Plan Review Details - Permit 15061025
Plan Review Stops For Permit 15061025
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-09-21 Cont ID  
Sent By jwitmer Date 2015-09-21 Time 12:30 Rev Time 0.00
Received By jwitmer Date 2015-09-21 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-27 Cont ID  
Sent By jwitmer Date 2015-06-27 Time 14:44 Rev Time  
Received By jwitmer Date 2015-06-27 Time 14:15 Sent To  
Notes
2015-06-27 14:44:20BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15061025
 ADD: 222 LAKEVIEW AVE. SUITE # 150
 CONT: HOLT LEE
 TEL: ( 954)725-4881
 E-MAIL: ????????
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. JUNE 27/2015
 ACTION: DENIED
  
 1) SHEET A3.1 SHOWS DETAILS OF A NEW STOREFRONT SYSTEM
 WITH POSSIBLE FIELD WEILDING. PLEASE IF THE HEADER TBE
 STEEL IS WELDED AT THE JOBSITE THE WELDERS
 CERTIFICATIONS WILL BE REQUIRED AT TIME OF FRAMING
 INSPECTION. 107.2.1.3 ADITIONAL INFORMATION IS
 REQUIRED.
  
 2) SHEET A3.1 THE DETAILS SHOW NEW STOREFRONT DOORAND
 SIDELIGHT FRAMING SYSTEM, THIS APPEARS TO BE THE
 EXTERIOR OF THE BUILDING.
 PLEASE PROVIDE THE WIND DESIGN CRITERIA FOR THIS INFILL
 FRAMING SYSTEM. 2010 FBC-B 1609.1.1 DETERMINATION OF
 WIND DESIGN- CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
  
 2.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 2.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 2.AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10 EXPOSURE D
  
 2.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
 HIGH-RISE BLDG.
  
 2.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2).
  
 3) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) STOREFRONTS
  
 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5A) SHEET A1.1 FUTURE STAGE BY OTHERS, PLEASE PROVIDE A
 LIFE SAFETY PLAN SHOWING CHAIR LAYOUT AND ACCESS
 AISLES. SHOW COMPLIANCE WITH 2010 FBC-B 1028.6.
  
 5B) PLEASE ALSO SHOW COMPLIANCE WITH FBC-B 1028.8 A
 COMMON PATH OF TRAVEL SHALL BE PERMITTED FOR TH 20 FEET
 FROM ANY POINT WHERE SERVING ANY NUMBER OF OCCUPANTS
 AND FOR THE FIRST 75 FEET FROM ANY POINT WHERE SERVING
 NOT MORE THAN 50 OCUPANTS.
  
 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-09-29 Cont ID  
Sent By albarran Date 2015-09-29 Time 09:06 Rev Time 0.00
Received By albarran Date 2015-09-29 Time 08:37 Sent To I
Notes
2015-09-29 09:04:369/29/15 ALL PREVIOUSLY MENTIONED ELECTRICAL ISSUES HAVE
 BEEN SATISFACTORILY ADDRESSED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-09-17 Cont ID  
Sent By albarran Date 2015-09-17 Time 16:20 Rev Time 0.00
Received By albarran Date 2015-09-17 Time 15:07 Sent To B
Notes
2015-09-17 16:21:45PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 1. NEC 210.62 REQUIRES AT LEAST ONE RECEPTACLE OUTLET
 INSTALLED WITHIN 18? OF THE TOP OF A SHOW WINDOW FOR
 EVERY 12 LINEAR FOOT OR PORTION THEREOF.
 2. NEC 600.5 REQUIRES THAT EVERY COMMERCIAL OCCUPANCY
 BE PROVIDED AT EACH PEDESTRIAN ENTRANCE TO THE SPACE A
 20 AMP DEDICATED OUTLET FOR SIGNAGE OR OUTLINE LIGHTING
 PROVISIONS.
 3. NEC 210.63 REQUIRES THAT THERE BE A 125 V 15 -20 AMP
 SERVICE OUTLET WITHIN 25? OF THE HVAC EQUIPMENT.
 4. DESCRIBE AND PROVIDE SPEC SHEETS FOR THE
 APPARATUS/EQUIPMENT BEING CONNECTED TO THE PROPOSED 100
 AMP 3? LOAD.
 5. THE NOTES INCORRECTLY INDICATE THAT THE WORK SHALL
 BE AS PER THE 2007 FBC. THE CODE IN EFFECT FOR THIS
 PROJECT IS THE 2010 EDITION OF THE FBC.
 6. ALL FIRE ALARM WORK SHALL BE PERFORMED UNDER A
 SEPARATE PERMIT AND SHOP DRAWINGS.
 7. TEMP POWER FOR CONSTRUCTION SHALL REQUIRE A SEPARATE
 PERMIT.
  
 THOUGH THE MEP NARRATIVES WERE NOT AVAILABLE, THE ABOVE
 ITEMS NEED TO BE ADDRESSED FOR A SATISFACTORY
 ELECTRICAL REVIEW.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-06-24 Cont ID  
Sent By dhayes Date 2015-06-24 Time 16:48 Rev Time 0.00
Received By dhayes Date 2015-06-24 Time 16:48 Sent To  
Notes
2015-06-24 16:57:596/24/2015
 PROJECT: AIM SUITE 150
 PERMIT#: 15061025
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) INDICATE THE SPECIFIC USE AND CONNECTION OF THE NEW
 100AMP 3PHASE 100AMP CIRCUIT . THE RISER DIAGRAM
 INDICATES A NEW DISCONNECT THEN CALLS OUT TO VERIFY
 FINAL CONNECTION TO EQUIPMENT. THE FLOOR PLAN INDICATES
 THE NEW 100AMP 3PHASE DISCONNECT CONNECTED TO A
 RECEPTACLE SYMBOL. PLEASE CLARIFY AND AND INDICATE WHAT
 EQUIPMENT THE NEW CIRCUIT IS FOR AND THE METHODS AND
 MATERIALS USED FOR THE FIANL CONNECTION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-06-26 Cont ID  
Sent By pleduc Date 2015-06-26 Time   Rev Time 0.00
Received By pleduc Date 2015-06-26 Time 10:05 Sent To  
Notes
2015-06-26 10:15:34THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 PROVIDE FIRE EXTIGUISHERS PER NFPA 10
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-09-29 Cont ID  
Sent By albarran Date 2015-09-29 Time 09:04 Rev Time 0.00
Received By albarran Date 2015-09-28 Time 10:19 Sent To  
Notes
2015-09-29 09:06:299/29/15 ALL TRADE REVIEWS HAVE BEEN APPROVED BUT IMPACT
 FEES ARE STILL PENDING PAYMENT. CONTRACTOR NOTIFIED VIA
 EMAIL. SENT TO LARGE DENIED BIN "H"> MA

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-21 Cont ID  
Sent By jwitmer Date 2015-09-21 Time 12:30 Rev Time 0.00
Received By jwitmer Date 2015-09-14 Time 13:57 Sent To  
Notes
2015-09-14 13:58:11RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-20 Cont ID  
Sent By tklarge Date 2015-07-20 Time 09:30 Rev Time  
Received By tklarge Date 2015-06-23 Time   Sent To  
Notes
2015-06-24 16:48:10B09

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2015-10-02 Cont ID  
Sent By jwitmer Date 2015-10-02 Time 16:39 Rev Time 0.00
Received By jwitmer Date 2015-10-02 Time 13:19 Sent To  
Notes
2015-10-02 13:19:09ON JWITMER'S DESK

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-06-27 Cont ID  
Sent By jwitmer Date 2015-06-27 Time 14:44 Rev Time  
Received By jwitmer Date 2015-06-27 Time   Sent To  
Notes
2015-06-27 14:45:00BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-09-15 Cont ID  
Sent By ccole Date 2015-09-15 Time 10:01 Rev Time 0.00
Received By ccole Date 2015-09-15 Time 10:01 Sent To  
Notes
2015-09-15 10:05:25PERMIT #15061025
 9/15/15
 MECHANICAL PROVISO:
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE DUCTSOX SHALL BE ON-SITE AT TIME
 OF INSPECTION.
 THERE ARE MANUFACTURER'S SPECS AND UL CERTIFICATIONS IN
 THE PERMIT FILE FOR THE TWO PRODUCTS SPECIFIED ON SHEET
 M2.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-07-16 Cont ID  
Sent By ccole Date 2015-07-16 Time 08:13 Rev Time 0.00
Received By ccole Date 2015-07-16 Time 08:02 Sent To  
Notes
2015-07-16 08:18:092ND REVIEW: FBC-10 MECHANICAL
 7/16/15
  
 1) PROVIDE PROTECTION FROM VEHICULAR DAMAGE FOR THE
 CONDENSERS LOCATED IN THE PARKING GARAGE- SECTION
 303.4.

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-07-20 Cont ID  
Sent By tklarge Date 2015-07-20 Time 09:29 Rev Time 0.00
Received By tklarge Date 2015-07-20 Time 09:11 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-07-16 Cont ID  
Sent By aponte Date 2015-07-16 Time 14:52 Rev Time 0.00
Received By aaponte Date 2015-07-16 Time 14:47 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved