| Plan Review Stops For Permit 15060795 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2015-10-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-10-08 |
Time |
06:31 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-10-08 |
Time |
05:32 |
Sent To |
|
|
| Notes |
| 2015-10-08 06:49:05 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT:15060795 | | | ADD: 1016 CLEARWATER PL. | | | CONT: SIDNEY SCHREIDELL | | | TEL: (954)214-7908 | | | E-MAIL: | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | DATE: THURS. OCT. 08/2015 | | | ACTION: BUILDING PROVISO | | | BUILDING APPROVED WITH EXCEPTION! | | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO | | | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO | | | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE | | | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE | | | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. | | | | | | 1) BLDG. # 3 CORRIDOR WITH DOORS 9 & 10, 2010 | | | FBC-ACCESSIBILITY CODE 404.2.6, DOORS IN SERIES, DOOR # | | | 9 WAS MOVED SO THERE IS NO LONGER 4 FOOT BETWEEN DOORS. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2015-07-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-07-07 |
Time |
12:29 |
Rev Time |
|
| Received By |
jwitmer |
Date |
2015-07-07 |
Time |
|
Sent To |
|
|
| Notes |
| 2015-07-07 08:06:38 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT:15060795 | | | ADD: 1016 CLEARWATER PL. | | | CONT: SIDNEY SCHREIDELL | | | TEL: (954)214-7908 | | | E-MAIL: | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: TUES. JULY 07/2015 | | | ACTION: DENIED | | | | | | 1) THE COVERSHEET: | | | 1A) THE OCCUPANCY CLASSIFICATION IS LISTED AS AN A3- | | | BUT THE PLANS INDICATE THE USAGE BEING A ANIMAL KENNEL, | | | PLEASE REVIEW 2010 FBC-B SECTION 304.1 IT APPEARS THE | | | OCCUPANCY SHOULD BE A BUSINESS OCCUPANCY. | | | | | | 1B) UNDER THE HEADING OF OCCUPANCY LOADS INDICATES AN | | | ADDITION BUT THERE IS A NOTE FURTHER DOWN THE PAGE THAT | | | THERE IS NO CHANGE OF SQUARE FOOTAGE. 2010 WEST PALM | | | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER | | | 1, ADMINISTRATION, 107.2.1.3 ADDITIONAL INFORMATION IS | | | REQUIRED. | | | | | | 1C) PLEASE NOTE THE PLANS INDICATE AN ASSEMBLY | | | OCCUPANCY OF 305 SQ. FT/ 11 = 28 OCCUPANTS ALWAYS ROUND | | | UP TO THE NEXT WHOLE PERSONS, WE DON'T HAVE PARTS OF | | | OCCUPANTS THEY ONLY COME IN A WHOLE PERSON. ALSO THE | | | SQUARE FOOTAGE IS UNDER 750 SQ. FT WHICH WOULD TRIGGER | | | THE ASSEMBLY OCCUPANCY WHEN THE OCCUPANT LOAD IS | | | FIGURED AT 15 SQ. FT./ OCCUPANT, ALSO NOTE FOR A MIXED | | | USE OCCUPANCY THE ACCESSORY OCCUPANCY HAS TO BE AT | | | LEAST 10% OF THE BUILDING AREA FOR THAT STORY TO BECOME | | | MIXED USE. | | | | | | 1D) IN THE DESCRIPTION OF WORK TO BE COMPLETED UNDER | | | THIS PERMIT, WITH THE REMOVAL OF A CONCRETE DRIVEWAY | | | AND ASPHALT PARKING LOT THIS WORK IS LOCATED ON AN | | | ADJOINING LOT. THE AERIAL VIEW SHOWS WORK AT 1022 | | | CLEARWATER PL. EITHER A SEPARATE PERMIT NEEDS TO BE | | | APPLIED FOR OR A UNITY OF TITLE TO UNIFY THE (2) LOTS. | | | | | | 2) SHEET SP-3 SHOWS ACCESSIBLE PARKING DETAILS, THEY | | | NEED TO BE TO THE CITY OF WEST PALM BEACH STANDARDS SEE | | | MUNI CODE 94-485 STALL PAINTING DETAIL. | | | 2010 FBC- ACCESSIBILITY 502.3.3. | | | | | | 3) SHEET A-3 EXISTING AND NEW DOORS ALL 3 BUILDINGS ARE | | | EITHER SHOWN AS 2'-6" OR 2'-8" PLEASE PROVIDE | | | COMPLIANCE WITH 2010 FBC-B SECTION 1008.1.1 SIZE OF | | | DOORS A MINIMUM OF 32" CLEAR OPENING OF THE DOOR. THIS | | | IS MEASURED WITH THE FACE OF THE DOOR TO THE OPPOSITE | | | SIDE DOOR STOP. FOR 32 INCHES CLEAR A MINIMUM OF A | | | 2'-10" IS REQUIRED. | | | ALSO SEE 2010 FBC-ACCESSIBILITY CODE 404.2.3 CLEAR | | | WIDTH. | | | | | | 3A) BUILDING # 2 THE DOOR TO THE LEFT SIDE OF THE FOYER | | | THAT LEADS TO THE DOG KENNELS DOES NOT HAVE THE CLEAR | | | FLOOR SPACE REQUIRED ON THE KENNEL SIDE OF THE DOOR SEE | | | FL ACCESS. FIGURE 404.2.4.1(J) REQUIRES A MINIMUM OF 42 | | | INCHES. | | | | | | 3B) PLEASE INDICATE WHERE THE GATES OR DOORS WILL BE ON | | | THE FRONT OF THE KENNELS, IT APPEARS THERE WILL BE ALOT | | | OF DOORS THAT WILL NOT HAVE THE REQUIRED 18" ON THE | | | LATCH SIDE OF THE DOOR. 2010 FBC-ACCESSIBILITY CODE | | | 404.2.4. | | | | | | 3C) BUILDING # 3 IN BOTH DOOG AREAS 246 SQ. FT & 270 | | | SQ. FT. THE INSWING DOORS ARE MISSING THE REQUIRED 18 | | | INCHES REQUIRED BY ACCESS. CODE 404.2.4. | | | | | | 3D) THE HALLWAY DOOR DIRECTLY IN FRONT OF THE OFFICE IS | | | ALSO MISSING THE REQUIRED 18 INCHES REQUIRED BY THE | | | 2010 FBC-ACCESS. CODE 404.2.4. | | | | | | 3E) THE NEW ACCESSIBLE RESTROOM IS NOT DEMINSIONED SO | | | CODE COMPLIANCE WITH 2010 FBC-ACCESSIBILITY CODE | | | SECTION 604.3.2 CAN NOT BE DETERMINED. | | | | | | 4) SHEET A4 THE LIFE SAFETY SHEET NOR THE COVER SHEET | | | INDICATE IF THE BUILDING IS FIRE SPRINKLERED OR NOT. | | | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION, 107.3.5.1.1 MINIMUM | | | PLAN REVIEW CRITERIA FOR BUILDINGS. | | | | | | 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2015-11-24 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-11-24 |
Time |
10:04 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-11-24 |
Time |
10:00 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2015-10-27 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-10-27 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-10-27 |
Time |
11:39 |
Sent To |
I |
|
| Notes |
| 2015-10-27 16:37:19 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION | | | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE2008 EDITION | | | OF THE NEC, (NATIONAL ELECTRICAL CODE); 2010 EDITION OF | | | THE FBC, (FLORIDA BUILDING CODE) AS APPLICABLE AND | | | BELOW ARE THE DEFICIENCIES NOTED. | | | | | | 1. BLDG. 1: | | | A) PER NEC, THE RESTROOM SHALL HAVE A LIGHT CONTROLLED | | | VIA A WALL SWITCH. PER FBC-ENERGY CONSERVATION CODE, | | | THAT SWITCH SHALL BE MOTION ACTIVATED. | | | B) EXIT/EMERGENCY LIGHT COMBO REQUIRED ABOVE THE EXIT | | | DOORWAY AND INSIDE THE WORKROOM. | | | C) NEC 600.5 REQUIRES THAT THERE BE A DEDICATED SIGN | | | OUTLET AT EVERY PEDESTRIAN ENTRY IN EVERY COMMERCIAL | | | ESTABLISHMENT. | | | 2. BLDG. 2 | | | A) NEC 600.5 REQUIRES THAT THERE BE A DEDICATED SIGN | | | OUTLET AT EVERY PEDESTRIAN ENTRY IN EVERY COMMERCIAL | | | ESTABLISHMENT. | | | B) EXIT/EMERGENCY LIGHT COMBO REQUIRED ABOVE THE EXIT | | | DOORWAY. | | | C) EXIT LIGHT REQUIRED AT THE END OF THE CORRIDORS | | | W/ARROW TOWARDS EXIT DOORWAY. | | | D) EMERGENCY LIGHTS REQUIRED MIDWAY IN THE CORRIDORS. | | | E) NEC 110.26(D) REQUIRES PROPER ILLUMINATION ABOUT | | | ELECTRICAL EQUIPMENT. THIS ILLUMINATION SHALL NOT BE | | | CONTROLLED BY AUTOMATIC MEANS. | | | 3. BLDG. 3: | | | A) NEC 600.5 REQUIRES THAT THERE BE A DEDICATED SIGN | | | OUTLET AT EVERY PEDESTRIAN ENTRY IN EVERY COMMERCIAL | | | ESTABLISHMENT. | | | B) NEC 422.52 REQUIRES THAT THE OUTLET FOR THE ELECTRIC | | | DRINKING FOUNTAIN BE PROTECTED WITH GFI. | | | C) EXIT/EMERGENCY LIGHT COMBO REQUIRED ABOVE THE EXIT | | | DOORWAY. | | | D) EXIT/EMERGENCY LIGHT COMBO REQUIRED IN HALL AND IN | | | EACH ENCLOSED ROOM AT EITHER END OF HALLWAY. | | | 4. GENERAL: | | | A) ALL LIGHTING SHALL COMPLY WITH ALL THE REQUIREMENTS | | | OF THE FBC-ENERGY CONSERVATION CODE. | | | B) CORRECT ALL THE LOAD CALCS TO MATCH THE ADDED LOADS. | | | C) CORRECT CIRCUIT DIRECTORIES TO MATCH ADDED DEVICES | | | AND COMMENTS PER THIS REVIEW. | | | D) CORRECT THE FEEDER DIAGRAM REQUIRED BY NEC 215.5 | | | CONDUCTOR SIZING TO MATCH THE PANEL CONNECTED LOADS. | | | E) ALL PANELBOARDS SHALL BE MARKED WITH THE ARC-FLASH | | | HAZARD WARNING LABEL AS REQUIRED IN NEC 110.16. | | | F) YOU HAD BETTER EMERGENCY LIGHT LAYOUT ON THE | | | PREVIOUSLY SUBMITTED PAGE EP 1. USE THAT AS A GUIDE FOR | | | YOUR RESUBMITTAL. | | | | | | THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN | | | MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED | | | FOR ANOTHER REVIEW. WHEN RESUBMITTING, YOU ARE REQUIRED | | | TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG | | | WITH THE STANDARD CITY RE-SUBMITTAL FORM. PLEASE, | | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE SUBMITTAL | | | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR | | | COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY | | | APPRECIATED. | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU, | | | MIKE ALBARRAN | | | ELECTRICAL PLANS EXAMINER | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2015-08-07 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-08-07 |
Time |
10:17 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-08-07 |
Time |
10:17 |
Sent To |
|
|
| Notes |
| 2015-08-07 10:22:42 | 1ST REVIEW: FBC 2010/NEC 2008 | | | | | | REVIEW DENIED. INFORMATION PROVIDED IS INSUFFICIENT. | | | | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.. | | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY | | | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK | | | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, | | | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING | | | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL | | | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, | | | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS | | | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH | | | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES | | | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE | | | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE | | | FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE | | | DESIGN. (SEE ALSO SECTION 107.3.5). | | | | | | PLEASE PROVIDE PER FBC- 107.3.5.3 ? ELECTRIC SERVICE | | | RISER WITH WIRE SIZES, CONDUIT DETAIL AND GROUNDING | | | DETAIL. COMPLETE LOAD CALCULATIONS, PANEL SCHEDULES AND | | | SHOW CIRCUITS ON FLOOR PLAN. T | | | | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2015-10-07 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2015-10-07 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2015-10-06 |
Time |
16:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2015-06-23 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2015-06-23 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2015-06-23 |
Time |
16:17 |
Sent To |
|
|
| Notes |
| 2015-06-23 16:25:52 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) SHEET CVR -PLEASE PROVIDE NOTE INDICATING COMPLIANCE | | | WITH NFPA 150 STANDARD ON FIRE AND LIFE SAFETY IN | | | ANIMAL HOUSING 2009 EDITION. | | | | | | 2) INDICATE, FOR EACH BUILDING, THE ANIMAL CATEGORY AND | | | ANIMAL CLASS IN COMPLIANCE WITH NFPA 150. | | | | | | 3) INDICATE, FOR EACH BUILDING, IF A FIRE SPRINKLER | | | AND/OR FIRE ALARM SYSTEM BE PROVIDED IN COMPLIANCE WITH | | | NFPA 150 AND PROVIDE CONCEPTUAL DRAWINGS. SHOP DRAWINGS | | | WILL BE REQUIRED SEPARATELY. | | | | | | 4) PROVIDE A DOOR SCHEDULE INCLUDING DOOR HARDWARE. | | | | | | 5) PROVIDE CAGE/GATE DETAIL FOR EACH KENNEL. | | | | | | 6) PROVIDE DETAIL ON ROLL DOWN GATES. DO THEY HAVE | | | CLUTHCING SYSTEM TO PREVENT RAPID ROLL DOWN? WILL THEY | | | BE ATTACHED TO FIRE ALARM SYSTEM? HOW WILL THEY BE | | | ACCESSED IN EMERGENCY SITUATION? IS THERE A FAIL SAFE | | | IN THE EVENT OF POWER FAILURE? | | | | | | 7) THE OVERNIGHT DOG SHELTER FLOOR LAYOUT INDICATES | | | DEADEND CORRIDORS OVER 20'. PROVIDE FOR A SECOND EXIT | | | OR PROVIDED ADDITIONAL DOORS TO CREATE A LOOP WITH | | | PROPER EXIT SIGNAGE. | | | | | | 8) WILL THE CAMPUS BE STAFFED 24 HOURS? HOW WILL A FIRE | | | ALARM/SPRINKLER ACTIVATION BE HANDLED? | | | | | | 9) HOW WILL EMERGENCY ACCESS TO THE CAMPUS BE PROVIDED. | | | A KNOX BOX KEY SYSTEM IS RECOMMENDED. | | | | | | 10) THERE ARE EXIT DISCHARGES INTO AREAS THAT DO NOT | | | APPEAR TO BE PUBLIC WAYS. EACH EACH SHALL LEAD TO A | | | PUBLIC WAY. AREAS FENCED IN SHALL BE HAVE EXIT ACCESS | | | GATES CLEARLY MARKED AS AN EXIT WITH PROPER EXIT | | | HARDWARE ON THOSE GATES. | | | | | | 11) IF GAS APPLIANCES ARE INSTALLED A CARBON MONOXIDE | | | DETECTION SYSTEM IS REQUIRED. | | | | | | 12) ADDITIONAL COMMENTS MAY BE PROVIDED WITH THE ABOVE | | | RESUBMITTALS. | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2015-12-02 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-12-02 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-12-02 |
Time |
12:50 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2015-12-01 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-12-01 |
Time |
10:04 |
Rev Time |
|
| Received By |
albarran |
Date |
2015-11-04 |
Time |
09:23 |
Sent To |
|
|
| Notes |
| 2015-11-30 15:14:24 | 11/24/15 PASSED ELECTRICAL REVIEWS BUT STILL PENDING | | | MECHANICAL AND IMPACT FEES. CONTRACTOR NOTIFIED VIA | | | EMAIL. SENT TO LARGE DENIED BIN "S". MA | | 2015-11-05 09:23:49 | C30 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2015-10-27 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-10-27 |
Time |
16:40 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-09-29 |
Time |
10:29 |
Sent To |
|
|
| Notes |
| 2015-10-27 16:40:09 | 10/27/15 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR | | | NOTIFIED VIA EMAIL. SENT TO LARGE DENIED BIN "S". MA | | 2015-09-29 10:30:08 | C30 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-08-07 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-08-07 |
Time |
10:22 |
Rev Time |
|
| Received By |
skennedy |
Date |
2015-06-18 |
Time |
|
Sent To |
|
|
| Notes |
| 2015-06-18 16:32:34 | INCOMING SENT TO C34 BOX. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2015-12-04 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2015-12-04 |
Time |
13:59 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2015-12-04 |
Time |
13:58 |
Sent To |
|
|
| Notes |
| 2015-12-04 13:59:55 | NO FEES DUE. MU-2015-028157. JG. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2015-07-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-07-07 |
Time |
12:22 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-07-07 |
Time |
12:22 |
Sent To |
|
|
| Notes |
| 2015-07-07 12:22:57 | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2015-12-02 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-12-02 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-12-02 |
Time |
15:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2015-11-17 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-11-17 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-11-17 |
Time |
08:40 |
Sent To |
|
|
| Notes |
| 2015-11-23 14:05:02 | 11/23/15 ON MALBARRAN'S DESK. CP | | 2015-11-17 08:57:43 | 3RD REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15060795 | | | 11/17/15 | | | | | | 1) SHEET M1, BUILDING #3: THE EXHAUST FAN AT 150 CFM IN | | | THE GROOMING AREA MUST BE A MINIMUM OF 202 CFM PER | | | TABLE 403.3 ( 225 SF. X .9 CFM/SF.) | | | 2) M1: PLEASE NUMBER THE BUILDINGS TO MATCH THE FLOOR | | | PLANS AND PROVIDE THE CFM'S AT EACH SUPPLY DIFFUSER | | | LOCATION SHOWN ON THE MECHANICAL PLANS FOR BUILDINGS #1 | | | & #2. | | | 3) M2: THE VENTILATION CALCULATIONS ARE INCOMPLETE. THE | | | EXISTING AC SYSTEMS MUST BE CAPABLE OF PROVIDING THE | | | REQUIRED OUTDOOR AIR FOR OCCUPANTS AS INDICATED IN | | | TABLE 403.3: (7.5 CFM PER OCCUPANT + .18 CFM/SF). | | | INDICATE ON THE SCHEDULES THE TOTAL SUPPLY AIR CFM'S OF | | | EACH AIR HANDLER, AND THE TOTAL OUTDOOR AIR BEING | | | SUPPLIED. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2015-10-08 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-10-08 |
Time |
09:32 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-10-08 |
Time |
07:48 |
Sent To |
|
|
| Notes |
| 2015-10-08 10:07:55 | 2ND REVIEW: FBC 2010 MECHANICAL | | | PERMIT #15060795 | | | 10/8/15 | | | | | | 1) THE HVAC PLAN DOES NOT MEET COMPLIANCE PER TABLE | | | 404.3 FBC-10 MECHANICAL. AS STATED IN THE 1ST REVIEW | | | EXHAUST AIR AT A RATE OF .90 CFM PER SQ. FT. IS | | | REQUIRED AND THE RECIRCULATION OF AIR FROM THE SPACES | | | CANNOT BE RECIRCULATED PER FOOTNPOTE B. THE PLAN DOES | | | NOT INDICATE A SYSTEM OF "AIR IN AND AIR OUT" AS | | | REQUIRED, AND ALSO INDICATES RETURN AIR FROM THE ANIMAL | | | AREAS BEING RECIRCULATED. FURTHER, PLEASE NOTE THAT THE | | | FANTECH ERV'S SPECIFIED AND SHOWN ON THE PLANS ARE | | | DESIGNED FOR HEAT EXCHANGE IN RESIDENTIAL OCCUPANCIES, | | | AND AS SHOWN IN THE DIAGRAMS, ARE NOT PROVIDING THE | | | NECESSARY EXHAUST. | | | 2) THE VENTILATION CALCULATIONS ARE NOT INDICATING THE | | | REQUIRED O/A FOR OCCUPANTS AS PREVIOSULY REQUESTED IN | | | THE1ST REVIEW- REFER TO TABLE 403.3: 7.5 CFM PER | | | OCCUPANT + 0.18 PER SQ. FT. OF THE SPACE. | | | 3) AT THIS TIME I AM REQUESTING THAT A MEETING BE | | | ARRANGED BETWEEN THE DESIGN PROFESSIOANLS AND MYSELF IN | | | AN EFFORT TO HELP CLARIFY THE CODE REQUIREMENTS AND | | | EXPEDITE THE REVIEW PROCESS. MY CONTACT INFORMATION IS | | | PRINTED BELOW. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2015-07-06 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-07-06 |
Time |
16:24 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-07-06 |
Time |
16:23 |
Sent To |
|
|
| Notes |
| 2015-07-06 16:49:56 | 1ST REVIEW: FBC 2010 MECHANICAL | | | PERMIT #15060795 7/6/15 | | | | | | 1) REVISE THE PLANS AND THE PERMIT APPLICATION WORK | | | DESCRIPTION TO INDICATE THE ACTUAL SCOPE OF THE | | | PROPOSED PROJECT- NEW PET BOARDING BUSINESS. PLEASE | | | REFERENCE SECTION 901.2 FBC- EXISTING BUILDING CODE AND | | | REVISE THE DESIGN CRITERIA AND PLANS TO BE IN | | | COMPLIANCE WITH ALL THE APPLICABLE REQUIREMENTS LISTED | | | IN CHAPTER 9. | | | 2) REFERENCE SECTION 909.1 FBC-10 EXISTING BUILDING | | | CODE FOR SPECIFIC MECHANICAL COMPLIANCE: PROVIDE | | | MINIMUM VENTILATION CALCULATIONS ON THE PLAN INCLUDING | | | THE REQUIRED OUTSIDE AIR AND REQUIRED EXHAUST RATES PER | | | TABLE 403.3 FBC-10 MECHANICAL. PLEASE NOTE THAT .9 CFM | | | PER SF IS THE REQUIRED RATE OF EXHAUST FOR ALL ANIMAL | | | ROOMS AND SPACES PER THE TABLE, AND THE AIR EXHAUSTED | | | FROM THOSE AREAS SHALL NOT BE RECIRCULATED PER FOOTNOTE | | | B. IN ADDITION, ALL AIR SUPPLIED (100 %) TO SUCH SPACES | | | SHALL BE EXHAUSTED INCLUDING ANY AIR IN EXCESS OF THAT | | | REQUIRED BY TABLE 403.3- REFERENCE SECTION 403.2.1. THE | | | SUBMITTED MECHANICAL PLAN INDICATING NO WORK TO BE DONE | | | IS DEFICIENT. NEW REVISED PLANS, DETAILS, AND | | | SPECIFICATIONS MEETING COMPLIANCE WITH THE ABOVE | | | REQUIREMENTS MUST BE SUBMITTED FOR REVIEW. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2015-11-10 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2015-11-10 |
Time |
09:33 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2015-11-10 |
Time |
09:33 |
Sent To |
|
|
| Notes |
| 2015-11-10 09:36:28 | | | | | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | APPROVED WITH EXCEPTION | | | PLUMBING PROVISO | | | 1. BUILDING 2 MOP SINK SHALL HAVE HOT WATER PROVIDED. | | | PER.FBC P 2010 SEC 607.1 WHERE REQUIRED. | | | | | | IN OCCUPIED STRUCTURES, HOT WATER SHALL BE SUPPLIED TO | | | ALL PLUMBING FIXTURES AND EQUIPMENT UTILIZED FOR | | | BATHING, WASHING, CULINARY PURPOSES, CLEANSING, LAUNDRY | | | OR BUILDING MAINTENANCE. | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2015-10-04 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-10-04 |
Time |
10:22 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-10-04 |
Time |
09:50 |
Sent To |
|
|
| Notes |
| 2015-10-04 09:59:17 | 1) SHT. P-2 - WATER RISER #2 NOTES " EXISTING TO REMAIN | | | NO CHANGES" YET A TOILET ROOM IS BEING DELETED AND A | | | MOP SINK ADDED.THE SAME APPLIES TO THE SANITARY | | | RISER.CLARIFY. | | | 2) SIZE THE VENT FOR THE DRINKING FOUNTAINS. | | | 3) IDENTIFY THE MOP SINK ON THE WATER RISER AS SUCH. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2015-07-12 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-07-12 |
Time |
09:52 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-07-12 |
Time |
09:24 |
Sent To |
|
|
| Notes |
| 2015-07-12 09:52:38 | 1) THE COVERSHEET NOTES THIS AS AN ASSEMBLY OCCUPANCY. | | | PLEASE REFER TO 2010 FBC SEC.304. THIS SHOULD BE | | | DEFINED AS A BUSINESS OCCUPANCY. | | | 2) SHT.A-3 - SHOW THE CLEAR INSIDE WIDTH OF THE TOILET | | | ROOM. THE MINIMUM WIDTH SHALL BE 85 INCHES IF BUILT | | | PERFECT, 86 INCHES ALLOWS FOR TOLERANCES. 2010 | | | FBC-ACCESSIBILITY SECS.604 & 606.2. | | | 3) A DRINKING FOUNTAIN IS REQUIRED IN A BUSINESS | | | OCCUPANCY. INDICATE IF BUILDING #3 HAS AN EXISTING | | | DRINKING FOUNTAIN.TABLE 403.1 OF 2010 FPC. | | | 4) SUBMIT A WATER RISER FOR REVIEW. WPB AMEND. TO FBC | | | 107.3.5.1.3. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2015-10-23 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2015-10-23 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2015-10-23 |
Time |
|
Sent To |
|
|
| Notes |
| 2015-10-23 11:06:20 | SEPARATE PERMIT REQUIRED FOR LANDSCAPE. | | | | | | (REFERENCE CLASS B SPECIAL USE PERMIT, DAC CASE NO. | | | 15-02) |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2015-07-08 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2015-07-08 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2015-07-08 |
Time |
|
Sent To |
|
|
| Notes |
| 2015-07-08 13:53:42 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) CONDITIONS FOR THE CLASS B SPECIAL USE PERMIT NOT | | | ADDRESSED (REFERENCE: FINAL ORDER DAC 15-02) | | | | | | NOTES: | | | | | | * SEPARATE PERMIT REQUIRED FOR LANDSCAPING. | | | | | | PLEASE CONTACT LINDA LOUIE @ (561) 822-1458 IF YOU HAVE | | | QUESTIONS. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2015-06-22 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2015-06-22 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2015-06-22 |
Time |
13:39 |
Sent To |
|
|
| Notes |
|
|