Plan Review Details - Permit 15061093
Plan Review Stops For Permit 15061093
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-07-13 Cont ID  
Sent By jwitmer Date 2015-07-13 Time 14:03 Rev Time  
Received By jwitmer Date 2015-07-13 Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-08-04 Cont ID  
Sent By albarran Date 2015-08-04 Time 09:30 Rev Time 0.00
Received By albarran Date 2015-08-03 Time 19:29 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-06-26 Cont ID  
Sent By pleduc Date 2015-06-26 Time   Rev Time 0.00
Received By pleduc Date 2015-06-26 Time 09:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-10 Cont ID  
Sent By ccole Date 2015-08-10 Time 16:38 Rev Time 0.00
Received By ccole Date 2015-08-10 Time 15:33 Sent To  
Notes
2015-08-10 15:33:17RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-04 Cont ID  
Sent By albarran Date 2015-08-04 Time 09:33 Rev Time 0.00
Received By albarran Date 2015-06-24 Time 19:06 Sent To  
Notes
2015-08-04 09:35:338/4/15 - PASSED ELECTRICAL AND OTHER TRADE REVIEWS BUT
 PENDING MECHANICAL CORRECTIONS. CONTRACTOR NOTIFIED VIA
 EMAIL. SENT TO LARGE DENIED BIN "B". MA
2015-06-24 18:52:14SENT TO B16

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-08-10 Cont ID  
Sent By ccole Date 2015-08-10 Time 16:37 Rev Time 0.00
Received By ccole Date 2015-08-10 Time 16:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-07-09 Cont ID  
Sent By ccole Date 2015-07-09 Time 17:07 Rev Time 0.00
Received By ccole Date 2015-07-09 Time 17:07 Sent To  
Notes
2015-07-09 17:28:341ST REVIEW: FBC 2010 MECHANICAL
 PERMIT #15061093 7/9/15
  
 1) PROVIDE ADDITIONAL FIRE DAMPER SPECIFICATIONS-
 TYPES, FIRE RATINGS, AND HOW THEY WILL BE ACTUATED- SEE
 SECTION 607, AND SUBMIT MANUFACTURER'S SPECIFICATIONS
 REVIEWED AND APPROVED BY THE ENGINEER OF RECORD.
 2) PROVIDE ADDITIONAL DETAILS AND NOTES TO CLARIFY
 WHERE THE RETURN AIR THROUGH THE 48X12 GRILL IS BEING
 TRANSFERRED TO- ABOVE THE CORRIDOR CEILING INTO A RATED
 PLENUM ENCLOSURE?
 3) AS NOTED ON SHEET M1.1, PLEASE SHOW WHERE THE
 EXPOSED SPIRAL DUCTWORK IS TO BE INSTALLED IN THE
 SPACE: THE LAYOUT PLAN APPEARS TO INDICATE ALL ABOVE
 CEILING INSTALLATIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-07-20 Cont ID  
Sent By gjohnson Date 2015-07-20 Time 16:46 Rev Time 0.00
Received By gjohnson Date 2015-07-20 Time 16:45 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-06-29 Cont ID  
Sent By ajones Date 2015-06-29 Time 13:51 Rev Time 0.00
Received By ajones Date 2015-06-29 Time 13:51 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved