| | PROJECT: ORBIT LABS |
| | PERMIT#: 15061012 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | 1) NEC 230.2 |
| | A BUILDING OR OTHER STRUCTURE SERVED SHALL BE SUPPLIED |
| | BY ONLY ONE SERVICE. PROVIDE REVISED ELECTRICAL RISER |
| | DIAGRAM FOR ONE SERVICE THAT SUPPORTS THE TOTAL |
| | CONNECTED LOAD OF THE ENTIRE BUILDING. |
| | |
| | 2) NEC 225.34 (A) |
| | THE TWO TO SIX DISCONNECTS AS PERMITTED IN 225.33 SHALL |
| | BE GROUPED. EACH DISCONNECT SHALL BE MARKED TO INDICATE |
| | THE LOAD SERVED. |
| | |
| | 3) NEC 220.16 |
| | PROVIDE A COMPLETE ELECTRICAL LOAD SUMMARY CALCULATION. |
| | |
| | 4) NEC 110.16. |
| | PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR |
| | THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. |
| | |
| | 5) NEC 110.9 |
| | VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS HAS A |
| | FAULT CURRENT RATING THAT IS SUFFICIENT AT NOMINAL |
| | CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| | INTERRUPTED. |
| | |
| | 6) WPB AMENDMENTS TO FBC 107.2.1 |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 7) WPB AMENDMENTS TO FBC 107.2.1.4 |
| | BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH |
| | SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE |
| | MEDIUM. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |