Plan Review Details - Permit 15061181
Plan Review Stops For Permit 15061181
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-11-17 Cont ID  
Sent By jwitmer Date 2015-11-17 Time 15:50 Rev Time 0.00
Received By jwitmer Date 2015-11-12 Time 13:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-10-02 Cont ID  
Sent By jwitmer Date 2015-10-02 Time 11:06 Rev Time 0.00
Received By jwitmer Date 2015-10-02 Time 05:47 Sent To  
Notes
2015-10-02 11:06:00BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15061181
 ADD: 2403 S DIXIE HIGHWAY
 CONT: BUTLER CONSTRUCTION COMPANY
 TEL: (561)832-9700
 E-MAIL: SBUTLERBUTLERCONSTRUCTIONUSA.COM
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
  
 2ND REVIEW
 DATE: FRI. OCT. 02/2015
 ACTION: DENIED
  
 NOTE: THE MEZZANINE AS IT STANDS IS A CODE COMPLIANT
 MEZZANINE UNDER THE BUILDING CODE IT WAS BUILT
 UNDER1960-1961 SOUTHERN STANDARD BUILDING CODE. 402.4.
 MEZZANINE FLOORS SHALL NOT BE REGARDED AS A STORY
 UNLESS THEY EXCEED THIRTY-THREE AND ONE-THIRD (33 1/3)
 PER CENT OF THE AGGREGATE FLOOR AREA. THE CURRENT
 CODE2010 FBC-B 505.2 THE WORDING STATES THE ENCLOSED
 PORTION OF A ROOM SHALL NOT BE INCLUDED IN A
 DETERMINATION OF THE FLOOR AREA OF THE ROOM IN WHICH
 THE MEZZANINE IS LOCATED.
  
 AS PART OF THE INTERIOR DEMO PERMIT 800 SQ. FT. OF
 MEZZANINE FLOOR AREA WAS REMOVED FROM THE FLOOR AREA,
 THE MEZZANINE FLOOR WILL BE DEEMED CODE COMPLIANT UNDER
 THE 2010 FBC-EXISTING BUILDING 101.5 EXCEPTION SUBJECT
 TO THE APPROVAL OF THE BUILDING OFFICIAL, ALTERATIONS
 COMPLYING WITH THE LAWS IN EXISTENCE AT THE TIME THE
 BUILDING WAS BUILT.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1) COMPLIED. INTERIOR RENOVATION.
 2) COMPLIED. MERCANTILE.
 3) COMPLIED
 4) SHEET A-2.0:
 4A-C) COMPLIED
 4D) 2ND REQUEST . PLEASE PROVIDE THE WIND DESIGN
 CRITERIA FOR THE ROOF TOP CURB:
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
  
 4D)(1)COMPLIED. THE BASIC WIND SPEED, VU, SHALL BE
 DETERMINED IN ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 4D)( 2) COMPLIED. AN IMPORTANCE FACTOR, FIGURE 1609
 A-C, ASCE 7-10.
  
 4D)( 3) COMPLIED. AN EXPOSURE CATEGORY SHALL BE
 DETERMINED IN ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4D)(4) 2ND REQUEST. A HEIGHT AND EXPOSURE ADJUSTMENT
 COEFFICIENT, * SHALL BE DETERMINED FROM TABLE 1609.7.2.
 ASCE 7-10.
  
 4D)(5)2ND REQUEST. COMPONENTS & CLADDING PRESSURES
 POSITIVE & NEGATIVE TABLE 1609.2(2) . NOTE IF THE
 PARAPET IS 3?-0? OR MORE AROUND THE PERMTER !!!!
 AFFECTS ROOF PRESSURES FOR ZONE 3.
  
 4E) COMPLIED.
 4F) 2ND REQUEST, DO NOT RECITE CODE, SHOW COMPLIANCE.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH
 DRAWINGS AND SPECIFICATIONS SHALL CONTAIN INFORMATION,
 IN THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
 COMMENT FROM 1ST REVIEW. PLEASE ALSO SHOW COMPLIANCE
 WITH 2010 FBC-B 1013.5 GUARDS ON ROOFS FOR MECHANICAL
 EQUIPMENT/ 1013.6 ROOF ACCESS.
  
 5) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A)-(C) COMPLIED.
 2ND REQUEST. (D) ROOFING PRODUCTS AND ASSEMBLIES/ ROOF
 TOP CURBS ROOFING REPAIRS OF THE ROOF WILL NEED TO
 OCCUR WHERE THE NEW ROOF HATCH AND ROOF TOP CURB ARE
 INSTALLED .
  
 6) COMPLIED. 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC
  
 7) SHEET A-8.0, NEW COMMENT THE STAIR DETAIL OPEN TO
 THE 2ND FLOOR NOW SHOWS A NEW MODULAR SHELVING UNIT.
 THE 2010 FBC-B 1009.9.3 THERE SHALL BE NO STORAGE UNDER
 THE STAIR, UNLESS IN A 1 HOUR ENCLOSURE. PLEASE REVIEW
 THE 2012 IBC COMMENTARY, COMMENTARY SECTION STATES, THE
 STAIRWAY MUST BE PROTECTED FROM STORAGE UNDER IT, EVEN
 IF THE STAIR IS NOT REQUIRED TO BE ENCLOSED.
  
 8A) 2ND REQUEST. SHEET A1.5 INDICATES ON THE MEZZANINE
 LEVEL THIS AREA IS TO BE A STORAGE. PLEASE SEE UNDER
 THE 2010 FBC-B TABLE 1607.1 STORAGE LIGHT 125 PSF OR
 HEAVY 250 PSF.
 SHEET A1.5COMMENT FROM 1ST REVIW.2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 106.1 LIVE LOADS POSTED. WHERE THE LIVE
 LOADS FOR WHICH EACH FLOOR OR PORTION THEREOF OF A
 COMMERCIAL OR INDUSTRIAL BUILDING IS OR HAS BEEN
 DESIGNED TO EXCEED 50 PSF (2.40 KN/M2), SUCH DESIGN
 LIVE LOADS SHALL BE CONSPICUOUSLY POSTED BY THE OWNER
 IN THAT PART OF EACH STORY IN WHICH THEY APPLY, USING
 DURABLE SIGNS. IT SHALL BE UNLAWFUL TO REMOVE OR DEFACE
 SUCH NOTICES.
  
 8B) 2ND REQUEST. 106.2 ISSUANCE OF CERTIFICATE OF
 OCCUPANCY. A CERTIFICATE OF OCCUPANCY REQUIRED BY
 SECTION 111 SHALL NOT BE ISSUED UNTIL THE FLOOR LOAD
 SIGNS, REQUIRED BY SECTION 106.1, HAVE BEEN INSTALLED.
  
 8C) 2ND REQUEST. 106.3 RESTRICTIONS ON LOADING. IT
 SHALL BE UNLAWFUL TO PLACE, OR CAUSE OR PERMIT TO BE
 PLACED, ON ANY FLOOR OR ROOF OF A BUILDING, STRUCTURE
 OR PORTION THEREOF, A LOAD GREATER THAN IS PERMITTED BY
 THIS CODE.
  
 9) PLANS MAY REQUIRE REVIEW BY PALM BEACH COUNTY IMPACT
 FEE OFFICE. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date   Cont ID  
Sent By albarran Date 2015-07-24 Time 10:03 Rev Time 0.00
Received By jwitmer Date 2015-07-24 Time 06:32 Sent To  
Notes
2015-07-24 06:53:26BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15061181
 ADD: 2403 S DIXIE HIGHWAY
 CONT: BUTLER CONSTRUCTION COMPANY
 TEL: (561)832-9700
 E-MAIL: SBUTLERBUTLERCONSTRUCTIONUSA.COM
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
  
 1ST REVIEW
 DATE: FRI. JULY 24/2015
 ACTION: DENIED
  
 NOTE: THE MEZZANINE AS IT STANDS IS A CODE COMPLIANT
 MEZZANINE UNDER THE BUILDING CODE IT WAS BUILT
 UNDER1960-1961 SOUTHERN STANDARD BUILDING CODE. 402.4.
 MEZZANINE FLOORS SHALL NOT BE REGADED AS A STORY UNLESS
 THEY EXCEED THIRTHY-THREE AND ONE-THIRD (33 1/3) PER
 CENT OF THE AGGREGATE FLOOR AREA. THE CURRENT CODE2010
 FBC-B 505.2 THE WORDING STATES THE ENCLOSED PORTION OF
 A ROOM SHALL NOT BE INCLUDED IN A DETERMENATION OF THE
 FLOOR AREA OF THE ROOM IN WHICH THE MEZANINE IS
 LOCATED.
  
 AS PART OF THE INTERIOR DEMO PERMIT 800 SQ. FT. OF
 MEZZANINE FLOOR AREA WAS REMOVED FROM THE FLOOR AREA,
 THE MEZANINE FLOOR WILL BE DEEMED CODE COMPLIANT UNDER
 THE 2010 FBC-EXESTING BUILDING 101.5 EXCEPTION SUBJECT
 TO THE APPROVAL OF THE BUILDING OFFICIAL,ALTERATIONS
 COMPLYING WITH THE LAWS IN EXISTENCE AT THE TIME THE
 BUILDING WAS BUILT.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1) CLARIFICATION OF THE PERMIT APPLICATION UNDER THE
 HEADING OF DESCRIPTION OF WORK: ADD WINDOWS & FINISHES
 TO EXISTING COVERED TERRACE. THE WORK SHOWN WITHIN THE
 PERMIT SET OF PLANS HAS NOTHING TO DO WITH AN EXISTING
 COVERED TERRACE. 107.2.1.3 ADDITIONAL INFORMATION
 REQUIRED, DESCREPANCY IN PERMIT APPLICATIONAND SCOPE OF
 WORK IN PLANS.
  
 2) THE LS-1 SHEET THIS SHEET APPEARS TO BE A BUSINESS
 OCCUPANCY ON THE MAIN FLOOR VERSES THE CODE DATA
 LISTING THE OCCUPANCY AS A MERCANTILE. PLEASE PROVIDE A
 NARRATIVE AS HOW THIS SPACE WILL BE USED? BUSNIESS
 VERSES MERCANTILE. 2010 FBC-B SECTION 304-BUSINESS
 VERSES 309-MERCANTILE.
  
 3) SHEET LS-1 THE CONERENCE ROOM # 108 IS APPROXIMATELY
 324 SQ. FT./ 15 = 22 OCCUPANTS. 2010 FBC-B TABLE
 1004.1.1 USES 15 SQ. FT. / OCCUPANT WHEN THERE IS AN
 ASSEMBLY FUNCTION SEE BOAF INFORMAL INTERPRETATION
 6754. THE CONFERENCE ROOM SHOWS HORIZONTAL SLIDING
 DOORS AS THE ONLY MEANS OF EGRESS FOR THIS ROOM. THE
 2010 FBC-B 1008.1.2 DOOR SWING REQUIRES EGRESS DOORS TO
 BE PIVOTED OR SIDE HINGED SWINGING TYPE. EXCEPTION # 1
 LIMITS THE USE OF SLIDDING DOORS IN OFFICE AREAS WHERE
 THE OCCUPANT LOAD IS 10 OR LESS. DOORS NOT FOUND ON
 DOOR SCHEDULE FOR ROOMS 108, 107 & 105.
  
 4) SHEET A-2.0:
  
 4A) DETAIL # 2 IS A ROOF TOP CURB DETAIL FOR A NEW ROOF
 TOP A/C UNIT. DETAIL NOTE INDICATES SEE MECHANICAL CURB
 EQUIPMENT DETAIL. THE MECHANICAL SHEETS DO NOT SHOW ANY
 SUCH DETAIL. PLEASE SHOW HOW THE NEW ROOF TOP CURB WILL
 BE SECURED TO THE (MWFRS) MAIN WIND FORCE RESISTING
 SYSTEM. PLEASE PROVIDE THE SIZE OF THE NEW HOLE TO BE
 CUT INTO THE ROOF DECK. SHOW THE REINFORCING OF THE
 EDGE OF DECK, NEW FRAMING MEMBER SIZES, HOW THEY ARE TO
 ANCHORED TO THE BAR JOIST, IF THE BAR JOIST ARE GOING
 TO NEED TO BE RE-INFORCED BECAUSE OF THE NEW POINT
 LOADING. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES.
  
 4B) PLEASE PROVIDE THE PRODUCT APPROVAL FOR THE NEW
 ROOF TOP CURB. 2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES/ ROOF TOP
 CURBS.
  
 4C) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 4D) PLEASE PROVIDE THE WIND DESIGN CRITERIA FOR THE
 ROOF TOP CURB:
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
  
 4D)(1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 4D)( 2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE
 7-10.
  
 4D)( 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4D)(4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 4D)(5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 4E) THE PLANS FAIL TO SHOW COMPLIANCE WITH SECTION 2010
 FBC-B 1509.6 EQUIPMENT AND APPLIANCES ON ROOFS.
  
 4F) PLEASE ALSO SHOW COMPLIANCE WITH 2010 FBC-B 1013.5
 GUARDS ON ROOFS FOR MECHANICAL EQUIPMENT/ 1013.6 ROOF
 ACCESS.
  
 5) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) WALL LOUVERS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES/ ROOF TOP CURBS
  
 6) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC
  
 7) SHEET A-8.0 SHOWS THE WATER FOUNTAIN UNDER THE
 STAIRS. PLEASE PROVIDE COMPLIANCE WITH 2010
 FBC-ACCESSIBILITY CODE 307.2 PROTRUDING OBJECTS.
  
 8A) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION 106.1 LIVE
 LOADS POSTED. WHERE THE LIVE LOADS FOR WHICH EACH FLOOR
 OR PORTION THEREOF OF A COMMERCIAL OR INDUSTRIAL
 BUILDING IS OR HAS BEEN DESIGNED TO EXCEED 50 PSF (2.40
 KN/M2), SUCH DESIGN LIVE LOADS SHALL BE CONSPICUOUSLY
 POSTED BY THE OWNER IN THAT PART OF EACH STORY IN WHICH
 THEY APPLY, USING DURABLE SIGNS. IT SHALL BE UNLAWFUL
 TO REMOVE OR DEFACE SUCH NOTICES.
  
 8B) 106.2 ISSUANCE OF CERTIFICATE OF OCCUPANCY. A
 CERTIFICATE OF OCCUPANCY REQUIRED BY SECTION 111 SHALL
 NOT BE ISSUED UNTIL THE FLOOR LOAD SIGNS, REQUIRED BY
 SECTION 106.1, HAVE BEEN INSTALLED.
  
 8C) 106.3 RESTRICTIONS ON LOADING. IT SHALL BE UNLAWFUL
 TO PLACE, OR CAUSE OR PERMIT TO BE PLACED, ON ANY FLOOR
 OR ROOF OF A BUILDING, STRUCTURE OR PORTION THEREOF, A
 LOAD GREATER THAN IS PERMITTED BY THIS CODE.
  
 9) PLANS MAY REQUIRE REVIEW BY PALM BEACH COUNTY IMPACT
 FEE OFFICE. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-12-02 Cont ID  
Sent By albarran Date 2015-12-02 Time 19:09 Rev Time 0.00
Received By albarran Date 2015-12-02 Time 18:57 Sent To I
Notes
2015-12-02 19:10:24ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 SATISFACTORILY ADDRESSED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-10-23 Cont ID  
Sent By albarran Date 2015-10-23 Time 09:27 Rev Time 0.00
Received By albarran Date 2015-10-22 Time 09:52 Sent To I
Notes
2015-10-23 09:35:53I TRIED TO RED-LINE THESE FOR THE CONTRACTOR IN ORDER
 TO ISSUE THE PERMIT, BUT LATER REALIZED THAT THIS HAD
 FAILED THE FIRE AND BLDG REVIEWS AND A PROVISO WOULD
 NOT HELP. I EMAILED JOE OF GLIDDENSPINA TO ADVISE HIM
 THE THE SITUATION.
 THE FOLLOWING ITEMS NEED TO BE CORRECTED ON THE
 DRAWINGS:
 1. THE LIGHT IN THE STORAGE AREA SHALL BE CONTROLLED
 VIA AN OCCUPANCY/MOTION SENSOR SWITCH RATHER THAN A
 STRAIGHT ON/OFF SWITCH SO THE LIGHT CAN'T BE LEFT ON
 UNINTENTIONALLY.
 2. THERE IS A SIGN OUTLET MISSING FROM A SECOND ENTRY
 DOOR AS EXPLAINED TO JOE.
2015-10-22 10:51:25I CALLED TO SPEAK W/THE DESIGN PROFESSIONAL ON TWO
 MINOR ITEMS NEEDING CORRECTION. I AM WILLING TO
 RED-LINE THE DRAWINGS AND GET THEM OUT AS LONG AS THE
 DP CONCURS WITH MY FINDINGS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-08-10 Cont ID  
Sent By albarran Date 2015-08-10 Time 15:51 Rev Time 0.00
Received By albarran Date 2015-07-24 Time 09:37 Sent To I
Notes
2015-08-10 15:51:33PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. ELECTRICAL SUB PERMIT REQUIRRED
 2. GRD FLOOR LIGHTING NOT IN COMPLIANCE W/FBC-E
 3. GRD FLOOR MISSING EMERGENCY LIGHTING IN RESTROOMS,
 OFFICE 105 & BREAK ROOM PER FBC=B 1006.2
 4. GRD FLOOR MISSING THE SHOW WINDOW OUTLETS REQUIRED
 IN NEC 210.62
 5. GRD FLOOR MISSING THE SIGN OUTLET AS PER NEC 600.5
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  
2015-07-24 10:00:07 
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2015-12-02 Cont ID  
Sent By rlindow Date 2015-12-02 Time 07:51 Rev Time 0.00
Received By rlindow Date 2015-12-02 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2015-09-30 Cont ID  
Sent By   Date 2015-09-30 Time   Rev Time 0.00
Received By   Date 2015-09-30 Time   Sent To  
Notes
2015-09-30 07:38:36TRAVEL DISTANCE AND COMMON PATH OF TRAVEL DISTANCE
 EXCEED MAXIMUM DISTANCE ALLOWED FOR MEZZANINE. (LS-1)
 FFPC NFPA 101, 37.2.5.3

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-06-30 Cont ID  
Sent By Lindow Date 2015-06-30 Time   Rev Time 0.00
Received By rlindow Date 2015-06-30 Time   Sent To  
Notes
2015-06-30 15:01:35OCCUPANCY CALCULATIONS ON SHEET LS-1 ARE BASED ON
 MERCANTILE.
 PLANS SUBMITTED SHOW BUSINESS OCCUPANCY.
 FURTHER DEFINE USE OF SPACE.
 6/30/15 LINDOW

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-12-02 Cont ID  
Sent By albarran Date 2015-12-02 Time 19:13 Rev Time 0.00
Received By albarran Date 2015-11-03 Time 10:58 Sent To  
Notes
2015-12-02 19:17:4412/2/15 PASSED ELECTRICAL REVIEW. CONTACTED JOE OF
 GLIDDENSPINA AND SAK BECAUSE THERE IS NO EMAIL FOR THE
 CONTRACTOR IN THE SYSTEM. SENT TO LARGE READY BIN "G".
 MA
2015-11-04 10:59:10C15

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-23 Cont ID  
Sent By albarran Date 2015-10-23 Time 09:36 Rev Time 0.00
Received By albarran Date 2015-08-27 Time 13:35 Sent To  
Notes
2015-10-23 09:37:0010/22/15 FAILED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT TO LARGE DENIED BIN "G". MA
2015-08-27 13:36:09C16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-10 Cont ID  
Sent By albarran Date 2015-08-10 Time 15:56 Rev Time 0.00
Received By albarran Date 2015-06-25 Time 13:41 Sent To  
Notes
2015-08-10 15:58:158/10/15 FAILED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT TO LARGE DENIED BIN "B". MA

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2015-12-08 Cont ID  
Sent By jwitmer Date 2015-12-08 Time 13:56 Rev Time 0.00
Received By jwitmer Date 2015-12-08 Time 13:56 Sent To  
Notes
2015-12-08 13:57:2512/08/2015 PLANS STAMPED NO FEES DUE P. B. C. IMPACT
 FEES. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-10-02 Cont ID  
Sent By jwitmer Date 2015-10-02 Time 11:06 Rev Time 0.00
Received By jwitmer Date 2015-10-02 Time 11:06 Sent To  
Notes
2015-10-02 11:08:36WITH THE REDUCTION OF SQUARE FEETOF THE MEZZANINE THERE
 MAYBE A CREDIT DUE FOR IMPACT FEES, PLUS THE SQARE
 FOOTAGE TAX BASE SHOULD ALSO BE REDUCED.
 PLANS MAY REQUIRE REVIEW BY PALM BEACH COUNTY IMPACT
 FEE OFFICE. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-07-24 Cont ID  
Sent By jwitmer Date 2015-07-24 Time 10:29 Rev Time 0.00
Received By jwitmer Date 2015-07-24 Time 10:29 Sent To  
Notes
2015-07-24 10:29:30PLANS MAY REQUIRE REVIEW BY PALM BEACH COUNTY IMPACT
 FEE OFFICE. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-09-02 Cont ID  
Sent By ccole Date 2015-09-02 Time 15:34 Rev Time 0.00
Received By ccole Date 2015-09-02 Time 15:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-07-08 Cont ID  
Sent By ccole Date 2015-07-08 Time 15:06 Rev Time 0.00
Received By ccole Date 2015-07-08 Time 15:06 Sent To  
Notes
2015-07-08 15:49:341ST REVIEW: FBC 2010 MECHANICAL
  
 1) THE AC SYSTEMS AT 15 TONS OF COOLING CAPACITY ARE
 OVERSIZED PER THE LOAD CALCULATIONS WHICH ARE
 INDICATING A TOTAL LOAD OF 11.3 TONS. HEATING AND
 COOLING EQUIPMENT AND SYSTEMS CAPACITY SHALL NOT EXCEED
 THE CALCULATED LOADS- SECTION 503.2.2 FBC-10 ENERGY
 CONSERVATION.
 2) SHEET M6.1: THE 34.3 SENSIBLE CAPACITY LISTED IN THE
 AC SCHEDULE DOES NOT SEEM TO BE ACCURATE FOR THE NEW
 7.5 TON PACKAGED UNIT- PLEASE SUBMIT MANUFACTURER'S
 PRODUCT SPEC SHEETS FOR VERIFICATION.
 3) M2.1: PROVIDE THE RETURN DUCT SIZES FROM THE OFFICE
 (107) AND CONFERENCE (108) GRILLS, AND SHOW THE ENTIRE
 DUCT RUNS BACK TO THE RTU. IF THE DUCTS SHOWN IN THE
 DRAWING ARE DUCT BOOT SOUND ATTENTUATORS, PLEASE LABEL
 THEM AS SUCH TO CLARIFY HOW THE RETURN AIR SYSTEM IS
 FUNCTIONING.
 4) M2.1: PLEASE CLARIFY WHY TWO 6 INCH TRANSFER DUCTS
 ARE SHOWN CONNECTING THE RETURN GRILLS IN THE OPEN
 SEATING (104) AND THE OFFICE (105) CEILINGS.
 5) M2.1: SHOW THE SIZE OF THE TRANSFER GRILL BETWEEN
 THE FLEX SPACE (113), AND THE HALLWAY (110).
 6) A2.0: THE DETAILS SHOWN FOR INSTALLATION OF THE NEW
 RTU AND CURB ARE INCOMPLETE. ENGINEERED STRUCTURAL
 DETAILS ARE REQUIRED FOR MODIFICATIONS TO THE EXISTING
 ROOF STRUCTURE, AND WINDLOAD ENGINEERING FOR ANCHORING
 OF THE CURB AND MOUNTING THE RTU- SECTION 301.12 FBC-10
 MECHANICAL.
 7) A2.0: SHOW THE CONDENSATE PIPING RUN AND DISCHARGE
 LOCATION. INDICATE THE TYPE AND SIZE OF PIPING, PIPING
 SUPPORTS, AND HOW THE PIPING WILL BE PROTECTED FROM
 WEATHERING AND UV DEGRADATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-09-09 Cont ID  
Sent By gjohnson Date 2015-09-08 Time 10:16 Rev Time 0.00
Received By gjohnson Date 2015-09-08 Time 10:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-07-22 Cont ID  
Sent By gjohnson Date 2015-07-22 Time 10:41 Rev Time 0.00
Received By gjohnson Date 2015-07-22 Time 10:41 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2015-09-16 Cont ID  
Sent By eschneid Date 2015-09-16 Time 08:46 Rev Time 0.00
Received By eschneid Date 2015-09-15 Time 17:16 Sent To  
Notes
2015-09-16 08:51:30PASSED W/PROVISOS
  
 1) PROVISO - THE VALUE OF THE CONSTRUCTION ($300,450)
 EXCEEDS 50% OF THE STRUCTURE'S VALUE ($283,838)
 ACCORDING TO THE P.B.C. PROPERTY APPRAISER'S OFFICE;
 THEREFORE, PURSUANT TO SECTION 94-441(C)(2) OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDR), THE
 LANDSCAPE ON THE SITE SHALL BE IN COMPLIANCE WITH ALL
 APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF THE
 ZLDR. PRIOR TO THE FINAL INSPECTION (104) APPROVAL FOR
 THE WORK ASSOCIATED WITH THIS PERMIT, THE APPLICANT
 SHALL APPLY FOR A SEPARATE LANDSCAPE PERMIT AND AN
 IRRIGATION PERMIT SHOWING MATERIAL TO BRING THE SITE
 INTO CONFORMITY AND INSTALL AND PASS INSPECTIONS FOR
 THE APPROVED PERMITS.
  
 2) PROVISO - THE PARKING LOT REQUIRES A SEPARATE
 PARKING PERMIT WHICH SHALL BE SUBMITTED, INSTALLED AND
 PASS FINAL INSPECTION PRIOR TO THE FINAL INSPECTION
 (104) APPROVAL FOR THE WORK ASSOCIATED WITH THIS
 PERMIT. PLEASE NOTE THAT THE PARKING LOT AS SHOWN DOES
 NOT MEET THE CURRENTLY APPROVED PARKING LAYOUT (PLEASE
 SEE PERMIT NO. 8999G), NOR DOES IT CONFORM TO CITY
 PARKING REQUIREMENTS. PARKING COMMENTS WILL BE PROVIDED
 AT TIME OF PARKING LOT PERMIT SUBMITTAL.
  
 3) A SEPARATE PERMIT WILL BE REQUIRED FOR ANY SIGNAGE
 ON THE SITE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2015-07-29 Cont ID  
Sent By eschneid Date 2015-07-29 Time 15:11 Rev Time 0.75
Received By eschneid Date 2015-07-14 Time 15:00 Sent To  
Notes
2015-07-29 15:13:21FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) THE VALUE OF THE CONSTRUCTION ($300,450) EXCEEDS 50%
 OF THE STRUCTURE'S VALUE ($283,838) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY.
  
 2) THE BUILDING ENCROACHES INTO THE SOUTH SIDE SETBACK
 - FIVE (5) FEET REQUIRED, ZERO (0) FEET PROVIDED, WHICH
 CLASSIFIES THE STRUCTURE AS HAVING A DIMENSIONAL
 NONCONFORMITY. IN ACCORDANCE WITH SECTION
 94-513(B)(1)A, THE PORTION OF THE BUILDING LOCATED
 WITHIN THE SETBACK MAY ONLY BE ALTERED IF THE
 ALTERATION REDUCES THE IMPACT ON OF THE NONCONFORMITY
 UPON ADJACENT PROPERTIES. PLEASE EXPLAIN HOW THE
 ALTERATIONS TO THE SOUTH FIVE (5) FEET OF THE BUILDING
 WILL REDUCE THE IMPACT ON ADJACENT PROPERTIES. STAFF
 HAS NOTED THAT EXISTING WINDOW OPENINGS ON THE SOUTH
 FACADE ARE BEING CLOSED, WHICH SEEMS TO INCREASE THE
 NEGATIVE IMPACT THAT BLANK WALLS HAVE ON ADJACENT
 PROPERTIES.
  
 3) THE PARKING LOT REQUIRES A SEPARATE PARKING PERMIT.
 PLEASE NOTE THAT THE PARKING LOT AS SHOWN DOES NOT MEET
 THE CURRENTLY APPROVED PARKING LAYOUT (PLEASE SEE
 PERMIT NO. 8999G), NOR DOES IT CONFORM TO CITY PARKING
 REQUIREMENTS. PARKING COMMENTS WILL BE PROVIDED AT TIME
 OF PARKING LOT PERMIT SUBMITTAL.
  
 EXCEPT FOR THIS ISSUES LISTED ABOVE, ZONING STAFF DOES
 NOT FIND ANY ISSUES WITH THE BUILDING PLANS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  