Plan Review Details - Permit 15061009
Plan Review Stops For Permit 15061009
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-09-28 Cont ID  
Sent By shill Date 2015-09-28 Time 14:41 Rev Time 0.00
Received By shill Date 2015-09-28 Time 14:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-07-27 Cont ID  
Sent By shill Date 2015-07-27 Time 18:30 Rev Time 0.00
Received By shill Date 2015-07-27 Time 18:30 Sent To ENG
Notes
2015-07-27 18:31:47****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
  
 1. PROVIDE A LEGIBLE PLAN TO PROVIDE THE FOLLOWING
 INFORMATION:
  
 TOTAL NUMBER OF PARKING SPACES
 NUMBER OF ACCESSIBLE SPACES
 LOCATION OF ACCESSIBLE ENTRANCES
 LOCATION OF ACCESSIBLE SPACES AND ACCESS AISLES
 SHOW ACCESSIBLE ROUTE FROM PUBLIC WAY
 ACCESSIBLE ROUTE FROM ACCESSIBLE SPACE TO ACCESSIBLE
 ENTRANCE
  
 SEE FBC 2010 ACCESSIBLITY 202.3 (ALTERATIONS), 208.2
 (PARKING SPACES), 502 (PARKING SPACES), 206 (ACCESSIBLE
 ROUTE).
  
 YOU MAY FIND THE FOLLOWING DOCUMENT USEFUL,
 PARTICULARLY THE INTRODUCTION: "WHEN A BUSINESS
 RESTRIPES A PARKING LOT, IT MUST PROVIDE ACCESSIBLE
 PARKING SPACES AS REQUIRED BY THE ADA STANDARDS FOR
 ACCESSIBLE DESIGN."
  
 HTTP://WWW.ADA.GOV/RESTRIPE.HTM
  
 2. FBC 2010 ACCESSIBILITY ADVISORY 502.3, WHERE THE
 ACCESSIBLE ROUTE MUST CROSS VEHICULAR TRAFFIC LANES,
 MARKED CROSSINGS ENHANCE PEDESTRIAN SAFETY; PLEASE
 INDICATE LOCATION ON PLAN.
  
 3. THE INDIVIDUAL TAKING RESPONSIBILITY SHALL PROVIDE
 THEIR PRINTED NAME AND SIGNATURE ON THE PLAN, FBC 107.
  
 4. FBC 2010 ACCESSIBILITY 208.2.1, THE FOLLOWING USES
 HAVE ADDITIONAL PARKING REQUIREMENTS:
  
 HOSPITAL OUTPATIENT FACILITES
 REHABILITATION FACILITIES
 OUTPATIENT PHYSICAL THERAPY FACILITIES
  
 PLAN IS TO EITHER SHOW LOCATION OF TENANTS WITH ANY OF
 THE ABOVE USES OR PLAN IS TO INCLUDE A STATEMENT WHICH
 STATES THAT NONE OF THE ABOVE USES (HOSPITAL OUTPATIENT
 FACILITIES, REHABILITATION FACILITIES, OUTPATIENT
 PHYSICAL THERAPY FACILITIES) ARE AT THIS LOCATION.
  
 5. PROVIDE A SPECIFICATION FOR THE ASPHALT (THICKNESS),
 FBC 107.
  
 6. PROVIDE A VERIFIABLE COPY OF THE CONTRACT FOR THIS
 JOB, FBC 109.
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2015-09-25 Cont ID  
Sent By cranford Date 2015-09-25 Time 10:39 Rev Time 0.00
Received By cranford Date 2015-09-25 Time 10:36 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2015-08-03 Cont ID  
Sent By cranford Date 2015-08-03 Time 13:49 Rev Time 0.00
Received By cranford Date 2015-08-03 Time 13:31 Sent To I
Notes
2015-08-03 13:51:12PLEASE SUBMIT STRIPING PLAN MATCHING PREVIOUS SITE PLAN
 APPROVAL ISPR 08-06 (Z0811022)
  
 KELLY CRANFORD, P.E.
 LAND DEVELOPMENT ENGINEER
 PUBLIC WORKS DEPARTMENT
 CITY OF WEST PALM BEACH
 [email protected]
 561-494-1098 (OFFICE)

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-28 Cont ID  
Sent By shill Date 2015-09-28 Time 14:41 Rev Time 0.00
Received By shill Date 2015-09-15 Time 11:58 Sent To  
Notes
2015-09-15 11:59:00ROUTED TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-03 Cont ID  
Sent By cranford Date 2015-08-03 Time 13:51 Rev Time 0.00
Received By cranford Date 2015-06-23 Time   Sent To Z
Notes
2015-07-27 18:32:077/27 TO ENGINEERING
  

Review Stop Z ZONING
Rev No 2 Status P Date 2015-09-16 Cont ID  
Sent By sgraham Date 2015-09-16 Time 11:11 Rev Time 0.00
Received By sgraham Date 2015-09-16 Time 11:11 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2015-06-25 Cont ID  
Sent By cranford Date 2015-08-03 Time 13:51 Rev Time 0.00
Received By sgraham Date 2015-06-25 Time 11:31 Sent To B
Notes
2015-06-25 11:32:246/25/15 ZONING FAILED
  
 1. SUBMIT A PLAN SHOWING THE PARKING LAYOUT, PARKING
 LOT MUST BE DOUBLE STRIPPED.