Plan Review Details - Permit 15060795
Plan Review Stops For Permit 15060795
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-10-08 Cont ID  
Sent By jwitmer Date 2015-10-08 Time 06:31 Rev Time 0.00
Received By jwitmer Date 2015-10-08 Time 05:32 Sent To  
Notes
2015-10-08 06:49:05BUILDING PLAN REVIEW
 W. P. B. PERMIT:15060795
 ADD: 1016 CLEARWATER PL.
 CONT: SIDNEY SCHREIDELL
 TEL: (954)214-7908
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. OCT. 08/2015
 ACTION: BUILDING PROVISO
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) BLDG. # 3 CORRIDOR WITH DOORS 9 & 10, 2010
 FBC-ACCESSIBILITY CODE 404.2.6, DOORS IN SERIES, DOOR #
 9 WAS MOVED SO THERE IS NO LONGER 4 FOOT BETWEEN DOORS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-07-07 Cont ID  
Sent By jwitmer Date 2015-07-07 Time 12:29 Rev Time  
Received By jwitmer Date 2015-07-07 Time   Sent To  
Notes
2015-07-07 08:06:38BUILDING PLAN REVIEW
 W. P. B. PERMIT:15060795
 ADD: 1016 CLEARWATER PL.
 CONT: SIDNEY SCHREIDELL
 TEL: (954)214-7908
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JULY 07/2015
 ACTION: DENIED
  
 1) THE COVERSHEET:
 1A) THE OCCUPANCY CLASSIFICATION IS LISTED AS AN A3-
 BUT THE PLANS INDICATE THE USAGE BEING A ANIMAL KENNEL,
 PLEASE REVIEW 2010 FBC-B SECTION 304.1 IT APPEARS THE
 OCCUPANCY SHOULD BE A BUSINESS OCCUPANCY.
  
 1B) UNDER THE HEADING OF OCCUPANCY LOADS INDICATES AN
 ADDITION BUT THERE IS A NOTE FURTHER DOWN THE PAGE THAT
 THERE IS NO CHANGE OF SQUARE FOOTAGE. 2010 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION, 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 1C) PLEASE NOTE THE PLANS INDICATE AN ASSEMBLY
 OCCUPANCY OF 305 SQ. FT/ 11 = 28 OCCUPANTS ALWAYS ROUND
 UP TO THE NEXT WHOLE PERSONS, WE DON'T HAVE PARTS OF
 OCCUPANTS THEY ONLY COME IN A WHOLE PERSON. ALSO THE
 SQUARE FOOTAGE IS UNDER 750 SQ. FT WHICH WOULD TRIGGER
 THE ASSEMBLY OCCUPANCY WHEN THE OCCUPANT LOAD IS
 FIGURED AT 15 SQ. FT./ OCCUPANT, ALSO NOTE FOR A MIXED
 USE OCCUPANCY THE ACCESSORY OCCUPANCY HAS TO BE AT
 LEAST 10% OF THE BUILDING AREA FOR THAT STORY TO BECOME
 MIXED USE.
  
 1D) IN THE DESCRIPTION OF WORK TO BE COMPLETED UNDER
 THIS PERMIT, WITH THE REMOVAL OF A CONCRETE DRIVEWAY
 AND ASPHALT PARKING LOT THIS WORK IS LOCATED ON AN
 ADJOINING LOT. THE AERIAL VIEW SHOWS WORK AT 1022
 CLEARWATER PL. EITHER A SEPARATE PERMIT NEEDS TO BE
 APPLIED FOR OR A UNITY OF TITLE TO UNIFY THE (2) LOTS.
  
 2) SHEET SP-3 SHOWS ACCESSIBLE PARKING DETAILS, THEY
 NEED TO BE TO THE CITY OF WEST PALM BEACH STANDARDS SEE
 MUNI CODE 94-485 STALL PAINTING DETAIL.
 2010 FBC- ACCESSIBILITY 502.3.3.
  
 3) SHEET A-3 EXISTING AND NEW DOORS ALL 3 BUILDINGS ARE
 EITHER SHOWN AS 2'-6" OR 2'-8" PLEASE PROVIDE
 COMPLIANCE WITH 2010 FBC-B SECTION 1008.1.1 SIZE OF
 DOORS A MINIMUM OF 32" CLEAR OPENING OF THE DOOR. THIS
 IS MEASURED WITH THE FACE OF THE DOOR TO THE OPPOSITE
 SIDE DOOR STOP. FOR 32 INCHES CLEAR A MINIMUM OF A
 2'-10" IS REQUIRED.
 ALSO SEE 2010 FBC-ACCESSIBILITY CODE 404.2.3 CLEAR
 WIDTH.
  
 3A) BUILDING # 2 THE DOOR TO THE LEFT SIDE OF THE FOYER
 THAT LEADS TO THE DOG KENNELS DOES NOT HAVE THE CLEAR
 FLOOR SPACE REQUIRED ON THE KENNEL SIDE OF THE DOOR SEE
 FL ACCESS. FIGURE 404.2.4.1(J) REQUIRES A MINIMUM OF 42
 INCHES.
  
 3B) PLEASE INDICATE WHERE THE GATES OR DOORS WILL BE ON
 THE FRONT OF THE KENNELS, IT APPEARS THERE WILL BE ALOT
 OF DOORS THAT WILL NOT HAVE THE REQUIRED 18" ON THE
 LATCH SIDE OF THE DOOR. 2010 FBC-ACCESSIBILITY CODE
 404.2.4.
  
 3C) BUILDING # 3 IN BOTH DOOG AREAS 246 SQ. FT & 270
 SQ. FT. THE INSWING DOORS ARE MISSING THE REQUIRED 18
 INCHES REQUIRED BY ACCESS. CODE 404.2.4.
  
 3D) THE HALLWAY DOOR DIRECTLY IN FRONT OF THE OFFICE IS
 ALSO MISSING THE REQUIRED 18 INCHES REQUIRED BY THE
 2010 FBC-ACCESS. CODE 404.2.4.
  
 3E) THE NEW ACCESSIBLE RESTROOM IS NOT DEMINSIONED SO
 CODE COMPLIANCE WITH 2010 FBC-ACCESSIBILITY CODE
 SECTION 604.3.2 CAN NOT BE DETERMINED.
  
 4) SHEET A4 THE LIFE SAFETY SHEET NOR THE COVER SHEET
 INDICATE IF THE BUILDING IS FIRE SPRINKLERED OR NOT.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.3.5.1.1 MINIMUM
 PLAN REVIEW CRITERIA FOR BUILDINGS.
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-11-24 Cont ID  
Sent By albarran Date 2015-11-24 Time 10:04 Rev Time 0.00
Received By albarran Date 2015-11-24 Time 10:00 Sent To I
Notes
2015-11-30 15:11:28 
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-10-27 Cont ID  
Sent By albarran Date 2015-10-27 Time 16:35 Rev Time 0.00
Received By albarran Date 2015-10-27 Time 11:39 Sent To I
Notes
2015-10-27 16:37:19THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE2008 EDITION
 OF THE NEC, (NATIONAL ELECTRICAL CODE); 2010 EDITION OF
 THE FBC, (FLORIDA BUILDING CODE) AS APPLICABLE AND
 BELOW ARE THE DEFICIENCIES NOTED.
  
 1. BLDG. 1:
 A) PER NEC, THE RESTROOM SHALL HAVE A LIGHT CONTROLLED
 VIA A WALL SWITCH. PER FBC-ENERGY CONSERVATION CODE,
 THAT SWITCH SHALL BE MOTION ACTIVATED.
 B) EXIT/EMERGENCY LIGHT COMBO REQUIRED ABOVE THE EXIT
 DOORWAY AND INSIDE THE WORKROOM.
 C) NEC 600.5 REQUIRES THAT THERE BE A DEDICATED SIGN
 OUTLET AT EVERY PEDESTRIAN ENTRY IN EVERY COMMERCIAL
 ESTABLISHMENT.
 2. BLDG. 2
 A) NEC 600.5 REQUIRES THAT THERE BE A DEDICATED SIGN
 OUTLET AT EVERY PEDESTRIAN ENTRY IN EVERY COMMERCIAL
 ESTABLISHMENT.
 B) EXIT/EMERGENCY LIGHT COMBO REQUIRED ABOVE THE EXIT
 DOORWAY.
 C) EXIT LIGHT REQUIRED AT THE END OF THE CORRIDORS
 W/ARROW TOWARDS EXIT DOORWAY.
 D) EMERGENCY LIGHTS REQUIRED MIDWAY IN THE CORRIDORS.
 E) NEC 110.26(D) REQUIRES PROPER ILLUMINATION ABOUT
 ELECTRICAL EQUIPMENT. THIS ILLUMINATION SHALL NOT BE
 CONTROLLED BY AUTOMATIC MEANS.
 3. BLDG. 3:
 A) NEC 600.5 REQUIRES THAT THERE BE A DEDICATED SIGN
 OUTLET AT EVERY PEDESTRIAN ENTRY IN EVERY COMMERCIAL
 ESTABLISHMENT.
 B) NEC 422.52 REQUIRES THAT THE OUTLET FOR THE ELECTRIC
 DRINKING FOUNTAIN BE PROTECTED WITH GFI.
 C) EXIT/EMERGENCY LIGHT COMBO REQUIRED ABOVE THE EXIT
 DOORWAY.
 D) EXIT/EMERGENCY LIGHT COMBO REQUIRED IN HALL AND IN
 EACH ENCLOSED ROOM AT EITHER END OF HALLWAY.
 4. GENERAL:
 A) ALL LIGHTING SHALL COMPLY WITH ALL THE REQUIREMENTS
 OF THE FBC-ENERGY CONSERVATION CODE.
 B) CORRECT ALL THE LOAD CALCS TO MATCH THE ADDED LOADS.
 C) CORRECT CIRCUIT DIRECTORIES TO MATCH ADDED DEVICES
 AND COMMENTS PER THIS REVIEW.
 D) CORRECT THE FEEDER DIAGRAM REQUIRED BY NEC 215.5
 CONDUCTOR SIZING TO MATCH THE PANEL CONNECTED LOADS.
 E) ALL PANELBOARDS SHALL BE MARKED WITH THE ARC-FLASH
 HAZARD WARNING LABEL AS REQUIRED IN NEC 110.16.
 F) YOU HAD BETTER EMERGENCY LIGHT LAYOUT ON THE
 PREVIOUSLY SUBMITTED PAGE EP 1. USE THAT AS A GUIDE FOR
 YOUR RESUBMITTAL.
  
 THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN
 MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED
 FOR ANOTHER REVIEW. WHEN RESUBMITTING, YOU ARE REQUIRED
 TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG
 WITH THE STANDARD CITY RE-SUBMITTAL FORM. PLEASE,
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE SUBMITTAL
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY
 APPRECIATED.
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-08-07 Cont ID  
Sent By skennedy Date 2015-08-07 Time 10:17 Rev Time 0.00
Received By skennedy Date 2015-08-07 Time 10:17 Sent To  
Notes
2015-08-07 10:22:421ST REVIEW: FBC 2010/NEC 2008
  
 REVIEW DENIED. INFORMATION PROVIDED IS INSUFFICIENT.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS..
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 PLEASE PROVIDE PER FBC- 107.3.5.3 ? ELECTRIC SERVICE
 RISER WITH WIRE SIZES, CONDUIT DETAIL AND GROUNDING
 DETAIL. COMPLETE LOAD CALCULATIONS, PANEL SCHEDULES AND
 SHOW CIRCUITS ON FLOOR PLAN. T
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-10-07 Cont ID  
Sent By pleduc Date 2015-10-07 Time   Rev Time 0.00
Received By pleduc Date 2015-10-06 Time 16:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-06-23 Cont ID  
Sent By pleduc Date 2015-06-23 Time   Rev Time 0.00
Received By pleduc Date 2015-06-23 Time 16:17 Sent To  
Notes
2015-06-23 16:25:52THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET CVR -PLEASE PROVIDE NOTE INDICATING COMPLIANCE
 WITH NFPA 150 STANDARD ON FIRE AND LIFE SAFETY IN
 ANIMAL HOUSING 2009 EDITION.
  
 2) INDICATE, FOR EACH BUILDING, THE ANIMAL CATEGORY AND
 ANIMAL CLASS IN COMPLIANCE WITH NFPA 150.
  
 3) INDICATE, FOR EACH BUILDING, IF A FIRE SPRINKLER
 AND/OR FIRE ALARM SYSTEM BE PROVIDED IN COMPLIANCE WITH
 NFPA 150 AND PROVIDE CONCEPTUAL DRAWINGS. SHOP DRAWINGS
 WILL BE REQUIRED SEPARATELY.
  
 4) PROVIDE A DOOR SCHEDULE INCLUDING DOOR HARDWARE.
  
 5) PROVIDE CAGE/GATE DETAIL FOR EACH KENNEL.
  
 6) PROVIDE DETAIL ON ROLL DOWN GATES. DO THEY HAVE
 CLUTHCING SYSTEM TO PREVENT RAPID ROLL DOWN? WILL THEY
 BE ATTACHED TO FIRE ALARM SYSTEM? HOW WILL THEY BE
 ACCESSED IN EMERGENCY SITUATION? IS THERE A FAIL SAFE
 IN THE EVENT OF POWER FAILURE?
  
 7) THE OVERNIGHT DOG SHELTER FLOOR LAYOUT INDICATES
 DEADEND CORRIDORS OVER 20'. PROVIDE FOR A SECOND EXIT
 OR PROVIDED ADDITIONAL DOORS TO CREATE A LOOP WITH
 PROPER EXIT SIGNAGE.
  
 8) WILL THE CAMPUS BE STAFFED 24 HOURS? HOW WILL A FIRE
 ALARM/SPRINKLER ACTIVATION BE HANDLED?
  
 9) HOW WILL EMERGENCY ACCESS TO THE CAMPUS BE PROVIDED.
 A KNOX BOX KEY SYSTEM IS RECOMMENDED.
  
 10) THERE ARE EXIT DISCHARGES INTO AREAS THAT DO NOT
 APPEAR TO BE PUBLIC WAYS. EACH EACH SHALL LEAD TO A
 PUBLIC WAY. AREAS FENCED IN SHALL BE HAVE EXIT ACCESS
 GATES CLEARLY MARKED AS AN EXIT WITH PROPER EXIT
 HARDWARE ON THOSE GATES.
  
 11) IF GAS APPLIANCES ARE INSTALLED A CARBON MONOXIDE
 DETECTION SYSTEM IS REQUIRED.
  
 12) ADDITIONAL COMMENTS MAY BE PROVIDED WITH THE ABOVE
 RESUBMITTALS.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-12-02 Cont ID  
Sent By ccole Date 2015-12-02 Time 15:04 Rev Time 0.00
Received By ccole Date 2015-12-02 Time 12:50 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-12-01 Cont ID  
Sent By albarran Date 2015-12-01 Time 10:04 Rev Time  
Received By albarran Date 2015-11-04 Time 09:23 Sent To  
Notes
2015-11-30 15:14:2411/24/15 PASSED ELECTRICAL REVIEWS BUT STILL PENDING
 MECHANICAL AND IMPACT FEES. CONTRACTOR NOTIFIED VIA
 EMAIL. SENT TO LARGE DENIED BIN "S". MA
2015-11-05 09:23:49C30

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-27 Cont ID  
Sent By albarran Date 2015-10-27 Time 16:40 Rev Time 0.00
Received By albarran Date 2015-09-29 Time 10:29 Sent To  
Notes
2015-10-27 16:40:0910/27/15 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT TO LARGE DENIED BIN "S". MA
2015-09-29 10:30:08C30

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-07 Cont ID  
Sent By skennedy Date 2015-08-07 Time 10:22 Rev Time  
Received By skennedy Date 2015-06-18 Time   Sent To  
Notes
2015-06-18 16:32:34INCOMING SENT TO C34 BOX.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2015-12-04 Cont ID  
Sent By jgomez Date 2015-12-04 Time 13:59 Rev Time 0.00
Received By jgomez Date 2015-12-04 Time 13:58 Sent To  
Notes
2015-12-04 13:59:55NO FEES DUE. MU-2015-028157. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-07-07 Cont ID  
Sent By jwitmer Date 2015-07-07 Time 12:22 Rev Time 0.00
Received By jwitmer Date 2015-07-07 Time 12:22 Sent To  
Notes
2015-07-07 12:22:57BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2015-12-02 Cont ID  
Sent By ccole Date 2015-12-02 Time 15:04 Rev Time 0.00
Received By ccole Date 2015-12-02 Time 15:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2015-11-17 Cont ID  
Sent By ccole Date 2015-11-17 Time 08:40 Rev Time 0.00
Received By ccole Date 2015-11-17 Time 08:40 Sent To  
Notes
2015-11-23 14:05:0211/23/15 ON MALBARRAN'S DESK. CP
2015-11-17 08:57:433RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #15060795
 11/17/15
  
 1) SHEET M1, BUILDING #3: THE EXHAUST FAN AT 150 CFM IN
 THE GROOMING AREA MUST BE A MINIMUM OF 202 CFM PER
 TABLE 403.3 ( 225 SF. X .9 CFM/SF.)
 2) M1: PLEASE NUMBER THE BUILDINGS TO MATCH THE FLOOR
 PLANS AND PROVIDE THE CFM'S AT EACH SUPPLY DIFFUSER
 LOCATION SHOWN ON THE MECHANICAL PLANS FOR BUILDINGS #1
 & #2.
 3) M2: THE VENTILATION CALCULATIONS ARE INCOMPLETE. THE
 EXISTING AC SYSTEMS MUST BE CAPABLE OF PROVIDING THE
 REQUIRED OUTDOOR AIR FOR OCCUPANTS AS INDICATED IN
 TABLE 403.3: (7.5 CFM PER OCCUPANT + .18 CFM/SF).
 INDICATE ON THE SCHEDULES THE TOTAL SUPPLY AIR CFM'S OF
 EACH AIR HANDLER, AND THE TOTAL OUTDOOR AIR BEING
 SUPPLIED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-10-08 Cont ID  
Sent By ccole Date 2015-10-08 Time 09:32 Rev Time 0.00
Received By ccole Date 2015-10-08 Time 07:48 Sent To  
Notes
2015-10-08 10:07:552ND REVIEW: FBC 2010 MECHANICAL
 PERMIT #15060795
 10/8/15
  
 1) THE HVAC PLAN DOES NOT MEET COMPLIANCE PER TABLE
 404.3 FBC-10 MECHANICAL. AS STATED IN THE 1ST REVIEW
 EXHAUST AIR AT A RATE OF .90 CFM PER SQ. FT. IS
 REQUIRED AND THE RECIRCULATION OF AIR FROM THE SPACES
 CANNOT BE RECIRCULATED PER FOOTNPOTE B. THE PLAN DOES
 NOT INDICATE A SYSTEM OF "AIR IN AND AIR OUT" AS
 REQUIRED, AND ALSO INDICATES RETURN AIR FROM THE ANIMAL
 AREAS BEING RECIRCULATED. FURTHER, PLEASE NOTE THAT THE
 FANTECH ERV'S SPECIFIED AND SHOWN ON THE PLANS ARE
 DESIGNED FOR HEAT EXCHANGE IN RESIDENTIAL OCCUPANCIES,
 AND AS SHOWN IN THE DIAGRAMS, ARE NOT PROVIDING THE
 NECESSARY EXHAUST.
 2) THE VENTILATION CALCULATIONS ARE NOT INDICATING THE
 REQUIRED O/A FOR OCCUPANTS AS PREVIOSULY REQUESTED IN
 THE1ST REVIEW- REFER TO TABLE 403.3: 7.5 CFM PER
 OCCUPANT + 0.18 PER SQ. FT. OF THE SPACE.
 3) AT THIS TIME I AM REQUESTING THAT A MEETING BE
 ARRANGED BETWEEN THE DESIGN PROFESSIOANLS AND MYSELF IN
 AN EFFORT TO HELP CLARIFY THE CODE REQUIREMENTS AND
 EXPEDITE THE REVIEW PROCESS. MY CONTACT INFORMATION IS
 PRINTED BELOW.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-07-06 Cont ID  
Sent By ccole Date 2015-07-06 Time 16:24 Rev Time 0.00
Received By ccole Date 2015-07-06 Time 16:23 Sent To  
Notes
2015-07-06 16:49:561ST REVIEW: FBC 2010 MECHANICAL
 PERMIT #15060795 7/6/15
  
 1) REVISE THE PLANS AND THE PERMIT APPLICATION WORK
 DESCRIPTION TO INDICATE THE ACTUAL SCOPE OF THE
 PROPOSED PROJECT- NEW PET BOARDING BUSINESS. PLEASE
 REFERENCE SECTION 901.2 FBC- EXISTING BUILDING CODE AND
 REVISE THE DESIGN CRITERIA AND PLANS TO BE IN
 COMPLIANCE WITH ALL THE APPLICABLE REQUIREMENTS LISTED
 IN CHAPTER 9.
 2) REFERENCE SECTION 909.1 FBC-10 EXISTING BUILDING
 CODE FOR SPECIFIC MECHANICAL COMPLIANCE: PROVIDE
 MINIMUM VENTILATION CALCULATIONS ON THE PLAN INCLUDING
 THE REQUIRED OUTSIDE AIR AND REQUIRED EXHAUST RATES PER
 TABLE 403.3 FBC-10 MECHANICAL. PLEASE NOTE THAT .9 CFM
 PER SF IS THE REQUIRED RATE OF EXHAUST FOR ALL ANIMAL
 ROOMS AND SPACES PER THE TABLE, AND THE AIR EXHAUSTED
 FROM THOSE AREAS SHALL NOT BE RECIRCULATED PER FOOTNOTE
 B. IN ADDITION, ALL AIR SUPPLIED (100 %) TO SUCH SPACES
 SHALL BE EXHAUSTED INCLUDING ANY AIR IN EXCESS OF THAT
 REQUIRED BY TABLE 403.3- REFERENCE SECTION 403.2.1. THE
 SUBMITTED MECHANICAL PLAN INDICATING NO WORK TO BE DONE
 IS DEFICIENT. NEW REVISED PLANS, DETAILS, AND
 SPECIFICATIONS MEETING COMPLIANCE WITH THE ABOVE
 REQUIREMENTS MUST BE SUBMITTED FOR REVIEW.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-11-10 Cont ID  
Sent By gjohnson Date 2015-11-10 Time 09:33 Rev Time 0.00
Received By gjohnson Date 2015-11-10 Time 09:33 Sent To  
Notes
2015-11-10 09:36:28 
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 APPROVED WITH EXCEPTION
  PLUMBING PROVISO
 1. BUILDING 2 MOP SINK SHALL HAVE HOT WATER PROVIDED.
  PER.FBC P 2010 SEC 607.1 WHERE REQUIRED.
  
 IN OCCUPIED STRUCTURES, HOT WATER SHALL BE SUPPLIED TO
 ALL PLUMBING FIXTURES AND EQUIPMENT UTILIZED FOR
 BATHING, WASHING, CULINARY PURPOSES, CLEANSING, LAUNDRY
 OR BUILDING MAINTENANCE.
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-10-04 Cont ID  
Sent By tklarge Date 2015-10-04 Time 10:22 Rev Time 0.00
Received By tklarge Date 2015-10-04 Time 09:50 Sent To  
Notes
2015-10-04 09:59:171) SHT. P-2 - WATER RISER #2 NOTES " EXISTING TO REMAIN
 NO CHANGES" YET A TOILET ROOM IS BEING DELETED AND A
 MOP SINK ADDED.THE SAME APPLIES TO THE SANITARY
 RISER.CLARIFY.
 2) SIZE THE VENT FOR THE DRINKING FOUNTAINS.
 3) IDENTIFY THE MOP SINK ON THE WATER RISER AS SUCH.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-07-12 Cont ID  
Sent By tklarge Date 2015-07-12 Time 09:52 Rev Time 0.00
Received By tklarge Date 2015-07-12 Time 09:24 Sent To  
Notes
2015-07-12 09:52:381) THE COVERSHEET NOTES THIS AS AN ASSEMBLY OCCUPANCY.
 PLEASE REFER TO 2010 FBC SEC.304. THIS SHOULD BE
 DEFINED AS A BUSINESS OCCUPANCY.
 2) SHT.A-3 - SHOW THE CLEAR INSIDE WIDTH OF THE TOILET
 ROOM. THE MINIMUM WIDTH SHALL BE 85 INCHES IF BUILT
 PERFECT, 86 INCHES ALLOWS FOR TOLERANCES. 2010
 FBC-ACCESSIBILITY SECS.604 & 606.2.
 3) A DRINKING FOUNTAIN IS REQUIRED IN A BUSINESS
 OCCUPANCY. INDICATE IF BUILDING #3 HAS AN EXISTING
 DRINKING FOUNTAIN.TABLE 403.1 OF 2010 FPC.
 4) SUBMIT A WATER RISER FOR REVIEW. WPB AMEND. TO FBC
 107.3.5.1.3.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2015-10-23 Cont ID  
Sent By llouie Date 2015-10-23 Time   Rev Time 0.00
Received By llouie Date 2015-10-23 Time   Sent To  
Notes
2015-10-23 11:06:20SEPARATE PERMIT REQUIRED FOR LANDSCAPE.
  
 (REFERENCE CLASS B SPECIAL USE PERMIT, DAC CASE NO.
 15-02)

Review Stop Z ZONING
Rev No 2 Status F Date 2015-07-08 Cont ID  
Sent By llouie Date 2015-07-08 Time   Rev Time 0.00
Received By llouie Date 2015-07-08 Time   Sent To  
Notes
2015-07-08 13:53:42** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) CONDITIONS FOR THE CLASS B SPECIAL USE PERMIT NOT
 ADDRESSED (REFERENCE: FINAL ORDER DAC 15-02)
  
 NOTES:
  
 * SEPARATE PERMIT REQUIRED FOR LANDSCAPING.
  
 PLEASE CONTACT LINDA LOUIE @ (561) 822-1458 IF YOU HAVE
 QUESTIONS.
  

Review Stop Z ZONING
Rev No 1 Status P Date 2015-06-22 Cont ID  
Sent By ajones Date 2015-06-22 Time 13:39 Rev Time 0.00
Received By ajones Date 2015-06-22 Time 13:39 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved