Plan Review Details - Permit 15060957
Plan Review Stops For Permit 15060957
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-09-21 Cont ID  
Sent By rmcdouga Date 2015-09-21 Time 17:10 Rev Time 0.00
Received By rmcdouga Date 2015-09-21 Time 17:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-10 Cont ID  
Sent By rmcdouga Date 2015-08-10 Time 19:06 Rev Time 0.00
Received By rmcdouga Date 2015-08-06 Time 19:00 Sent To  
Notes
2015-08-10 18:25:36PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY THE TYPE OF CONSTRUCTION AN OCCUPANCY TYPE
 ON THE PLANS. FBC 601 AND 302. SINGLE FAMILY HOMES ARE
 OCCUPANCY TYPE R-3 AND CONSTRUCTION TYPE V-B HAS THE
 LEAST RESTRICTIONS.
  
 2) SHEET SP-2 WHICH IS LISTED IN THE DRAWING LIST ON
 SP-1, IS MISSING FROM THE PLANS. FBC 107.2.1
  
 3) SUBMIT ENERGY COMPLIANCE FORMS FOR UNITS A, B AND C
 AS REQUIRED BY FBC ENERGY CONSERVATION 405.3
  
 4) THE TAG FOR THE NEWEL POST AT DETAIL D/A-5.2 SHOULD
 BE E/A-5.2 NOT E/A-15. FBC 107.2.1
  
 5) THE HANDRAIL TAG AND SECTION ON A-5.2 SHOULD BE
 3/A-5.2 NOT 3/A-15. FBC 107.2.1
  
 6) THE WINDOW SCHEDULE IN THE PLANS SPECIFIES DOUBLE
 HUNG WINDOWS AND THE PRODUCT APPROVALS (NOA NO.
 11-1013.14) THAT WERE SUBMITTED ARE FOR SINGLE HUNG
 WINDOWS. FBC 107.2.1
  
 7) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE
 FIXED WINDOWS ( NOA NO. 11-1110.15 ) EXPIRED ON
 FEBRUARY 19, 2014. DCA RULE 9N-3
  
 8) SUBMIT TWO SETS OF PRODUCT APPROVALS THAT HAVE BEEN
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD FOR THE ASPHALT SHINGLE AND METAL ROOF COVERING
 MATERIALS. FBC 107.3.4.1
  
 9) THE GUARD SPACING FOR SEVERAL OF THE PORCH RAILINGS
 ON SHEET A-5.4 DO NOT COMPLY WITH FBC-R312.3 FOR
 REQUIRED GUARDS REJECTING A 4 INCH DIAMETER SPHERE. THE
 PLANS INDICATE THAT THE PORCHES ARE LESS THAN 30 INCHES
 ABOVE GRADE, THEREFORE THE GUARDS ARE NOT REQUIRED AND
 THE SPACING OF THE RAILS ARE NOT REQUIRED TO COMPLY.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-09-16 Cont ID  
Sent By rmcdouga Date 2015-09-16 Time 17:59 Rev Time 0.00
Received By rmcdouga Date 2015-09-16 Time 17:59 Sent To  
Notes
2015-09-16 18:01:46APPROVAL IS PENDING SUBMITTAL OF RECORDED ELECTRICAL
 UTILITY EASEMENTS AND SURVEY SHOWING THEIR LOCATIONS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-08-11 Cont ID  
Sent By rmcdouga Date 2015-08-11 Time 14:18 Rev Time 0.00
Received By rmcdouga Date 2015-08-10 Time 19:06 Sent To  
Notes
2015-08-11 13:48:14PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010 / 2008 NEC
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE UNDERGROUND ELECTRICAL SERVICE LATERALS FOR THE
 TWO SINGLE FAMILY STRUCTURES LOCATED ON N STREET CAN
 NOT CROSS THROUGH THE ADJACENT PROPERTY CONTAINING THE
 TWO SINGLE FAMILY STRUCTURES LOCATED ON GEORGIA AVENUE,
 AS SHOWN ON THE ELECTRICAL SITE PLAN E-1, WITHOUT A
 RECORDED UTILITY EASEMENT. UTILITY EASEMENTS, EASEMENT
 LOCATION AND ASSOCIATED RESTRICTIVE PROPERTY COVENANTS
 ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL FOR REVIEW
 AND APPROVAL PRIOR TO RECORDING. SAID DOCUMENTS SHALL
 BE RECORDED AND PROOF OF RECORDING ON THE PLAT, AND
 ACCEPTANCE BY THE CITY SURVEYOR, SHALL BE PROVIDED.
  
