EXCEEDING THE ALLOWABLE
 MAXIMUMS AS DETERMINED BY TABLE R609.3.3A-1. PLEASE
 REDUCE THE SPACING PER THE TABLE REQUIREMENTS." THE
 REVISED PLANS DO NOT INDICATE ANY CORRECTIONS TO THE 8'
 SPACINGS. PLEASE NOTE THAT INTERPOLATION BETWEEN THE
 130 AND 140 TABLE CATEGORIES WILL BE NECESSARY TO
 ARRIVE AT CORRECT SPACINGS.
 3) COMMENT #9: "S-4A: DETAIL 9/S4- INDICATE THE
 SPECIES, GRADE, SIZE, AND SPACING OF WOOD STUDS FOR THE
 GARAGE/LIVING COMMON WALL. SPECIFY PRESSURE TREATED FOR
 THE BOTTOM PLATE" THE DETAIL WAS NOT REVISED.
 4) COMMENT #10: "S-4A: DETAIL 4/S4 & 5/S4- INDICATE THE
 TYPE OF WEATHER AND WATER RESISTANT FINISH TO BE
 ATTACHED TO THE WOOD FRAMED GABLE WALLS. REFER TO
 SECTION R703 AND R703.6 FOR EXTERIOR PLASTER (STUCCO),
 AND R703.6.3 FOR WATER-RESISTANT BARRIER MATERIAL.
 REVISE THE DETAIL ACCORDINGLY." ALTHOUGH THERE IS A NEW
 NOTE ADDRESSING STUCCO FINISH FOR THE GABLES ON SHEET
 3A, PLEASE PLACE THE NOTES ON THE DETAIL AS PREVIOUSLY
 REQUESTED.
 5) COMMENT #15: "PRODUCT APPROVALS AND MIAMI-DADE
 NOA'S: A) THE GARAGE DOOR PRODUCT APPROVAL FL 09174-R7
 IS OUTDATED FOR 2010- PROVIDE TWO COPIES OF FL
 09174-R9. B) ENTRY DOOR FL 8871.5-R4 IS OUTDATED FOR
 2010- PROVIDE TWO COPIES OF FL 8871.5-R6. C) THE DESIGN
 PROFESSIONAL OF RECORD SHALL CIRCLE, HIGHLIGHT, OR
 OTHERWISE MARK ALL APPLICABLE DETAILS, NOTES, DESIGN
 PRESSURES, GLASS TYPES, ANCHORING SCHEDULES ETC. ON THE
 PRODUCT APPROVALS AND NOA'S FOR THE WINDOWS, SLIDER
 DOORS, ENTRY DOORS, AND TILE ROOFING. PLEASE SUBMIT
 PRODUCT APPROVALS FOR TILE UNDERLAYMENT AND FOAM
 ADHESIVE IF APPLICABLE TO THE TILE ROOF INSTALLATION."
 IN RESPONSE TO THIS COMMENT TWOL ISSUES NOT RESOLVED:
 A) THE ROOF TILE PRODUCT APPROVAL WAS NOT MARKED TO
 INDICATE A MECHANICAL OR FOAM ADHESIVE INSTALLATION,
 AND A PRODUCT APPROVAL FOR THE ADHESIVE WAS NOT
 SUBMIITTED. B) NOA'S FOR THE PGT FIXED WINDOWS WERE NOT
 SUBMITTED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-21 Cont ID  
Sent By ccole Date 2015-08-21 Time 09:07 Rev Time 0.00
Received By ccole Date 2015-08-21 Time 09:07 Sent To  
Notes
2015-08-21 09:09:191ST REVIEW: FBC 2010 BUILDING
 PERMIT #15061203
 8/21/15
  
