Plan Review Details - Permit 15060950
Plan Review Stops For Permit 15060950
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-07-29 Cont ID  
Sent By rmcdouga Date 2015-07-29 Time 09:52 Rev Time 0.00
Received By rmcdouga Date 2015-07-28 Time 19:14 Sent To E
Notes
2015-07-29 09:53:43SEE REDLINED NOTATIONS ON PLANS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-08-27 Cont ID  
Sent By skennedy Date 2015-08-27 Time 14:45 Rev Time 0.00
Received By skennedy Date 2015-08-27 Time 14:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-08-01 Cont ID  
Sent By skennedy Date 2015-08-01 Time 14:50 Rev Time 0.00
Received By skennedy Date 2015-08-01 Time 14:50 Sent To  
Notes
2015-08-01 14:51:361ST REVIEW: FBC 2010/NEC 2008
  
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS
  
 PROVIDE FEEDER DETAILS FOR THE NEW ELECTRICAL
 PANELBOARD FOR THE POOL. NEC 215.5
  
 VERIFY THAT ALL FEEDERS FROM THE ELECTRICAL SERVICE
 SOURCE INCLUDE A FULL SIZE INSULATED COPPER EQUIPMENT
 GROUNDING CONDUCTOR SIZED IN ACCORDANCE WITH NEC
 250.22, 680.21, 680.25
  
 SHOW THE LOCATION AND SAFETY CLEARANCES REQUIRED FOR
 THE NEW PANEL BOARD SERVING THE SPA EQUIPMENT. NEC
 110.26
  
 VERIFY ALL SIGHT LIGHTING AND DECORATIVE LIGHTING IS
 GFCI PROTECTED AND LOCATED MORE THAN 5 FEET FROM THE
 POOL AND ABOVE 12 FEET. NEC 680.42, 680.22 (C),
 680.43(B)
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2015-07-14 Cont ID  
Sent By tklarge Date 2015-07-14 Time 03:40 Rev Time 0.00
Received By tklarge Date 2015-07-14 Time 03:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-09-10 Cont ID  
Sent By tklarge Date 2015-09-10 Time 08:58 Rev Time 0.00
Received By tklarge Date 2015-09-09 Time 12:51 Sent To  
Notes
2015-09-09 12:52:07RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-27 Cont ID  
Sent By skennedy Date 2015-08-27 Time 14:45 Rev Time 0.00
Received By skennedy Date 2015-08-21 Time 16:24 Sent To  
Notes
2015-08-21 16:24:51TLARGE DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-01 Cont ID  
Sent By skennedy Date 2015-08-01 Time 14:51 Rev Time 0.00
Received By skennedy Date 2015-06-22 Time 10:34 Sent To  
Notes
2015-06-23 10:35:14SENT TO ZONING SHELF FOR REVIEW. JG.

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-09-10 Cont ID  
Sent By tklarge Date 2015-09-10 Time 08:55 Rev Time 0.00
Received By tklarge Date 2015-09-10 Time 08:31 Sent To  
Notes
2015-09-10 08:55:20SEPARATE PERMIT REQUIRED FOR EXFILTRATION TRENCH
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-08-24 Cont ID  
Sent By tklarge Date 2015-08-24 Time 03:15 Rev Time 0.00
Received By tklarge Date 2015-08-24 Time 02:36 Sent To E
Notes
2015-08-24 03:15:13SHEET 4 OF 7 - NOTES ON PLAN STATE THAT THE 2" POOL
 WASTE SHALL DISCHARGE TO STORM SEWER AND THE WASTE FROM
 THE FILTER SHALL DRAIN TO THE SANITARY. CITY OF WPB
 CODE OF ORDINANCES SEC.90-126 (B) (5) & SEC.90-203
 PROHIBIT THE DISCHARGE OF POOL WATER TO THE CITY'S
 SANITARY OR STORM DRAINAGE SYSTEM. 2ND REQUEST.
 INDICATE ON THE PLANS AN ALTERNATE LOCATION FOR THE
 POOL WASTE DISCHARGE.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-07-14 Cont ID  
Sent By tklarge Date 2015-07-14 Time 03:40 Rev Time 0.00
Received By tklarge Date 2015-07-14 Time 02:12 Sent To  
Notes
2015-07-14 03:39:021) SHOW THE DISTANCE OF THE FLOOR INLETS TO THE
 ADJACENT WALLS. THE SPACING BETWEEN FLOOR INLETS AND
 ADJACENT WALLS SHALL NOT EXCEED 10 FEET PER 2010 FBC
 SEC.424.1.6.5.9.4.
 2) INDICATE ON THE PLANS THAT THE POOL RESTROOMS ARE
 UNDER A SEPARATE PERMIT.
 3) A BACKFLOW PREVENTION DEVICE IS REQUIRED AT THE
 WATER METER FOR THE BUILDING PER THE CITY OF WEST PALM
 BEACH CROSS CONNECTION MANUAL. THE MINIMUM PROTECTION
 REQUIRED AT THE METER IS A DOUBLE CHECK VALVE ASSEMBLY
 AND THE DEVICE MUST BE TESTED BY THE CITY OF WEST PALM
 BEACH UTILITIES DEPT. CONTACT STEPHEN HUNTER AT
 561-822-2242 FOR ADDITIONAL INFORMATION.
 4) AUTOMATIC CHEMICAL FEEDERS SHALL COMPLY WITH
 ANSI/NSF 50 - 2007.
 5) THE SWIMMING POOL WATER CANNOT DISCHARGE TO THE
 CITY'S STORM OR SANITARY SYSTEM PER CITY OF WPB CODE
 CODE OF ORDINANCE SEC. 90-126 (B) (5) AND SEC. 90-203.
 I SUGGEST CONTACTING MANNY GONZALEZ IN THE CITY'S
 ENGINERING DEPT. FOR FURTHER DIRECTION. HE CAN BE
 REACHED AT 561-494-1085.
 6) THE EQUIPMENT AREA SHALL BE SURROUNDED WITH A FENCE
 AT LEAST 4 FEET HIGH AND SHALL COMPLY WITH FBC
 SEC.424.1.5.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2015-06-29 Cont ID  
Sent By llouie Date 2015-06-29 Time   Rev Time 0.00
Received By llouie Date 2015-06-29 Time 11:58 Sent To P
Notes
***NONE***