Plan Review Details - Permit 15060981
Plan Review Stops For Permit 15060981
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-11-24 Cont ID  
Sent By jwitmer Date 2015-11-24 Time 06:46 Rev Time 0.00
Received By jwitmer Date 2015-11-16 Time 06:02 Sent To  
Notes
2015-11-16 07:28:48BUILDING PLAN REVIEW
 REVISION: 15060981
 W. P. B. PERMIT: 14050111
 ADD: 600 OKEECHOBEE BLVD
 CONT: N R WINDOWS/ COASTAL
 TEL: (561)844-1121: ELEANOR CASTELLANOS
 E-MAIL:
  
  
  
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 4THREVIEW
  
 DATE: MON. NOV. 16/ 2015
 ACTION: PROVISO
  
 THE FRONT ENTRY DOORS TO BE A BREAK-AWAY AS PER NOA
 13-0521.14 PAGE 16/21 WHICH SHOWS A HORIZONTAL MIDRAIL.
 THE LOCKING DEVICE IN THE DOOR CURRENTLY HAS TO BE
 REMOVED AND NEVER PUT BACK IN THE DOOR. THE OCCUPANT
 LOAD OF THE ROOMS THESE DOORS SERVE IS GREATER THAN 300
 THE 2010 FBC-B 1008.1.9.3(2) LOCKS AND LATCHES ALLOWING
 LOCKING DEVICE IN ASSMEBLY OCCUPANCY DOORS IS WHEN THE
 OCCUPANT LOAD IS 300 OR LESS. THE OCCUPANT LOAD FOR
 THIS ASSEMBLY OCCUAPANCY IS WELL OVER 300. NO LOCKING
 DEVICES IN THESE DOORS.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-10-19 Cont ID  
Sent By jwitmer Date 2015-10-19 Time 11:21 Rev Time 0.00
Received By jwitmer Date 2015-10-19 Time 09:53 Sent To  
Notes
2015-10-19 11:26:01BUILDING PLAN REVIEW
 REVISION: 15060981
 W. P. B. PERMIT: 14050111
 ADD: 600 OKEECHOBEE BLVD
 CONT: N R WINDOWS/ COASTAL
 TEL: (561)844-1121: ELEANOR CASTELLANOS
 E-MAIL:
  
  
  
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 3RD REVIEW
 DATE: MON. OCT. 19/ 2015
 ACTION: DENIED
  
 1) COMPLIED. THIS REVISION IS ONLY THE SHOP DRAWINGS,
 PLEASE PROVIDE THE ARCHITECTURAL SHEETS TO REFLECT ON
 THE RECORD SET OF DRAWINGS THIS CHANGE.
  
 2) THE NR FLOOR PLAN PO1 DOES NOT INDICATE A REVISION
 TAKING PLACE WITH A NUMBERED DELTA SHOWING THE REVISION
 LOCATION. NEITHER DOES THE NARRATIVE, THE NARRATIVE IS
 DATED MARCH 16/2015 BEFORE THIS REVISION WAS SUBMITTED.
 IT IS NOT A RESPONSE TO THE FIRST SET OF COMMENTS.
 PLEASE REMEMBER WE LOOK FOR A COMPLETE PAPER TRAIL, YES
 UNLESS YOU GIVE US THE ACTUAL NOA, NUMBER AND SHEET
 NUMBER WHERE THIS INFORMATION CAN BE FOUND WE ARE NOT
 GOING TO LOOK THROUGH THOUSANDS OF SHEETS OF NOA'S AND
 PLANS TO FIND THE REQUIRED INFORMATION. WE REQUIRE BOTH
 THE ARCHITECTURAL SHEETS AS WELL AS NR SHOP DRAWINGS
 SHEETS TO REFLECT THE CHANGE. IDENTIFIED BY A NUMBERED
 DELTA AND A WRITTEN RESPONSE.
  
 3) COMPLIED. THE LOCATION IS CRITICAL BECAUSE THE FENCE
 AND POOL BARRIERS ARE BEING CONSIDERED TO BE REMOVED ON
 A DIFFERENT REVISION. IF THESE DOORS ARE ON THE POOL
 SIDE OF THE BUILDING THEN THE POOL BARRIER AND GATES
 WILL AGAIN BE REQUIRED, SINCE CHILDREN WOULD BE ABLE TO
 GAIN ENTRY BY WAY OF THE ACUSENSOR AND SLIDING DOOR
 SYSTEM. 2010 FBC-B 424.1.3.1.9.
  
 4) THE LOCATION OF THESE DOORS WILL NEED TO COMPLY WITH
 1008.1.10 OR ONE OF THE EXCEPTIONS. THESE DOORS DO NOT
 INDICATE THE USE OF PANIC OR FIRE EXIT HARDWARE.
 EXCEPTION 1 DOES ALLOW THE MAIN EXIT DOOR IN A A
 OCCUPANCY IF IT IS IN COMPLIANCE WITH 1008.1.9.3 ITEM
 2.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
 COMMENT FROM 1ST REVIEW.
 THIS REVISION DOES NOT SHOW ON THE DOOR SCHEDULE WHICH
 DOORS THIS DOOR AFFECTS AND ON THE OCCUPANT LOADS OF
 THE FLOOR PLAN. THE 2010
 FBC-B 1008.1.10 REQUIRES EITHER PANIC OR FIRE EXIT
 HARDWARE ON ALL DOORS SERVING AN ASSEMBLY OCCUPANCY
 WITH AN OCCUPANT LOAD OF 50 OR MORE. ADDITIONAL
 INFORMATION IS REQUIRED. 107.2.1.3.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-09-02 Cont ID  
Sent By   Date 2015-09-02 Time 12:29 Rev Time 0.00
Received By jwitmer Date 2015-09-02 Time 11:08 Sent To  
Notes
2015-09-02 12:00:56BUILDING PLAN REVIEW
 REVISION: 15060981
 W. P. B. PERMIT: 14050111
 ADD: 600 OKEECHOBEE BLVD
 CONT: N R WINDOWS/ COASTAL
 TEL: (
 E-MAIL:
  
  
 NOTICE!!!!!!!!!!!!!!!!!!!!!: CHAPTER 553.80(2)(B)
 FLORIDA STATUTES STATES THAT A LOCAL GOVERNMENT SHALL
 IMPOSE A FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF
 PLANS ARE REJECTED (3) OR MORE TIMES FOR REPEATED
 FAILURE TO CORRECT A CODE VIOLATION.
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: WED. SEPT. 02/ 2015
 ACTION: DENIED
  
 1) THIS REVISION IS ONLY THE SHOP DRAWINGS, PLEASE
 PROVIDE THE ARCHITECTURAL SHEETS TO REFLECT ON THE
 RECORD SET OF DRAWINGS THIS CHANGE.
  
 2) THE NR FLOOR PLAN PO1 DOES NOT INDICATE A REVISION
 TAKING PLACE WITH A NUMBERED DELTA SHOWING THE REVISION
 LOCATION. NEITHER DOES THE NARRATIVE, THE NARRATIVE IS
 DATED MARCH 16/2015 BEFORE THIS REVISION WAS SUBMITTED.
 IT IS NOT A RESPONSE TO THE FIRST SET OF COMMENTS.
 PLEASE REMEMBER WE LOOK FOR A COMPLETE PAPER TRAIL, YES
 UNLESS YOU GIVE US THE ACTUAL NOA, NUMBER AND SHEET
 NUMBER WHERE THIS INFORMATION CAN BE FOUND WE ARE NOT
 GOING TO LOOK THROUGH THOUSANDS OF SHEETS OF NOA'S AND
 PLANS TO FIND THE REQUIRED INFORMATION. WE REQUIRE BOTH
 THE ARCHITECTURAL SHEETS AS WELL AS NR SHOP DRAWINGS
 SHEETS TO REFLECT THE CHANGE. IDENTIFIED BY A NUMBERED
 DELTA AND A WRITTEN RESPONSE.
  
 3) THE LOCATION IS CRITICAL BECAUSE THE FENCE AND POOL
 BARRIERS ARE BEING CONSIDERED TO BE REMOVED ON A
 DIFFERENT REVISION. IF THESE DOORS ARE ON THE POOL SIDE
 OF THE BUILDING THEN THE POOL BARRIER AND GATES WILL
 AGAIN BE REQUIRED, SINCE CHILDREN WOULD BE ABLE TO GAIN
 ENTRY BY WAY OF THE ACUSENSOR AND SLIDING DOOR SYSTEM.
 2010 FBC-B 424.1.3.1.9.
  
 4) THE LOCATION OF THESE DOORS WILL NEED TO COMPLY WITH
 1008.1.10 OR ONE OF THE EXCEPTIONS. THESE DOORS DO NOT
 INDICATE THE USE OF PANIC OR FIRE EXIT HARDWARE.
 EXCEPTION 1 DOES ALLOW THE MAIN EXIT DOOR IN A A
 OCCUPANCY IF IT IS IN COMPLIANCE WITH 1008.1.9.3 ITEM
 2.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
  
  
  
  
  
  
 COMMENT FROM 1ST REVIEW.
 THIS REVISION DOES NOT SHOW ON THE DOOR SCHEDULE WHICH
 DOORS THIS DOOR AFFECTS AND ON THE OCCUPANT LOADS OF
 THE FLOOR PLAN. THE 2010
 FBC-B 1008.1.10 REQUIRES EITHER PANIC OR FIRE EXIT
 HARDWARE ON ALL DOORS SERVING AN ASSEMBLY OCCUPANCY
 WITH AN OCCUPANT LOAD OF 50 OR MORE. ADDITIONAL
 INFORMATION IS REQUIRED. 107.2.1.3.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-04 Cont ID  
Sent By jwitmer Date 2015-08-04 Time 16:10 Rev Time  
Received By jwitmer Date 2015-08-04 Time   Sent To  
Notes
2015-08-04 16:10:12BUILDING PLAN REVIEW
 REVISION: 15060981
 W. P. B. PERMIT: 14050111
 ADD: 600 OKEECHOBEE BLVD
 CONT: N R WINDOWS/ COASTAL
 TEL: (
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: TUES. AUGUST 04/ 2015
 ACTION: DENIED
  
 1) THIS REVISION DOES NOT SHOW ON THE DOOR SCHEDULE
 WHICH DOORS THIS DOOR AFFECTS AND ON THE OCCUPANT LOADS
 OF THE FLOOR PLAN. THE 2010
 FBC-B 1008.1.10 REQUIRES EITHER PANIC OR FIRE EXIT
 HARDWARE ON ALL DOORS SERVING AN ASSEMBLY OCCUPANCY
 WITH AN OCCUPANT LOAD OF 50 OR MORE. ADDITIONAL
 INFORMATION IS REQUIRED. 107.2.1.3.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2015-11-20 Cont ID  
Sent By wjolin Date 2015-11-20 Time 11:17 Rev Time 0.00
Received By wjolin Date 2015-11-20 Time 11:16 Sent To  
Notes
2015-11-20 11:17:33ALL LOCKS AND LATCHES TO BE REMOVED FROM DOORS IF
 LISTED PANIC HARDWARE IS NOT INSTALLED ON DOORS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2015-10-21 Cont ID  
Sent By wjolin Date 2015-10-21 Time 11:43 Rev Time 0.00
Received By wjolin Date 2015-10-21 Time 10:56 Sent To  
Notes
2015-10-21 11:40:08600 OKEECHOBEE BOULEVARD
 TRACKING #15060981
 MASTER #15010064
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DOORS IN AN ASSEMBLY OCCUPANCY EQUIPPED WITH A LOCK OR
 LATCH ARE REQUIRED TO HAVE THE LOCK/LATCH BE RELEASED
 BY PANIC HARDWARE. PLEASE INDICATE THE DOORS ARE TO BE
 EQUIPPED WITH LISTED PANIC HARDWARE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2015-09-10 Cont ID  
Sent By wjolin Date 2015-09-10 Time 15:01 Rev Time 0.00
Received By wjolin Date 2015-09-10 Time 15:01 Sent To  
Notes
2015-09-10 15:03:13600 OKEECHOBEE BOULEVARD
 TRACKING #15060981
 MASTER #15010064
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DOORS DO NOT APPEAR TO BE EQUIPPED WITH PANIC HARDWARE.
 NO OTHER LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT
 BE RELEASED BY THE PANIC HARDWARE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-08-05 Cont ID  
Sent By wjolin Date 2015-08-05 Time 14:07 Rev Time 0.00
Received By wjolin Date 2015-08-05 Time 13:50 Sent To  
Notes
2015-08-05 14:06:57600 OKEECHOBEE BOULEVARD
 TRACKING #15060981
 MASTER #15010064
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLANS DO NOT INDICATE WHERE THE SLIDING GLASS DOORS ARE
 TO BE INSTALLED. PROVIDE FLOOR PLAN AND OCCUPANT LOAD
 ASSOCIATED WITH EGRESS.
  
 DOOR INDICATES THE USE OF A THUMB-TURN STYLE LOCK. HOW
 WILL THIS AFFECT EGRESS?
  
 INSTALLATION SHALL CONFORM TO NFPA 101 SECTION
 7.2.1.9.1.2 WHEREBY THE DOOR ASSEMBLY SHALL BE DESIGNED
 AND INSTALLED SO THAT, WHEN A FORCE IS APPLIED TO THE
 DOOR LEAF ON THE SIDE FROM WHICH EGRESS IS MADE, IT
 SHALL BE CAPABLE OF SWINGING FROM ANY POSITION TO
 PROVIDE FULL USE OF THE REQUIRED WIDTH OF THE OPENING
 IN WHICH IT IS INSTALLED. (SEE 7.2.1.4.)
 A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN. (25 MM) HIGH ON A CONTRASTING BACKGROUND
 THAT READS AS FOLLOWS SHALL BE LOCATED ON THE EGRESS
 SIDE OF EACH DOOR OPENING: IN EMERGENCY, PUSH TO OPEN
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-11-24 Cont ID  
Sent By jwitmer Date 2015-11-24 Time 06:46 Rev Time 0.00
Received By jwitmer Date 2015-11-16 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-10-21 Cont ID  
Sent By cpuell Date 2015-10-21 Time 11:50 Rev Time 0.00
Received By cpuell Date 2015-10-02 Time 11:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-18 Cont ID  
Sent By lmarchan Date 2015-09-10 Time 14:52 Rev Time 0.00
Received By lmarchan Date 2015-08-19 Time 16:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-06 Cont ID  
Sent By cpuell Date 2015-08-06 Time 12:55 Rev Time 0.00
Received By cpuell Date 2015-07-07 Time 12:43 Sent To  
Notes
***NONE***