Plan Review Details - Permit 15061029
Plan Review Stops For Permit 15061029
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-07-16 Cont ID  
Sent By rmcdouga Date 2015-07-16 Time 08:21 Rev Time 0.00
Received By rmcdouga Date 2015-07-16 Time 08:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-07-14 Cont ID  
Sent By rmcdouga Date 2015-07-14 Time 10:40 Rev Time 0.00
Received By rmcdouga Date 2015-07-14 Time 10:40 Sent To  
Notes
2015-07-14 10:49:30PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE WIND UPLIFT ENHANCED FASTENING CALCULATIONS THAT
 WERE SUBMITTED WERE DIGITALLY SIGNED BY DONALD J.
 FLOOD. DIGITAL SIGNATURES ARE ONLY ACCEPTABLE FOR
 ELECTRONICALLY TRANSMITTED DOCUMENTS. THESE DOCUMENTS
 ARE PAPER AND ARE REQUIRED TO HAVE THE ENGINEER'S SEAL,
 DATE AND ORIGINAL HAND WRITTEN SIGNATURE (FACSIMILES
 ARE NOT ACCEPTED) ON THEM. FAC 61G15-23.002

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-25 Cont ID  
Sent By rmcdouga Date 2015-06-25 Time 11:04 Rev Time 0.00
Received By rmcdouga Date 2015-06-25 Time 07:46 Sent To  
Notes
2015-06-25 09:53:47PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE WIND UPLIFT ENHANCED FASTENING CALCULATIONS
 SPECIFY PRODUCT APPROVAL FL14083-R7 SYSTEM NUMBER
 SC-104 ON PAGE 16 OF 17. THE PRODUCT APPROVAL SUBMITTED
 WAS FL14083-R8 AND SYSTEM NUMBER SC-116 ON PAGE 18 OF
 39 IS MARKED. SUBMIT MATCHING DOCUMENTS. FBC 107.2.1
  
 2) THE PRODUCT APPROVAL FOR A BILCO ROOF HATCH WITH A
 DESIGN PRESSURE OF + OR - 70 PSF WAS SUBMITTED. PROVIDE
 A ROOF PLAN THAT SHOWS THE LOCATION OF THE HATCH. BASED
 ON THE ENGINEER'S ROOF FASTENING DOCUMENT AND THE
 DESIGN PRESSURES FOR THIS HATCH, IT WILL HAVE TO BE
 LOCATED IN ROOF ZONE 1.
  
 3) CLARIFY THAT THE NEW BILCO HATCH IS THE REPLACEMENT
 OF AN EXISTING ONE, WHICH CAN BE DONE WITH A CCC
 LICENSE. OTHERWISE A GENERAL OR BUILDING CONTRACTOR
 WILL BE REQUIRED TO INSTALL THE HATCH. FS 489.105(E)

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2015-07-16 Time   Rev Time 0.00
Received By cpuell Date 2015-07-14 Time 08:49 Sent To  
Notes
2015-07-15 08:49:31MCDOUGAL'S DESK