| Plan Review Stops For Permit 15061052 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2015-06-29 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-06-29 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-06-29 |
Time |
15:00 |
Sent To |
I |
|
| Notes |
| 2015-06-29 15:14:24 | PER A TELEPHONE CONVERSATION WITH THE ELECTRICAL | | | CONTRACTOR, THE SCOPE OF THIS PERMIT IS TO RUN TWO NEW | | | CIRCUITS INSIDE AN EXISTING RACEWAY FOR THE TWO NEW | | | REFRIGERATORS. THESE TWO CIRCUITS WILL EACH HAVE A | | | DEDICATED NEUTRAL OR COMPLY WITH NEC 210.4. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-06-29 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-06-29 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-06-25 |
Time |
13:13 |
Sent To |
|
|
| Notes |
| 2015-06-29 15:17:33 | 6/29/15 - PASSED ELECTRICAL REVIEW AS NOTED. CONTRACTOR | | | NOTIFIED VIA EMAIL SENT TO SMALL READY BIN "A". MA | | 2015-06-25 13:14:08 | ROUTED TO ELECTRICAL $5000 & UNDER |
|
|
|