 1) SHEET CS1: PLEASE REVISE THE FLORIDA BUILDING CODE
 REFERENCE LISTED UNDER "CODES USED" TO INDICATE THE
 FLORIDA BUILDING CODE RESIDENTIAL- 2010. REFER TO
 SECTION R101.2.
 2) GEOTECHNICAL EVALUATION REQUIRED FOR CONSTRUCTION OF
 THE BUILDING. SUBMIT TWO COPIES OF A SOIL TEST AND
 REPORT SIGNED AND SEALED BY A FLORIDA LICENSED
 GEOTECHNICAL ENGINEER- SECTION R401.4 FBC-10
 RESIDENTIAL.
 3) PLEASE REVIEW SECTION R301 FBC-10 RESIDENTIAL AND
 PROVIDE THE WIND DESIGN CRITERIA ON THE PLAN:
 BASIC WIND SPEED PER FIGURE R301.2.(4),
 WIND SPEED CONVERSION IN ACCORDANCE WITH SECTION
 R301.2.1.3.
 EXPOSURE CATEGORY- R301.2.1.4.
 COMPONENTS AND CLADDING PRESSURES POSITIVE AND
 NEGATIVE- TABLE R301.2(2).
 HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENTS- TABLE
 R301.2(3).
 WINDLOADS- LATERAL AND UPLIFT PRESSURES- ON ROOFTOP
 STRUCTURES AND EQUIPMENT- SECTION R301.2.1.1.3
 4) S-0: SPECIFY THE PSI OF COLUMN, FILL CELL, AND BOND
 BEAM GROUT.
 5) S-1B: PLACE A NOTE INDICATING SUBTERRANEAN TERMITE
 PROTECTION (SOIL TREATMENT) WILL BE PROVIDED IN
 ACCORDANCE WITH R318 FBC-10 RESIDENTIAL.
 6) S-1B: THE SPACINGS OF THE #5 VERTICAL REINFORCEMENT
 BARS (REBAR) ON THE MAIN HOUSE AND GARAGE EXTERIOR
 MASONRY WALLS ARE EXCEEDING THE ALLOWABLE MAXIMUMS AS
 DETERMINED BY TABLE R609.3.3A-1. PLEASE REDUCE THE
 SPACING PER THE TABLE REQUIREMENTS.
 7) S-1B: PROVIDE STRUCTURAL DETAILS FOR THE ACCU PAD.
 8) S-4B: DETAIL 5/S4- SPECIFY PRESSURE TREATED FOR THE
 2X4 SLEEPER- R317.1
 9) S-4B: DETAIL 9/S4- INDICATE THE SPECIES, GRADE,
 SIZE, AND SPACING OF WOOD STUDS FOR THE GARAGE/LIVING
 COMMON WALL. SPECIFY PRESSURE TREATED FOR THE BOTTOM
 PLATE.
 10) S-4B: DETAIL 4/S4 & 5/S4- INDICATE THE TYPE OF
 WEATHER AND WATER RESISTANT FINISH TO BE ATTACHED TO
 THE WOOD FRAMED GABLE WALLS. REFER TO SECTION R703 AND
 R703.6 FOR EXTERIOR PLASTER (STUCCO), AND R703.6.3 FOR
 WATER-RESISTANT BARRIER MATERIAL. REVISE THE DETAIL
 ACCORDINGLY.
 11) REFER TO SECTION R301.1 AND ADDRESS ITEM #6 AS IT
 RELATES TO THE ROOF OVERHANG AND THE OPENING IN THE
 SUMMER KITCHEN WALL. INDICATE SEPARATION DISTANCES TO
 THE ADJACENT BUILDING.
 12) 2B: PLACE A NOTE IN THE PLAN INDICATING WHICH
 BATHROOM DOOR IS MEETING COMPLIANCE FOR THE REQUIRED
 29-INCH CLEAR OPENING PER SECTION R320.1.1.
 13) 9B: DETAIL 3- INDICATE THE TYPE, SIZE, AND SPACINGS
 OF THE 2X12 ANCHORS.
 14) 10B: DETAIL 3- REFER TO SECTION R401.3 AND SHOW THE
 MINIMUM GRADE FALL AWAY FROM THE FOUNDATION.
 15) PRODUCT APPROVALS AND MIAMI-DADE NOA'S: A) THE
 GARAGE DOOR PRODUCT APPROVAL FL 09174-R7 IS OUTDATED
 FOR 2010- PROVIDE TWO COPIES OF FL 09174-R9. B) ENTRY
 DOOR FL 8871.5-R4 IS OUTDATED FOR 2010- PROVIDE TWO
 COPIES OF FL 8871.5-R6. C) THE DESIGN PROFESSIONAL OF
 RECORD SHALL CIRCLE, HIGHLIGHT, OR OTHERWISE MARK ALL
 APPLICABLE DETAILS, NOTES, DESIGN PRESSURES, GLASS
 TYPES, ANCHORING SCHEDULES ETC. ON THE PRODUCT
 APPROVALS AND NOA'S FOR THE WINDOWS, SLIDER DOORS,
 ENTRY DOORS, AND TILE ROOFING. PLEASE SUBMIT PRODUCT
 APPROVALS FOR TILE UNDERLAYMENT AND FOAM ADHESIVE IF
 APPLICABLE TO THE TILE ROOF INSTALLATION.
 16) ENERGY FORM 405-10: A) SEE PAGE 2- DATA FOR GABLE
 ROOF AREA NOT INDICATED. B) PAGE 3- WOOD WINDOWS ARE
 LISTED HOWEVER THE NOA'S INDICATE ALUMINUM. D) COMPLETE
 THE CODE COMPLIANCE CHECKLIST ON PAGE #5.
  
 CHRISTOPHER L. COLE
 STANDARD PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-10-05 Cont ID  
Sent By albarran Date 2015-10-05 Time 16:02 Rev Time 0.00
Received By albarran Date 2015-10-05 Time 15:11 Sent To I
Notes
2015-10-05 16:05:16ALL THE PREVIOUSLY MENTIONED COMMENTS HAVE BEEN
 SATISFACTORILY ADDRESSED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-07-29 Cont ID  
Sent By albarran Date 2015-07-29 Time 18:37 Rev Time 0.00
Received By albarran Date 2015-07-29 Time 18:13 Sent To  
Notes
2015-07-29 18:25:19PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 1. CORRECT DRAWING INDEX TO INCLUDE ELECTRICAL PAGE
 E-0.
 2. CORRECT "ELECTRICAL NOTES" # 19 TO INCLUDE 36" FROM
 TIP OF PADDLE FAN BLADE.
 3. NEC 250.94, THE RISER DIAGRAM IS MISSING THE
 REQUIRED INTER-SYSTEM BONDING TERMINAL.
 4. THE WORD ?ROMEX? AS USED IN THIS NOTE IS TO IDENTIFY
 A TYPE OF CABLE. ROMEX IS A BRAND NAME AND NOT A TYPE
 OF CABLE, REFER TO CABLE TYPES ?NM?, ?NMC? OR ?NMS?.
 5. THE LOAD CALCS AS SUBMITTED DID NOT MATCH WITH MY
 CALCULATION OF THE CONNECTED LOAD AS SUBMITTED.
 6. FBC-B, PROVIDE THE SCALE USED ON THE DRAWING ALONG
 WITH THE COMPASS ?N? ON THE PLANS.
 7. NEC 314.27(A), BOXES USED AT LUMINAIRE OR LAMPHOLDER
 OUTLETS IN A CEILING SHALL BE REQUIRED TO SUPPORT A
 LUMINAIRE WEIGHING A MINIMUM OF 50 LB. ADD THIS TO THE
 NOTES ON CEILING BOXES ON PAGE.
 8. BATHROOM #3 IS MISSING THE REQUIRED GFCI OUTLET.
 9. NEC 410.11, THE ATTIC LIGHT SHALL HAVE A GUARD
 AROUND THE LAMP.
 10. FBC-E SECTION 404 HAS SPECIFIC LIGHTING
 REQUIREMENTS WHICH SHALL BE COMPLIED WITH.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2015-10-29 Cont ID  
Sent By tklarge Date 2015-09-24 Time 06:32 Rev Time 0.00
Received By tklarge Date 2015-09-24 Time 06:32 Sent To  
Notes
2015-09-24 06:32:47THE GAS INSTALLATION SHALL BE DONE UNDER A SEPARATE
 PERMIT. TWO COPIES OF MANUF. SPECS. FOR ALL QAS
 APPLIANCES SHALL BE SUBMITTED AT TIME OF GAS
 APPLICATION SUBMITTAL ALONG WITH VENTING DETAILS AND
 COMBUSTION AIR CALCULATIONS AND OTHER DETAILS AS
 REQUIRED BY THE CODE.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-07-15 Cont ID  
Sent By tklarge Date 2015-07-15 Time 05:18 Rev Time 0.00
Received By tklarge Date 2015-07-15 Time 05:18 Sent To  
Notes
2015-07-15 05:48:261) SHOW THE LOCATION OF THE TANKLESS WATER ON THE FLOOR
 PLAN.THE PLANS SHOW A TANK TYPE WATER HEATER IN THE
 GARAGE. WHAT IS BEING INSTALLED, A TANKLESS WATER
 HEATER OR A TANK TYPE? CLARIFY.WPB AMEND. TO FBC
 SEC.107.2.1.
 2) IF THE TANK TYPE WATER HEATER IN THE GARAGE IS
 REMAINING, IT SHALL BE PROTECTED FROM VEHICLE IMPACT
 DAMAGE,SUBMIT DETAILS AS TO THE METHOD OF
 PROTECTION.WPB AMEND. TO FBC SEC. 107.2.1.
 3) THE GAS RISER SHOWS A GAS GRILL ON IT BUT IT IS NOT
 SHOWN ANYWHERE ON THE PLANS. CLARIFY.
 5) SHOW THE LOCATION OF THE GAS METER ON THE PLANS. WPB
 AMEND. TO FBC SEC. 107.2.1.
 6 THE GAS INSTALLATION SHALL BE DONE UNDER A SEPARATE
 PERMIT. TWO COPIES OF MANUF. SPECS. FOR ALL QAS
 APPLIANCES SHALL BE SUBMITTED AT TIME OF GAS
 APPLICATION SUBMITTAL ALONG WITH VENTING DETAILS AND
 COMBUSTION AIR CALCULATIONS AND OTHER DETAILS AS
 REQUIRED BY THE CODE.
 7) SHT. P-1 INDICATES THE GAS PIPING WILL BE METALLIC
 PIPE. METALLIC PIPE CANNOT BE INSTALLED UNDERGROUND PER
 2012 FBC- RESIDENTIAL, SEC. G 2415.9, G2415.9.1.
 INDICATE THE TYPE OF PIPING TO BE INSTALLED FOR THE
 POOL HEATER,
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-10-29 Cont ID  
Sent By ccole Date 2015-10-29 Time 09:23 Rev Time 0.00
Received By ccole Date 2015-10-27 Time 09:48 Sent To  
Notes
2015-10-28 09:48:32RESUB ROUTED TO DKITTRED VIA SGRAHAM'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-05 Cont ID  
Sent By albarran Date 2015-10-05 Time 16:03 Rev Time 0.00
Received By albarran Date 2015-09-15 Time 11:58 Sent To  
Notes
2015-10-05 16:06:5310/5/15 PASSED ELECTRICAL REVIEW BUT STILL HAS BLDG.
 ISSUES PENDING. CONTRACTOR NOTIFIED VIA EMAIL. SENT TO
 LARGE DENIED BIN "W". MA
2015-10-05 16:04:35 
  
2015-09-16 11:59:33R28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-21 Cont ID  
Sent By ccole Date 2015-08-21 Time 09:10 Rev Time 0.00
Received By ccole Date 2015-06-25 Time 08:16 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2015-09-30 Cont ID  
Sent By ccole Date 2015-09-30 Time 11:09 Rev Time 0.00
Received By ccole Date 2015-09-30 Time 11:09 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-08-21 Cont ID  
Sent By ccole Date 2015-08-21 Time 09:10 Rev Time 0.00
Received By ccole Date 2015-08-21 Time 09:10 Sent To  
Notes
2015-08-21 09:10:281ST REVIEW: FBC 2010 BUILDING
 PERMIT #15061205
 8/20/15
  
 1) PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE.
 CALL 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED WITH A COPY OF RECEIPT AS APPLICABLE.
  
 CHRISTOPHER L. COLE
 STANDARD PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-09-24 Cont ID  
Sent By ccole Date 2015-09-24 Time 12:56 Rev Time 0.00
Received By ccole Date 2015-09-24 Time 12:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-08-21 Cont ID  
Sent By ccole Date 2015-08-21 Time 09:10 Rev Time 0.00
Received By ccole Date 2015-08-21 Time 09:10 Sent To  
Notes
2015-08-21 09:11:31MECHANICAL PROVISO:
 8/20/15
  
 1) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE KITCHEN EXHAUST HOOD SHALL BE
 ON-SITE AT TIME OF INSPECTION.
 REVISION REQUIRED FOR MAKEUP AIR IF APPLICABLE.
 M1503.4 FBC-10 RESIDENTIAL- MAKEUP AIR REQUIRED.
 EXHAUST HOOD SYSTEMS CAPABLE OF EXHAUSTING IN EXCESS OF
 400 CUBIC FEET PER MINUTE (0.19 M3/S) SHALL BE PROVIDED
 WITH MAKEUP AIR AT A RATE APPROXIMATELY EQUAL TO THE
 EXHAUST AIR RATE. SUCH MAKEUP AIR SYSTEMS SHALL BE
 EQUIPPED WITH A MEANS OF CLOSURE AND SHALL BE
 AUTOMATICALLY CONTROLLED TO START AND OPERATE
 SIMULTANEOUSLY WITH THE EXHAUST SYSTEM.
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-09-24 Cont ID  
Sent By tklarge Date 2015-09-24 Time 06:25 Rev Time 0.00
Received By tklarge Date 2015-09-24 Time 06:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-07-15 Cont ID  
Sent By tklarge Date 2015-07-15 Time 05:17 Rev Time 0.00
Received By tklarge Date 2015-07-15 Time 04:05 Sent To  
Notes
2015-07-15 05:17:131) SHT. P-2 - THE WATER CLOSET, SHOWER AND TUB IN THE
 MASTER BATH ARE NOT PROPERLY VENTED AS DRAWN. FBC-
 RESIDENTIAL SEC.P3101.2, P3101.2.1.
 2) SHOW THE LOCATION OF THE TANKLESS WATER HEATER ON
 THE FLOOR PLAN.THE PLANS SHOW A TANK TYPE WATER HEATER
 IN THE GARAGE. WHAT IS BEING INSTALLED, A TANKLESS
 WATER HEATER OR A TANK TYPE? CLARIFY.WPB AMEND. TO FBC
 SEC.107.2.1.
 3) IF THE TANK TYPE WATER HEATER IN THE GARAGE IS
 REMAINING, IT SHALL BE PROTECTED FROM VEHICLE IMPACT
 DAMAGE,SUBMIT DETAILS AS TO THE METHOD OF
 PROTECTION.WPB AMEND. TO FBC SEC. 107.2.1.
 4) THE GAS RISER SHOWS A GAS GRILL ON IT BUT IT IS NOT
 SHOWN ANYWHERE ON THE PLANS. CLARIFY.
 5) SHOW THE LOCATION OF THE GAS METER ON THE PLANS. WPB
 AMEND. TO FBC SEC. 107.2.1.
 6) THE GAS INSTALLATION SHALL BE DONE UNDER A SEPARATE
 PERMIT. TWO COPIES OF MANUF. SPECS. FOR ALL QAS
 APPLIANCES SHALL BE SUBMITTED AT TIME OF GAS
 APPLICATION SUBMITTAL ALONG WITH VENTING DETAILS AND
 COMBUSTION AIR CALCULATIONS AND OTHER DETAILS AS
 REQUIRED BY THE CODE.
 7) THE PLANS REFER TO PLUMBING AT THE SUMMER KITCHEN
 BUT NO PLUMBING IS SHOWN ON THE FLOOR PLAN OR THE
 SANITARY RISER.CLARIFY.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop Z ZONING
Rev No 4 Status P Date 2015-10-28 Cont ID  
Sent By dkittred Date 2015-10-28 Time 15:45 Rev Time 0.00
Received By dkittred Date 2015-10-28 Time 15:21 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2015-09-28 Cont ID  
Sent By dkittred Date 2015-09-28 Time 10:45 Rev Time 0.00
Received By dkittred Date 2015-09-28 Time 10:45 Sent To  
Notes
2015-09-28 10:45:23PLANNING AND ZONING COMMENTS: ***FAILED***
  
 9/28/15
  
 1. INCLUDE A WING WALL/FENCE ALONG THE ZERO LOT LINE
 SIDE OF THE PROPERTY (ZLDR SEC. 94-309(H)).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2015-09-17 Cont ID  
Sent By dkittred Date 2015-09-17 Time 11:55 Rev Time 0.00
Received By dkittred Date 2015-09-17 Time 11:55 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2015-07-08 Cont ID  
Sent By dkittrid Date 2015-07-08 Time 09:50 Rev Time 0.00
Received By dkittred Date 2015-07-08 Time 09:19 Sent To  
Notes
2015-07-08 09:50:57PLANNING AND ZONING: ***FAILED***
  
 7/8/15
  
 1. A SEPARATE LANDSCAPE PERMIT IN CONFORMANCE WITH
 ARTICLE XIV SHALL BE SUBMITTED. (NOTE: ZLDR SEC.
 94-442(B)(2)A. - FOR SINGLE-FAMILY DWELLING UNITS, AT
 LEAST ONE SHADE, FLOWERING, OR FRUIT TREE SHALL BE
 PLANTED FOR EACH 1,200 SQUARE FEET OF OPEN SPACE OR
 PORTION THEREOF. FOR SINGLE-FAMILY DWELLING UNITS, AT
 LEAST ONE SHRUB SHALL BE PLANTED FOR EACH 500 SQUARE
 FEET OF OPEN SPACE OR PORTION THEREOF. PLEASE ADJUST
 CALCULATIONS TABLE.)
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]