Plan Review Details - Permit 15060930
Plan Review Stops For Permit 15060930
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-08-05 Cont ID  
Sent By jwitmer Date 2015-08-05 Time 11:32 Rev Time 0.00
Received By jwitmer Date 2015-08-05 Time 09:52 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-07-09 Cont ID  
Sent By jwitmer Date 2015-07-09 Time 07:29 Rev Time 0.00
Received By jwitmer Date 2015-07-09 Time 06:29 Sent To  
Notes
2015-07-09 07:22:01BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060930
 ADD: 525 S. FLAGLER DR. SUITE 7B
 CONT: CAMBRIDGE
 TEL: (561)784-3722
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JULY 09/ 2015
 ACTION: DENIED
  
 1) PLEASE REVIEW THE ARCHITECTS LETTER AND RECOMMENDED
 NOA'S LISTED IN LETTER. BOTH THE SLIDDING GLASS DOOR
 AND FIXED WINDOW ARE WIN DOOR PRODUCTS. THE SLIDDING
 GLASS DOOR NOA 12-0130.14 AND THE FIXED WINDOW NOA
 14-0916.13. THE SUBMITTED PRODUCT APPROVALS ARE
 NEITHER. IF THE NEW PRODUCT APPROVALS ARE TO BE
 INSTALLED HAVE THEM REVIEWED BY THE DESIGNER OF RECORD
 AND THE LETTER UPDATED AND SIGNED AND SEALED.
  
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2) THE LETTER FROM ARCHITECT RAYMOND CHLANDY INDICATES
 THE WIND DESIGN CRITERIA TO BE 170 VULT, EXPOSURE D,
 WIND ZONES 4 & 5 AND GLASS HEIGHT AT 80 FT. THIS
 BUILDING IS APPROXIMATELY 32 STORIES TALL AND THE
 NEGATIVE PRESSURES ARE TAKEN FROM THE ROOF LINE.
 POSITVE PRESSURES BUILD UP FROM GRADE. PLEASE REVIEW
 THE NEGATIVE PRESSURES FROM THE HEIGHT OF APPROX. 320
 FT IN HEIGHT. PRESSURES (NEGATIVE) FOR ZONE 4 ARE LOW
 AND EXTREMELY LOW FOR ZONE 5.
  
 3) ON THE SUBMITTED NOA 14-0807.18 EGS ATLANTIC
 ALUMINUM SLIDING GLASS DOORS ENGINEERING SHEETS 3 OF 8,
 THE PRESSURES ARE MEASURED ON THE PANEL WIDTH AND
 HEIGHT OF DOORS, CIRCLE BOTH, TYPE OF GLAZING, AND
 ASSOCIATED PRESSURES. ALSO NOTE ENGINEERING SHEET 2 THE
 LIMITING FACTOR IS THE SILL HEIGHT, CIRCLE SILL HEIGHT
 ALSO. TO BE REVIEWED BY THE DESIGNER OF RECORD.
  
 4) FOR THE FIXED WINDOWS NOA 12-1005.01 PGT SS 3500
 ALUMINUM STOREFRONT WAS SUBMITTED. PLEASE IDENTIFY THE
 SYSTEM TO BE INSTALLED BY TABLE, PANEL WIDTH AND
 HEIGHT.
 TYPE OF GLAZING, AND ASSOCIATED PRESSURES. TO BE
 REVIEWED BY THE DESIGNER OF RECORD.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-08-10 Cont ID  
Sent By dhayes Date 2015-08-10 Time 11:40 Rev Time 0.00
Received By dhayes Date 2015-08-10 Time 11:40 Sent To  
Notes
2015-08-10 11:43:228/10/2015
 PROJECT: KOCH RESIDENCE
 PERMIT#: 15060930
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC,
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER ONE,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN
 APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) LUMINAIRES IN CLOTHES CLOSETS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE PROVISIONS OF THE NEC 410.16(A) AND
 (B). PROVIDE A NOTE TO INDICATE COMPLIANCE.
  
 2) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-07-22 Cont ID  
Sent By dhayes Date 2015-07-22 Time 11:23 Rev Time 0.00
Received By dhayes Date 2015-07-22 Time 09:12 Sent To  
Notes
2015-07-22 11:23:097/22/2015
 PROJECT: KOCH RESIDENCE
 PERMIT#: 15060930
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC,
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER ONE,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) PROVIDE A FIXTURE SCHEDULE FOR LIGHTING FIXTURES TO
 BE INSTALLED INDICATING COMPLIANCE WITH THE NEC
 110.3(B), 410.10(D) AND FBC-ENERGY 502.3.8
  
 2) LUMINAIRES IN CLOTHES CLOSETS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE PROVISIONS OF THE NEC 410.16(A) AND
 (B). PROVIDE A NOTE TO INDICATE COMPLIANCE.
  
 3) VERIFY OR INDICATE COMPLIANCE WITH THE FBC REGARDING
 THE EXISTIANCE OR INSTALLATION OF INTERCONNECTED SMOKE
 DETECTORS. WHEN ALTERATIONS, REPAIRS, OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS.
 FBC-RESIDENTIAL 314 AND 315
  
 4) INDICATE HOW THE LIGHTING WILL BE CONTROLLLED AND
 THE LOCATION OF SWITCHES. INDICATE WHETHER SWITCHES ARE
 NEW OR EXISTING.
  
 5) INDICATE COMPLIANCE WITH THE NEC. ALL NEW GENERAL
 PURPOSE OUTLETS MUST BE TAMPER RESISTANT AND AFCI
 PROTECTED. NEC 210.12, 406.11
  
 6) PROVIDE A PANEL SCHEDULE INDICATING COMPLIANCE WITH
 THE NEC 210.11(C)(3) AND 408.4
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-06-25 Cont ID  
Sent By pleduc Date 2015-06-25 Time   Rev Time 0.00
Received By pleduc Date 2015-06-25 Time 15:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-10 Cont ID  
Sent By dhayes Date 2015-08-10 Time 11:40 Rev Time 0.00
Received By dhayes Date 2015-07-30 Time 15:51 Sent To  
Notes
2015-07-30 15:51:09ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-22 Cont ID  
Sent By dhayes Date 2015-07-22 Time 11:23 Rev Time 0.00
Received By dhayes Date 2015-06-22 Time 15:23 Sent To  
Notes
2015-06-23 15:24:07SENT TO B39 SHELF FOR REVIEW. JG.

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-07-17 Cont ID  
Sent By gjohnson Date 2015-07-17 Time 16:33 Rev Time 0.00
Received By gjohnson Date 2015-07-17 Time 16:32 Sent To  
Notes
***NONE***