Plan Review Details - Permit 15061029
| Plan Review Stops For Permit 15061029 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2015-07-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-07-16 |
Time |
08:21 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-07-16 |
Time |
08:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2015-07-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-07-14 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-07-14 |
Time |
10:40 |
Sent To |
|
|
| Notes |
| 2015-07-14 10:49:30 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE WIND UPLIFT ENHANCED FASTENING CALCULATIONS THAT | | | WERE SUBMITTED WERE DIGITALLY SIGNED BY DONALD J. | | | FLOOD. DIGITAL SIGNATURES ARE ONLY ACCEPTABLE FOR | | | ELECTRONICALLY TRANSMITTED DOCUMENTS. THESE DOCUMENTS | | | ARE PAPER AND ARE REQUIRED TO HAVE THE ENGINEER'S SEAL, | | | DATE AND ORIGINAL HAND WRITTEN SIGNATURE (FACSIMILES | | | ARE NOT ACCEPTED) ON THEM. FAC 61G15-23.002 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2015-06-25 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-06-25 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-06-25 |
Time |
07:46 |
Sent To |
|
|
| Notes |
| 2015-06-25 09:53:47 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE WIND UPLIFT ENHANCED FASTENING CALCULATIONS | | | SPECIFY PRODUCT APPROVAL FL14083-R7 SYSTEM NUMBER | | | SC-104 ON PAGE 16 OF 17. THE PRODUCT APPROVAL SUBMITTED | | | WAS FL14083-R8 AND SYSTEM NUMBER SC-116 ON PAGE 18 OF | | | 39 IS MARKED. SUBMIT MATCHING DOCUMENTS. FBC 107.2.1 | | | | | | 2) THE PRODUCT APPROVAL FOR A BILCO ROOF HATCH WITH A | | | DESIGN PRESSURE OF + OR - 70 PSF WAS SUBMITTED. PROVIDE | | | A ROOF PLAN THAT SHOWS THE LOCATION OF THE HATCH. BASED | | | ON THE ENGINEER'S ROOF FASTENING DOCUMENT AND THE | | | DESIGN PRESSURES FOR THIS HATCH, IT WILL HAVE TO BE | | | LOCATED IN ROOF ZONE 1. | | | | | | 3) CLARIFY THAT THE NEW BILCO HATCH IS THE REPLACEMENT | | | OF AN EXISTING ONE, WHICH CAN BE DONE WITH A CCC | | | LICENSE. OTHERWISE A GENERAL OR BUILDING CONTRACTOR | | | WILL BE REQUIRED TO INSTALL THE HATCH. FS 489.105(E) |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2015-07-16 |
Time |
|
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2015-07-14 |
Time |
08:49 |
Sent To |
|
|
| Notes |
| 2015-07-15 08:49:31 | MCDOUGAL'S DESK |
|
|
|