 2) FBC-R314.3 SMOKE ALARMS SHALL BE INSTALLED IN THE
 FOLLOWING LOCATIONS: 3. ON EACH ADDITIONAL STORY OF THE
 DWELLING, INCLUDING BASEMENTS AND HABITABLE ATTICS BUT
 NOT INCLUDING CRAWL SPACES AND UNINHABITABLE ATTICS.
  
 3) IN ADDITION TO THE LIGHTING OUTLET SPECIFIED ON THE
 PLANS IN THE ATTIC, PROVIDE A RECEPTACLE OUTLET. FBC-R
 - M1305.1.3.1 ELECTRICAL REQUIREMENTS. A LUMINAIRE
 CONTROLLED BY A SWITCH LOCATED AT THE REQUIRED
 PASSAGEWAY OPENING AND A RECEPTACLE OUTLET SHALL BE
 INSTALLED AT OR NEAR THE APPLIANCE LOCATION IN
 ACCORDANCE WITH CHAPTER 34. SEE ALSO 2008 NEC 210.63
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2016-04-06 Cont ID  
Sent By mgonzale Date 2016-04-06 Time 14:09 Rev Time 0.00
Received By mgonzale Date 2016-04-06 Time 14:09 Sent To  
Notes
2016-04-06 14:10:08REVIEWED DRIVEWAY

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2015-07-22 Cont ID  
Sent By fmittner Date 2015-07-22 Time 17:03 Rev Time 0.00
Received By fmittner Date 2015-07-22 Time 17:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-21 Cont ID  
Sent By rmcdouga Date 2015-09-21 Time 17:10 Rev Time 0.00
Received By rmcdouga Date 2015-09-02 Time 10:58 Sent To  
Notes
2015-09-02 10:58:25RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-11 Cont ID  
Sent By rmcdouga Date 2015-08-11 Time 14:39 Rev Time 0.00
Received By rmcdouga Date 2015-06-22 Time 14:36 Sent To  
Notes
2015-06-23 14:36:24SENT TO R20 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2015-08-28 Cont ID  
Sent By rmcdouga Date 2015-08-28 Time 09:47 Rev Time 0.00
Received By rmcdouga Date 2015-08-26 Time 14:04 Sent To  
Notes
2015-08-28 09:53:24MU 2015 - 020214
2015-08-27 14:19:36RMCDOUGAL'S DESK

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-08-06 Cont ID  
Sent By rmcdouga Date 2015-08-06 Time 18:32 Rev Time 0.00
Received By rmcdouga Date 2015-08-06 Time 18:32 Sent To  
Notes
2015-08-06 18:32:46BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-09-16 Cont ID  
Sent By rmcdouga Date 2015-09-16 Time 18:52 Rev Time 0.00
Received By rmcdouga Date 2015-09-16 Time 15:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-08-07 Cont ID  
Sent By rmcdouga Date 2015-08-07 Time 08:02 Rev Time 0.00
Received By rmcdouga Date 2015-08-06 Time 18:59 Sent To  
Notes
2015-08-07 08:08:53PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
 PROVIDE TWO SETS EQUIPMENT SIZING CALCULATIONS FOR EACH
 OF THE FOUR UNITS.
  
 2) SUBMIT ENERGY CODE COMPLIANCE FORM 405 FOR UNITS A,
 B AND C AS REQUIRED BY FBC ENERGY CONSERVATION SECTION
 405.4.
  
 3) FBC-R - M1305.1.3 APPLIANCES IN ATTICS.
 ATTICS CONTAINING APPLIANCES SHALL BE PROVIDED WITH AN
 OPENING AND A CLEAR AND UNOBSTRUCTED PASSAGEWAY LARGE
 ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE, BUT
 NOT LESS THAN 30 INCHES (762 MM) HIGH AND 22 INCHES
 (559 MM) WIDE AND NOT MORE THAN 6 FEET (1829 MM) LONG
 MEASURED ALONG THE CENTERLINE OF THE PASSAGEWAY FROM
 THE OPENING TO THE APPLIANCE. THE PASSAGEWAY SHALL HAVE
 CONTINUOUS SOLID FLOORING IN ACCORDANCE WITH CHAPTER 5
 NOT LESS THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE
 SPACE AT LEAST 30 INCHES (762 MM) DEEP AND 30 INCHES
 (762 MM) WIDE SHALL BE PRESENT ALONG ALL SIDES OF THE
 APPLIANCE WHERE ACCESS IS REQUIRED. THE CLEAR ACCESS
 OPENING DIMENSIONS SHALL BE A MINIMUM OF 20 INCHES BY
 30 INCHES (508 MM BY 762 MM), AND LARGE ENOUGH TO ALLOW
 REMOVAL OF THE LARGEST APPLIANCE. M1305.1.3.1
 ELECTRICAL REQUIREMENTS.
 A LUMINAIRE CONTROLLED BY A SWITCH LOCATED AT THE
 REQUIRED PASSAGEWAY OPENING AND A RECEPTACLE OUTLET
 SHALL BE INSTALLED AT OR NEAR THE APPLIANCE LOCATION IN
 ACCORDANCE WITH CHAPTER 34.
  
 4) FBC-R - M1305.1.3.2 AIR-HANDLING UNITS.
 AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS IF THE
 FOLLOWING CONDITIONS ARE MET:
 1. THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 6 FEET (1829 MM) OF AN ATTIC ACCESS.
 2. A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT THE
 UNIT DOWN WHEN THE CONDENSATION DRAIN IS NOT WORKING
 PROPERLY.
 3. THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO
 REPLACE THE AIR HANDLER.
 4. A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL
 INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL
 CAPITALS, IN 16 POINT TYPE, WITH THE TITLE AND FIRST
 PARAGRAPH IN BOLD:
  
 NOTICE TO HOMEOWNER
  
 A PART OF YOUR AIR CONDITIONING SYSTEM, THE AIR
 HANDLER, IS LOCATED IN THE ATTIC. FOR PROPER, EFFICIENT
 AND ECONOMIC OPERATION OF THE AIR CONDITIONING SYSTEM,
 YOU MUST ENSURE THAT REGULAR MAINTENANCE IS PERFORMED.
 YOUR AIR CONDITIONING SYSTEM IS EQUIPPED WITH ONE OR
 BOTH OF THE FOLLOWING:
  
 1)A DEVICE THAT WILL ALERT YOU WHEN THE CONDENSATION
 DRAIN IS NOT WORKING PROPERLY OR
  
 2) A DEVICE THAT WILL SHUT THE SYSTEM DOWN WHEN THE
 CONDENSATION DRAIN IS NOT WORKING.
  
 TO LIMIT POTENTIAL DAMAGE TO YOUR HOME, AND TO AVOID
 DISRUPTION OF SERVICE, IT IS RECOMMENDED THAT YOU
 ENSURE PROPER WORKING ORDER OF THESE DEVICES BEFORE
 EACH SEASON OF PEAK OPERATION.
  
 5) FBC-R - M 1602.4 PROVIDE BALANCED AIR RETURN AT
 BEDROOMS. THE RETURN TRANSFER DUCTS FOR BEDROOM #2 AND
 THE MASTER BEDROOM ARE UNDER SIZED FOR UNITS D AND C.
 BEDROOM #2 HAS A 6" DIA. SUPPLY WHICH REQUIRES AN 8"
 DIA. TRANSFER DUCT . THE MASTER BEDROOM SUITE HAS (2)
 4" DIA. AND (1) 7" DIA. SUPPLY DUCTS WHICH REQUIRES A
 12" DIA. TRANSFER DUCT.
  
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-09-21 Cont ID  
Sent By tklarge Date 2015-09-21 Time 12:54 Rev Time 0.00
Received By tklarge Date 2015-09-21 Time 12:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-09-05 Cont ID  
Sent By tklarge Date 2015-09-05 Time 03:50 Rev Time 0.00
Received By tklarge Date 2015-09-05 Time 03:08 Sent To  
Notes
2015-09-05 03:43:291) PLEASE EXPLAIN HOW THE CREATION OF A MINOR LOT SPLIT
 ALLOWS THE SANITARY SEWER LINE FOR THE STRUCTURES ON N
 STREET TO CROSS THE PROPERTY FOR THE STRUCTURES ON
 GEORGIA AVENUE.IF THE MINOR LOT SPLIT SPECIFICALLY
 ALLOWS THE SANITARY SEWER LINE TO CROSS THE PROPERTY ON
 GEORGIA AVENUE PLEASE PROVIDE DOCUMENTATION THAT
 CONFIRMS IT.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-07-20 Cont ID  
Sent By tklarge Date 2015-07-20 Time 04:55 Rev Time 0.00
Received By tklarge Date 2015-07-20 Time 04:11 Sent To  
Notes
2015-07-20 04:59:061) SHT. P-0.1 IS MISSING FROM ONE SET OF PLANS. SUBMIT
 TWO COMPLETE SETS OF PLANS. WPB AMEND. TO 2010 FBC SEC.
 107.1.
 2) THE UNDERGROUND SANITARY SEWER LINES FOR THE TWO
 SINGLE FAMILY STRUCTURES LOCATED ON N STREET CANNOT
 CROSS THROUGH THE ADJACENT PROPERTY CONTAINING THE TWO
 SINGLE FAMILY STRUCTURES LOCATED ON GEORGIA AVENUE, AS
 SHOWN ON THE PLUMBING SITE PLAN, WITHOUT A RECORDED
 UTILITY EASEMENT. UTILITY EASEMENTS, EASEMENT LOCATION
 AND ASSOCIATED RESTRICTIVE PROPERTY COVENANTS ARE TO BE
 SUBMITTED TO THE BUILDING OFFICIAL FOR REVIEW AND
 APPROVAL PRIOR TO RECORDING. SAID DOCUMENTS SHALL BE
 RECORDED AND PROOF OF RECORDING ON THE PLAT, AND
 ACCEPTANCE BY THE CITY SURVEYOR, SHALL BE PROVIDED.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2015-09-16 Cont ID  
Sent By rmcdouga Date 2015-09-16 Time 15:22 Rev Time 0.00
Received By rmcdouga Date 2015-09-16 Time 15:22 Sent To  
Notes
2015-09-16 15:25:27FL 10674-R6 - OWENS CORNING ASPHALT ROOF SHINGLES

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2015-08-06 Cont ID  
Sent By rmcdouga Date 2015-08-06 Time 18:32 Rev Time 0.00
Received By rmcdouga Date 2015-08-06 Time 18:32 Sent To  
Notes
2015-08-06 18:33:36NO PRODUCT APPROVALS SUBMITTED FOR ROOFING MATERIALS.

Review Stop Z ZONING
Rev No 1 Status P Date 2015-07-22 Cont ID  
Sent By fmittner Date 2015-07-22 Time 17:03 Rev Time 0.00
Received By fmittner Date 2015-07-22 Time 17:03 Sent To  
Notes
***NONE***