Plan Review Details - Permit 15060791
Plan Review Stops For Permit 15060791
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-10-19 Cont ID  
Sent By jwitmer Date 2015-10-19 Time 15:55 Rev Time 0.00
Received By jwitmer Date 2015-10-19 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-09-21 Cont ID  
Sent By jwitmer Date 2015-09-21 Time   Rev Time 0.00
Received By jwitmer Date 2015-09-21 Time   Sent To  
Notes
2015-09-21 14:38:47BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060791
 ADD: 333 CLEMATIS ST.
 CONTRACTOR: HORMAK CONSTRUCTION
 TEL: (561)790-6863
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. SEPT. 21/2015
 ACTION: DENIED
  
 1A) COMPLIED. WILL NEED TO GET A CBC OR CGC ONBOARD FOR
 WORK BEYOND THE SCOPE OF YOUR LICENSE. FL S.S. 489.113.
  
 1B)VALUE IS STILL LOW AT $20,000.00. THE SUMMITED
 CONTRACT VALUE IS $23,500.00 AND THERE IS NO LINE ITEM
 FOR THE NEW STOREFRONT DOOR AND WALL SYSTEM.
 1ST REVIEW COMMENT. FOR THE WHOLE PROJECT THE VALUE OF
 $3,000.00 IS CONSIDERABLY LOW. 108.3* BUILDING PERMIT
 VALUATION.
  
 2) COMPLIED. SHEET A-1. THE RESTROOM DOORWAY NEXT TO
 THE REAR EXIT BLOCKS THE REAR EXIT, WILL NEED TO SWING
 INTO THE RESTROOM, SHOW COMPLIANCE WITH SECTION 2010
 FBC-B 1008.1.9.11 DURING ITS SWING, ANY DOOR IN A MEANS
 OF EGRESS SHALL LEAVE UNOBSTRUCTED AT LEAST ONE HALF OF
 THE REQUIRED WIDTH OF AN CORRIDOR, PASSAGEWAY OR
 LANDING, NOR PROJECT MORE THAN 7 INCHES INTO THE
 REQUIRED WIDTH OF CORRIDOR OR PASSAGEWAY.
  
 3) SEMI- COMPLIED. SHEET A-2 INDICATES THE WIND DESIGN
 CRITERIA. NOTE THE DESIGNER OF RECORD HAS INDICATED
 THAT THE EXPOSURE FOR THIS LOCATION IS A EXPOSURE D.
 THIS IS MORE RESTRICTIVE BUT IF THE DESIGNER OF ECORD
 WISHES TO DESIGN TO THE MORE RESTRICTIVE D EXPOSURE
 THEN THE PRESSURES ALSO WILL NEED TO MEET THE
 PRESSURES.
  
 THE PRESSURES FOR ROOF ZONES 1, 2 & 3 ALL INDICATE A
 PRESSURE OF 23.99 FOR 20 SQ. FT. THE FASTENING FOR
 ROOFS IS TAKEN AT 10 SQ. FT. FOR FASTENERS. THE DESIGN
 LIST THE VULT WIND SPEED OF 170 MPH. THE PRESSURES DO
 NOT INDICATE IF THEY ARE VULT OR VASD? THE ROOF
 PRESSURES IN VASD FOR A EXPOSURE D ARE FOR ZONE 1 ARE
 -50.4, ZONE 2 -108.4 & FOR ZONE 3 -127.3 @ 25 FT. MEAN
 ROOF HEIGHT.
  
 THE WINDOW PRESSURES WILL ALSO NEED TO INDICATE IF THEY
 ARE VULT OR VASD.
  
 COMMENT FROM THE 1ST REVIEW
 SHEET A-1 SHOWS A NEW GLASS STOREFRONT WINDOWS AND SET
 OF DOUBLE DOORS. PLEASE PROVIDE THE WIND DESIGN
 CRITERIA.
 . WIND DESIGN CRITERIA
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
  
  
 3.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 3.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 3.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 3.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 3.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2).
  
 4) 2ND REQUEST, UNTIL PRESSURES ARE INDICATED IN EITHER
 VULT OR VASD THE PRODUCT APPROVALS CAN NOT BE REVIEWED.
 COMPONENTS & CLADDING/ 2010 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) STOREFRONTS, CURTAIN WALLS, WALL LOUVERS, EFIS
 SYSTEMS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 5) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6) 2ND REQUEST. PLEASE PROVIDE ENERGY CALCULATIONS FOR
 THE NEW ADDITION. PROVIDE COMPLIANCE FOR THE SHGC OF
 THE GLAZING COMPLY WITH FBC-ENERGY TABLE 502.1.1.1(1)
 OR TABLE 502.1.1.1(2).
  
 7) 2ND REQUEST. DEALS WITH THE ELEVATED PEDICURE
 STATIONS AND THE RAISED PLATFORM BY TENANT. EITHER THE
 RAISED PLATFORM IS PART OF THE PERMIT AND THE WORK
 SHOWN OR IT IS NOT AND THE PEDICURE STATIONS ARE NOT
 SHOWN SINCE THEY WOULD NO LONGER BE IN THE SCOPE OF
 WORK.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION.
  
 AS FAR AS THE ACCESSIBLE PEDICURE STATION WITH A
 PORTABLE WASH TUB FOR SERVICE, IT WILL NEED TO SHOW A
 EQUIVALENCY TOO, 2010 FBC-ACCESSIBILITY CODE 103
 EQUIVALENT FACILITATION.
  
  
 COMMENT FROM THE 1ST REVIEW. SHEET A-1 SHOWS ELEVATED
 PEDICURE STATIONS AND A DETAIL 1 OF SHEET A-2. PLEASE
 SHOW COMPLIANCE WITH FBC-ACCESSIBILITY, VERTICAL
 ACCESSIBILITY TO PEDICURE STATIONS. 201.1.1.
  
 8) 2ND REQUEST, ADDITIONAL SQUARE FOOTAGE ADDED. BEFORE
 A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST
 BE PAID TO PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF
 PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE
 PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE
 CALL (561)233-5025 FOR MORE INFORMATION.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-22 Cont ID  
Sent By jwitmer Date 2015-06-22 Time 06:28 Rev Time 0.00
Received By jwitmer Date 2015-06-22 Time 05:44 Sent To  
Notes
2015-06-22 06:12:25 
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15060791
 ADD: 333 CLEMATIS ST.
 CONTRACTOR: RANDYS PLUMBING
 TEL: (561)242-9627
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JUNE 22/2015
 ACTION: DENIED
  
 1A) WILL NEED TO GET A CBC OR CGC ONBOARD FOR WORK
 BEYOND THE SCOPE OF YOUR LICENSE. FL S.S. 489.113.
  
 1B) FOR THE WHOLE PROJECT THE VALUE OF $3,000.00 IS
 CONSIDERABLY LOW. 108.3* BUILDING PERMIT VALUATION.
  
 2) SHEET A-1. THE RESTROOM DOORWAY NEXT TO THE REAR
 EXIT BLOCKS THE REAR EXIT, WILL NEED TO SWING INTO THE
 RESTROOM, SHOW COMPLIANCE WITH SECTION 2010 FBC-B
 1008.1.9.11 DURING ITS SWING, ANY DOOR IN A MEANS OF
 EGRESS SHALL LEAVE UNOBSTRUCTED AT LEAST ONE HALF OF
 THE REQUIRED WIDTH OF AN CORRIDOR, PASSAGEWAY OR
 LANDING, NOR PROJECT MORE THAN 7 INCHES INTO THE
 REQUIRED WIDTH OF CORRIDOR OR PASSAGEWAY.
  
 3) SHEET A-1 SHOWS A NEW GLASS STOREFRONT WINDOWS AND
 SET OF DOUBLE DOORS. PLEASE PROVIDE THE WIND DESIGN
 CRITERIA.
  
 WIND DESIGN CRITERIA
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
  
  
 3.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 3.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 3.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 3.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 3.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2).
  
 4) COMPONENTS & CLADDING/ 2010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 5) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6) PLEASE PROVIDE ENERGY CALCULATIONS FOR THE NEW
 ADDITION. PROVIDE COMPLIANCE FOR THE SHGC OF THE
 GLAZING COMPLY WITH FBC-ENERGY TABLE 502.1.1.1(1) OR
 TABLE 502.1.1.1(2).
  
 7) SHEET A-1 SHOWS ELEVATED PEDICURE STATIONS AND A
 DETAIL 1 OF SHEET A-2. PLEASE SHOW COMPLIANCE WITH
 FBC-ACCESSIBILITY, VERTICAL ACCESSIBILITY TO PEDICURE
 STATIONS. 201.1.1.
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2015-11-30 Cont ID  
Sent By albarran Date 2015-11-30 Time 15:37 Rev Time 0.00
Received By albarran Date 2015-11-30 Time 14:00 Sent To I
Notes
2015-11-30 15:45:30PER A TELEPHONE CONVERSATION WITH DEVEREN PETERKIN, WE
 AGREED THAT THERE IS A MISSING EMERGENCY LIGHT IN THE
 ELECTRICAL ROOM AND THE MISSING SIGN OUTLETS FOR THE
 REAR DOORS. SINCE ALL OTHER TRADES WERE APPROVED, I
 TOLD MR. PETERKIN THAT AS LONG AS WE AGREED TO GET
 THESE ITEMS DONE, I WOULD APPROVE MY REVIEW WITH THE
 EXCEPTION/PROVISO THAT THESE BE DONE FOR INSPECTION.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2015-10-28 Cont ID  
Sent By albarran Date 2015-10-28 Time 12:37 Rev Time 0.00
Received By albarran Date 2015-10-28 Time 09:37 Sent To I
Notes
2015-10-28 14:01:24THE FAILURE TO PROVIDE A NARRATIVE OF THE CORRECTIONS
 AS REQUIRED PROMPTED FOR A COMPLETE REVIEW OF THE
 PLANS. THIS REVIEW PROVED THAT THE PREVIOUS COMMENTS
 WERE NOT FULLY ADDRESSED. BELOW ARE THE RESULTS OF THE
 THIRD REVIEW
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2008 EDITION
 OF THE NEC, (NATIONAL ELECTRICAL CODE); 2010 EDITION OF
 THE FBC, (FLORIDA BUILDING CODE) AS APPLICABLE AND
 BELOW ARE THE DEFICIENCIES NOTED.
 1. FOR SAFE EMERGENCY EGRESS, AN EMERGENCY LIGHT SHALL
 BE INSTALLED IN THE ELECTRICAL ROOM. AN ADDITIONAL
 EMERGENCY LIGHT SHALL BE INSTALLED IN THE HAIR WASH
 AREA, AND ANY OTHER AREA AS REQUIRED BY CODE.
 2. PER NFPA 101 SECTION 7.10.1.5.1 ALL EXITS SHALL BE
 MARKED WITH APPROVED READILY VISIBLE SIGNS. THE WAY
 TOWARDS THE EXITS, IF NOT READILY APPARENT SHALL BE
 MARKED AS WELL.
 3. NEC 1101.26(D) REQUIRES THAT PROPER ILLUMINATION BE
 PROVIDED FOR ALL WORKING SPACES ABOUT ELECTRICAL
 PANELS. THE AREA IN FRONT OF ELECTRICAL PANEL ?A? IS
 LACKING SAFE WORKING ILLUMINATION.
 4. FBC-ENERGY CONSERVATION SECTION 502.3.8 REQUIRES
 THAT ALL RECESSED LIGHTING INSTALLED IN THE BUILDING
 ENVELOPE SHALL BE IC PROTECTED AND AIR-TIGHT RATED &
 SEALED TO PREVENT AIR LEAKAGE BETWEEN THE CONDITIONED
 AND UNCONDITIONED SPACE.
 5. NEC 422.52 REQUIRES THAT THE ELECTRIC WATER COOLER
 BE CONNECTED TO A GFCI PROTECTED CIRCUIT.
 6. NEC 600.5 REQUIRES THAT EVERY COMMERCIAL OCCUPANCY
 BE PROVIDED WITH A DEDICATED 20 AMP CIRCUIT FOR SIGN OR
 OUTLINE LIGHTING AT EACH PEDESTRIAN ENTRANCE.
 7. NEC 422.30(B) REQUIRES THAT THERE BE A DISCONNECT
 FOR THE 80 GAL STORAGE WATER HEATER.
 8. THE 5TH ED. 2014 FBC-ENERGY CONSERVATION SECTION 505
 HAS SPECIFIC REQUIREMENTS FOR COMMERCIAL LIGHTING WHICH
 SHALL BE ADHERED TO. IN ADDITION TO THE LIGHT DENSITY
 CHART, THERE ARE MANDATORY SWITCHING REQUIREMENTS WHICH
 SHALL BE PROVIDED.
 9. YOU SHALL PROVIDE SITE SPECIFIC LOAD CALCS IN
 ACCORDANCE TO NEC 220 PART III. YOUR LOAD CALCS AS
 SUBMITTED DO NOT MATCH THE PANEL ESTIMATED LOADS.
 10. INDICATE THE LOCATION OF THE HVAC EQUIPMENT ON THE
 ELECTRICAL FLOOR PLAN. YOU DO NOT HAVE ANY HVAC
 DRAWINGS OR SPECIFICATIONS ON THE PLANS.
 THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN
 MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED
 FOR ANOTHER REVIEW.
 WHEN RESUBMITTING, YOU ARE REQUIRED TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ACCOMPANIED WITH
 THE STANDARD CITY RE-SUBMITTAL FORM.
 PLEASE, ADDITIONALLY, INSERT CORRECTED PAGES INTO THE
 SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY
 APPRECIATED.
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 PURSUANT TO FS553.80, THE 4TH SUBMITTAL FOR A PERMIT
 WHICH REFLECTS FAILURE TO CORRECT A DEFICIENCY
 PREVIOUSLY SPECIFICALLY AND CONSISTENTLY IDENTIFIED ON
 ALL PRIOR SUBMITTALS MUST RESULT IN THE ASSESSMENT OF A
 PENALTY OF 3 TIMES THE PLAN REVIEW FEE IN ADDITION TO
 THE NORMAL FEE.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-09-16 Cont ID  
Sent By albarran Date 2015-09-16 Time 19:02 Rev Time 0.00
Received By albarran Date 2015-09-16 Time 17:32 Sent To  
Notes
2015-09-16 19:03:05PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. FOR SAFE EMERGENCY EGRESS, AN EMERGENCY LIGHT SHALL
 BE INSTALLED IN THE ELECTRICAL ROOM. AN ADDITIONAL
 EMERGENCY LIGHT SHALL BE INSTALLED IN THE HAIR WASH
 AREA.
 2. NEC 422.52, REQUIRES THAT THE ELECTRIC WATER COOLER
 BE CONNECTED TO A GFCI PROTECTED CIRCUIT.
 3. NEC 600.5, REQUIRES THAT EVERY COMMERCIAL OCCUPANCY
 BE PROVIDED WITH AT LEAST ONE OUTLET IN AN ACCESSIBLE
 LOCATION AT EACH ENTRANCE A DEDICATED 20 AMP CIRCUIT
 FOR SIGN OR OUTLINE LIGHTING
 4. NEC 422.30(B), REQUIRES THAT THERE BE A DISCONNECT
 FOR THE 80 GAL STORAGE WATER HEATER.
 5. NEC 210.70 (A)(2), REQUIRES THAT THE STAIRWAY BE
 ILLUMINATED AND THE LIGHT BE CONTROLLED BY A WALL
 SWITCH.
 6. THE 5TH ED. 2014 FBC-ENERGY CONSERVATION SECTION 505
 HAS SPECIFIC REQUIREMENTS FOR COMMERCIAL LIGHTING WHICH
 SHALL BE ADHERED TO.
 7. IN VARIOUS PLACES THROUGHOUT THE NOTES DIFFERENT
 NON-BINDING EDITIONS OF THE NEC ARE QUOTED. PLEASE
 CORRECT THE NOTES TO ADDRESS THE 2011 EDITION OF THE
 NEC.
 8. FIRE ALARM WORK, EVEN THOUGH SHALL BE UNDER A
 SEPARATE PERMIT AND SHOP DRAWING, SHALL BE DESIGNED TO
 COMPLY WITH NFPA 72, 2010 EDITION NOT THE NFPA 96.
 9. YOU SHALL INDICATE ON THE ELECTRICAL RISER DIAGRAM
 WHAT PORTIONS OF IT PERTAIN TO THIS SPECIFIC PROJECT,
 AND INDICATED THE CONDUCTOR SIZING FOR THE APPLICABLE
 PANELS.
 10. THE PANEL SCHEDULES AS PRESENTED DO NOT MATCH THE
 FLOOR PLAN MARKINGS AND CIRCUIT DESIGNATIONS.
 11. ACCORDING TO THE MARKINGS ON THE PANEL DESIGNATOR
 THIS IS A 3 PHASE SERVICE CONTRARY TO THE LAYOUT OF THE
 PANELS. CORRECT ACCORDINGLY.
 12. ACCORDING TO THE SAME PANEL DESIGNATOR, ALL PANELS
 ARE BOTTOM FED. IF THE FEEDERS ARE COMING FROM
 UNDERGROUND, CONDUCTOR INSULATION SHALL BE RATED FOR
 WET LOCATIONS AS INDICATED IN NEC 300.5 (B) AND THE
 ENDS OF THE RACEWAY SEALED ACCORDING TO NEC 300.5(G).
 13. YOU SHALL PROVIDE SITE SPECIFIC LOAD CALCS IN
 ACCORDANCE TO NEC 220 PART III.
 14. INDICATE THE LOCATION OF THE HVAC EQUIPMENT. YOU DO
 NOT HAVE ANY HVAC DRAWINGS OR SPECIFICATIONS ON THE
 PLANS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-07-10 Cont ID  
Sent By dhayes Date 2015-07-10 Time 10:08 Rev Time 0.00
Received By dhayes Date 2015-07-10 Time 10:05 Sent To  
Notes
2015-07-10 10:36:057/10/2015
 PROJECT: NAIL SALON
 PERMIT#: 15060791
 CODE: 2011EDITION OF THE NEC, FIFTH EDITION OF THE FBC
 , WPB AMENDMENTS TO THE FBC, CHAPTER 1, ADMINISTRATION,
 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) ACCESS TO EXITS SHALL BE MARKED BY APPROVED, READILY
 VISIBLE SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO
 REACH THE EXIT IS NOT READILY APPARENT TO THE
 OCCUPANTS. NFPA 101 SECTION 7.10.1.5.1
  
 2) EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED
 MEANS OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, AND
 ALL OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE
 REQUIRED ILLUMINATION. EMERGENCY LIGHTING SYSTEMS SHALL
 BE DESIGNED AND INSTALLED SO THAT THE FAILURE OF ANY
 INDIVIDUAL LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF
 A LAMP, CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT
 REQUIRES EMERGENCY ILLUMINATION. NEC 700.16
  
 3) THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL
 BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES. THE BRANCH CIRCUIT THAT FEEDS UNIT EQUIPMENT
 SHALL BE CLEARLY IDENTIFIED AT THE DISTRIBUTION PANEL.
 EMERGENCY LUMINAIRES THAT OBTAIN POWER FROM A UNIT
 EQUIPMENT AND ARE NOT PART OF THE UNIT EQUIPMENT SHALL
 BE WIRED TO THE UNIT EQUIPMENT AS REQUIRED BY 700.9 AND
 BY ONE OF THE WIRING METHODS OF NEC CHAPTER 3. NEC
 700.12(F)
  
 4) PLEASE INDICATE COMPLIANCE WITH FBC-ENERGY.
 ELECTRICAL POWER AND LIGHTING SYSTEMS. (MANDATORY)
 SECTION 505
  
 5) RECESSED LUMINAIRES INSTALLED IN THE BUILDING
 THERMAL ENVELOPE SHALL BE IC AND AIR TIGHT RATED AND
 SEALED TO LIMIT AIR LEAKAGE BETWEEN CONDITIONED AND
 UNCONDITIONED SPACES. FBC-E 502.3.8 RECESSED LIGHTING.
  
 6) AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED
 WITHIN 450 MM (18 IN.) OF THE TOP OF SHOW WINDOW FOR
 EACH 3.7 LINEAR M (12 LINEAR FT) OR MAJOR FRACTION
 THEREOF OF SHOW WINDOW AREA MEASURED HORIZONTALLY AT
 ITS MAXIMUM WIDTH. NEC 210.62
  
 7) EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS
 SHALL BE PROVIDED WITH AT LEAST ONE OUTLET SUPPLIED BY
 A BRANCH CIRCUIT RATED AT LEAST 20 AMPERES THAT
 SUPPLIES NO OTHER LOAD. NEC 600.5
  
 8) BOXES LISTED SPECIFICALLY FOR THIS APPLICATION SHALL
 BE USED FOR RECEPTACLES LOCATED IN THE FLOOR. NEC
 314.27(C)
  
 9) PROVIDE PRODUCT APPROVALS FOR THE WATER HEATER AND
 INDICATE THE APPROPRIATE SIZE CIRCUIT AND DISCONNECT
 REQUIRED. NEC 422.31
  
 10) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR FIRE ALARM, ACCESS CONTROL SYSTEM,
 SECURITY, CCTV, AUDIO/VIDEO, NETWORK, DATA, AND,
 COMMUNICATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-09-03 Cont ID  
Sent By pleduc Date 2015-09-03 Time   Rev Time 0.00
Received By pleduc Date 2015-09-03 Time 11:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-06-22 Cont ID  
Sent By pleduc Date 2015-06-22 Time   Rev Time 0.00
Received By pleduc Date 2015-06-22 Time 13:41 Sent To  
Notes
2015-06-22 14:08:52THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF
 THE 5TH EDITION OF FLORIDA FIRE PREVENTION CODE
 INCLUDING THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND
 ALL OTHER APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 2) A DOOR SCHEDULE, INCLUDING HARDWARE IS NOT PROVIDED.
  
 3) THE BATHROOM DOOR OPENS AND RESTRICTS THE MEANS OF
 EGRESS. IT SHALL SWING INTO THE BATHROOM. NFPA 101
 CHAPTER 7, MEANS OF EGRESS
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY
 OPEN.
  
 4) AN EXIT LIGHT SHALL BE INSTALLED AT THE REAR DOOR.
  
 5) AN EXIT LIGHT SHALL BE INSTALLED LEADING INTO THE
 REAR EXIT CORRIDOR.
  
 6) THE NATURE OF THE REMODE, IF EXISTING,L REQUIRES AN
 EVALUATION OF THE FIRE ALARM AND SPRINKLER SYSTEM FOR
 CODE COVERAGE AND COMPLIANCE. ANY REMOVAL AND/OR
 CONSTRUCTION OF WALLS REQUIRES AN EVALUATION. PLEASE
 PROVIDE A NOTE INDICATING ANY EXISTING SYSTEM(S).
 IF EXISTING, THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR
 FIRE SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 IF INDICATED, ANY AND ALL WORK ON THE FIRE ALARM AND
 FIRE SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE
 SHOP DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-11-30 Cont ID  
Sent By albarran Date 2015-11-30 Time 16:05 Rev Time 0.00
Received By albarran Date 2015-11-12 Time 10:00 Sent To  
Notes
2015-11-30 16:08:1811/30/15 ELECTRIC APPROVED WITH THE FOLLOWING PROVISO:
 ELECTRICAL PROVISO TO PERMIT 15090791 1. INSTALL
 EMERGENCY LIGHT IN ELECTRIC ROOM 2. INSTALL THE MISSING
 SIGN OUTLETS FOR THE REAR ENTRIES AS REQUIRED IN NEC
 600.5 PER CONVERSATION W/MR. PETERKIN. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT TO LARGE READY BIN "H." MA
  
2015-11-13 10:01:00RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-10-28 Cont ID  
Sent By albarran Date 2015-10-28 Time 14:03 Rev Time 0.00
Received By albarran Date 2015-10-06 Time 13:00 Sent To  
Notes
2015-10-28 14:04:0910/28/15 FAILED ELECTRICAL PLAN REVIEW FOR A THIRD
 TIME. NOTICE OF ADDITIONAL FEE FOR FAILING NEXT REVIEW
 WAS MADE ON FRONT SCREEN AND TO CUSTOMER VIA EMAIL WHEN
 NOTIFIED OF FAILED STATUS. SENT TO LARGE DENIED BIN
 "H". MA
2015-10-07 13:00:39C33

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-09-21 Cont ID  
Sent By jwitmer Date 2015-09-21 Time 14:39 Rev Time 0.00
Received By jwitmer Date 2015-09-02 Time 15:44 Sent To  
Notes
2015-09-02 15:45:27C36

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-10 Cont ID  
Sent By dhayes Date 2015-07-10 Time 10:36 Rev Time 0.00
Received By dhayes Date 2015-06-18 Time 14:00 Sent To  
Notes
2015-06-18 14:01:26INCOMING SENT TO C-35 BOX.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2015-10-19 Cont ID  
Sent By jwitmer Date 2015-10-19 Time 14:59 Rev Time 0.00
Received By jwitmer Date 2015-10-19 Time 14:59 Sent To  
Notes
2015-10-19 15:02:19IMPACT FEES
 MU-2015-022185-0000
 REC:2015-0922-182
 FEES PAID: $142.67
 J. WITMER

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-09-21 Cont ID  
Sent By   Date 2015-09-21 Time   Rev Time 0.00
Received By   Date 2015-09-21 Time   Sent To  
Notes
2015-09-21 14:39:272ND REQUEST, ADDITIONAL SQUARE FOOTAGE ADDED. BEFORE A
 PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE
 PAID TO PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF
 PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE
 PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE
 CALL (561)233-5025 FOR MORE INFORMATION.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-06-22 Cont ID  
Sent By jwitmer Date 2015-06-22 Time 06:12 Rev Time 0.00
Received By jwitmer Date 2015-06-22 Time 06:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2015-11-19 Cont ID  
Sent By ccole Date 2015-11-19 Time 11:51 Rev Time 0.00
Received By ccole Date 2015-11-19 Time 11:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2015-10-27 Cont ID  
Sent By ccole Date 2015-10-27 Time 16:09 Rev Time 0.00
Received By ccole Date 2015-10-27 Time 16:09 Sent To  
Notes
2015-10-27 16:30:223RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #15060791
 10/27/15
  
 1) PROVIDE EQUIPMENT SCHEDULES ON THE PLANS FOR THE
 INTAKE AND EXHAUST FANS INCLUDING MAKES AND MODELS, CFM
 CAPACITIES, ELECTRICAL DATA ETC.
 2) THE MECHANICAL DAMPERS SHOWN ON THE EXTRERIOR WALLS
 COVERING THE FANS MUST BE WIND AND WATER RESISTANT- SEE
 SECTIONS 401.5 AND 501.2.2 FBC-10 MECHANICAL AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS THAT INDICATE COMPLIANCE.
 3) PLEASE REFER TO SECTION 1609.1.2 (PROTECTION OF
 OPENINGS) AND 1609.6.4.4.1 (COMPONENTS AND CLADDING)
 FBC-10 BUILDING, AND PROVIDE TWO COPIES OF FLORIDA
 PRODUCT APPROVALS OR MIAMI-DADE NOA'S FOR THE DAMPERS-
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3.
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 FLEXIBLE EXHAUST HOSES. REFER TO SECTION 501.4: EXHAUST
 DUCTS SHALL BE OF METAL AND SUCH CONSTRUCTION SHALL
 COMPLY WITH CHAPTER 6 FBC-10 MECHANICAL. PLEASE NOTE
 THAT THIS SECTION DOES NOT RESTRICT THE USE OF
 ALTERNATE MATERIALS IF LISTED AND LABELED FOR THE USE
 SPECIFIED ON THE PLAN.
 5) IT APPEARS THAT THE EXHAUST DISCHARGE AT THE REAR OF
 THE BUILDING IS WITHIN THE MINIMUM 10 FT. REQUIRED
 CLEARANCE DISTANCE TO THE REAR DOOR OPENING- REFER TO
 SECTION 501.2.1 FBC-10 MECHANICAL AND INDICATE
 COMPLIANCE.
 6) INDICATE THE CLEARANCE DISTANCE MEASUIREMENT FROM
 THE NEW AIR INTAKE AT THE REAR OF THE BUILDING TO THE
 PARKING LOT AND DRIVE AREAS- REFER TO SECTION 401.4 AND
 401.4.1 FBC-10 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-09-09 Cont ID  
Sent By ccole Date 2015-09-09 Time 08:19 Rev Time 0.00
Received By ccole Date 2015-09-09 Time 08:19 Sent To  
Notes
2015-09-09 08:29:552ND REVIEW: FBC 2010 MECHANICAL
 PERMIT #15060791
 9/9/2015
  
 1) COMMENT #1 FROM THE 1ST REVIEW STILL EXISTS.
 ALTHOUGH THE REVISED PLAN DOES SHOW A NEW EXHAUST FAN,
 THE LOCATION OF THE FAN DOES NOT COMPLY WITH FOOTNOTE H
 UNDER TABLE 403.3 FBC-10 MECHANICAL WHICH REQUIRES
 CONTAMINANTS AND ODORS TO BE CAPTURED AT THEIR SOURCES.
 I AM RE-PRINTING THE COMMENT HERE FOR REVIEW:
 (AN EXHAUST VENTILATION SYSTEM DESIGNED IN ACCORDANCE
 WITH TABLE 403.3 FBC-20 MECHANICAL IS REQUIRED FOR THE
 NEW NAIL SALON. PLEASE REFER TO FOOTNOTES B AND H AT
 THE BOTTOM OF THE TABLE FOR SPECIFIC REQUIREMENTS FOR
 NAIL SALONS: B) MECHANICAL EXHAUST IS REQUIRED AND THE
 RECIRCULATION OF AIR FROM SUCH SPACES IS PROHIBITED
 (SEE SECTION 403.2.1, ITEM 3: WHERE MECHANICAL EXHAUST
 IS REQUIRED BY NOTE B IN TABLE 403.3, RECIRCULATION OF
 AIR FROM SUCH SPACES SHALL BE PROHIBITED. ALL AIR
 SUPPLIED TO SUCH SPACES SHALL BE EXHAUSTED, INCLUDING
 ANY AIR IN EXCESS OF THAT REQUIRED BY TABLE 403.3). H)
 FOR NAIL SALONS, THE REQUIRED EXHAUST SHALL INCLUDE
 VENTILATION TABLES OR OTHER SYSTEMS THAT CAPTURE THE
 CONTAMINANTS AND ODORS AT THEIR SOURCE AND ARE CAPABLE
 OF EXHAUSTING A MINIMUM OF 50 CFM PER STATION. THIS
 REQUIREMENT APPLIES TO BOTH MANICURE AND PEDICURE
 STATIONS. PLEASE REVISE THE PLANS ACCORDINGLY.) IN
 ORDER FOR THE SALON TO BE IN COMPLIANCE, EXHAUST INLETS
 MUST BE PLACED AT EVERY MANICURE TABLE AND PEDICURE
 STATION IN THE FACILITY, AND MAKE-UP AIR MUST BE
 PROVIDED AT THESE LOCATIONS FOR THE EXHAUST. THE SYSTEM
 MUST BE INDEPENDENT OF THE MAIN HVAC SYSTEM, AND MUST
 BE DESIGNED TO BE AIR IN/ AIR OUT WITH NO RECIRCULATION
 OF EXHAUST.
 2) PLEASE REVISE THE OUTDOOR AIR CALCULATIONS ON SHEET
 A-2 TO INCLUDE THE EXHAUST CFM'S PER SQ. FT., AND
 PROVIDE AN AIR BALANCE CALCULATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-07-09 Cont ID  
Sent By ccole Date 2015-07-09 Time 16:08 Rev Time 0.00
Received By ccole Date 2015-07-09 Time 16:08 Sent To  
Notes
2015-07-09 16:35:161ST REVIEW: FBC 2010 MECHANICAL
 PERMIT #15060791 7/9/15
  
 1) AN EXHAUST VENTILATION SYSTEM DESIGNED IN ACCORDANCE
 WITH TABLE 403.3 FBC-20 MECHANICAL IS REQUIRED FOR THE
 NEW NAIL SALON. PLEASE REFER TO FOOTNOTES B AND H AT
 THE BOTTOM OF THE TABLE FOR SPECIFIC REQUIREMENTS FOR
 NAIL SALONS: B) MECHANICAL EXHAUST IS REQUIRED AND THE
 RECIRCULATION OF AIR FROM SUCH SPACES IS PROHIBITED
 (SEE SECTION 403.2.1, ITEM 3: WHERE MECHANICAL EXHAUST
 IS REQUIRED BY NOTE B IN TABLE 403.3, RECIRCULATION OF
 AIR FROM SUCH SPACES SHALL BE PROHIBITED. ALL AIR
 SUPPLIED TO SUCH SPACES SHALL BE EXHAUSTED, INCLUDING
 ANY AIR IN EXCESS OF THAT REQUIRED BY TABLE 403.3). H)
 FOR NAIL SALONS, THE REQUIRED EXHAUST SHALL INCLUDE
 VENTILATION TABLES OR OTHER SYSTEMS THAT CAPTURE THE
 CONTAMINANTS AND ODORS AT THEIR SOURCE AND ARE CAPABLE
 OF EXHAUSTING A MINIMUM OF 50 CFM PER STATION. THIS
 REQUIREMENT APPLIES TO BOTH MANICURE AND PEDICURE
 STATIONS. PLEASE REVISE THE PLANS ACCORDINGLY.
 2) THE SUBMITTED PLAN SHOWS A NEW O/A INTAKE PROVIDING
 680 CFM TO THE AHU. PROVIDE A VENTILATION CALCULATION
 IN ACCORDANCE WITH TABLE 403.3 TO VERIFY THE MINIMUM
 RATE COMPLIANCE.
 3) INDICATE ON THE PLAN THE AIR INTAKE OPENING WILL BE
 LOCATED TO MEET OR EXCEED THE REQUIRED CLEARANCE
 DISTANCES OUTLINED IN SECTION 401.4.1, AND THE OPENING
 WILL BE PROTECTED IN COMPLIANCE WITH 401.5. PROVIDE TWO
 COPIES OF A FLORIDA PRODUCT APPROVAL OR MIAMI-DADE NOA
 FOR THE INTAKE LOUVER.
 4) A COMPLETE REVIEW OF THE PROJECT CANNOT BE COMPLETED
 AT THIS TIME DUE TO THE LACK OF DETAILS ON THE
 SUBMITTED PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-10-14 Cont ID  
Sent By gjohnson Date 2015-10-14 Time 14:11 Rev Time 0.00
Received By gjohnson Date 2015-10-14 Time 14:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-09-10 Cont ID  
Sent By gjohnson Date 2015-09-10 Time 14:09 Rev Time 0.00
Received By gjohnson Date 2015-09-10 Time 14:09 Sent To  
Notes
2015-09-10 14:12:221ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 561-805-6711
 [email protected]
  
  
  
 PLUMBING COMMENTS:
 .
 1.WATER FOUNTAIN S SHALL COMPLY WITH FBC ACC. SEC.
 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.7
 2. PROVIDE INFORMATION AND MANUFACTURE SPEC SHEETS ON
 THE PEDICURE CHAIRS. DELETING THEM OFF PLUMBING PLAN
 DOES NOT COMPLY WE NEED TO SEE HOW THEY WORK .
 WPB AMEND. 107.2.1

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-06-20 Cont ID  
Sent By tklarge Date 2015-06-20 Time 06:46 Rev Time 0.00
Received By tklarge Date 2015-06-20 Time 05:10 Sent To  
Notes
2015-06-20 06:39:011) SHT. A-1 - IDENTIFY THE ROOM WITH THE SINK THAT IS
 LOCATED NEAR THE HAIR WASH SINKS. WPB AMEND.TO 2010 FBC
 SEC. 107.2.1.
 2) A DRINKING FOUNTAIN IS REQUIRED IN A BUSINESS
 OCCUPANCY PER TABLE 403.1 OF THE 2010 FPC. NO FEWER
 THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED IN
 ACCORDANCE WITH THE 2010 FL. ACCESSIBILITY CODE SEC.
 211.2 & FOOTNOTE # E OF TABLE 403.1 OF FPC.
 3) ONE HAIR WASH SINK SHALL BE ACCESSIBLE PER SEC.212
 OF FL. ACCESSIBILITY CODE.
 4) SHT. A-3 - WATER HEATER DETAIL - THE RELIEF LINE
 SHALL DISCHARGE THROUGH AN AIR GAP LOCATED IN THE SAME
 ROOM AS THE WATER HEATER PERR 2010 FPC SEC. 504.6
 (2).THE PLAN SHOWS IT DISCHARGING TO THE EXTERIOR.
 5) IDENTIFY THE ACCESSIBLE RESTROOM ON THE FLOOR PLAN
 AND CLEARLY SHOW THE DIMENSIONS. (L X W). *5 INCHES IS
 THE MINIMUM WIDTH IF BUILT PERFECT, 86 INCHES ALLOWS
 FOR TOLERANCES.
 6) GRAB BARS SHALL BE MEASURED FORM THE FINISH FLOOR TO
 THE TOP OF THE GRIPPING SURFACE PER THE 2010 FAC SEC.
 609.4.
 7) SHT. P-2 - THE PEDICURE CHAIRS ARE NOT VENTED. 201
 FPC SEC.901.2.1.
 8) IF THE PEDICURE CHAIRS ARE GOING TO BE WET VENTED
 THE MAXIMUM NUMBER OF FIXTURE UNITS ON A HORIZONTAL WET
 VENT SHALL COMPLY WITH TABLE 909.3 OF 2010 FPC.
 9) SIZE THE LOOP VENT FOR THE HAIR SINKS. COMPLY WITH
 2010 FPC SEC. 916.1 & TABLE 916.1.
 10) CLEANOUTS ARE REQUIRED IN STACKS PER 2010 FPC
 SEC.708.3.4.
 11) SIZE ALL SECTIONS OF THE BUILDING DRAIN PER TABLE
 710.1 (1).
 12) SHT. P-2 CALLS OUT THE ADA BATH AS NEW & SHT. P-1
 NOTES IT AS EXISTING. CLARIFY.
 13) SHOW THE REQUIRED SHUTOFF VALVES TO THE PLUMBING
 FIXTURES PER 2010 FPC SEC.606.1, 606.2.
 14) SHT. P-2 - SHOW THE LOCATION WHERE THE WATER SUPPLY
 ENTERS THE STRUCTURE. WPB AMEND. TO 2010 FPC
 107.3.5.1.3.
 15) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS SHEETS AND INSRTALLATION MANUAL FOR THE
 PEDICURE CHAIRS.
 WPB AMEND.TO 2010 FBC SEC. 107.2.1.
 16) THE PLANS NOTE THAT THE APPLICABLE CODES ARE THE
 2014 FBC. THE CODE IN EFFECT FOR THIS PERMIT IS THE
 2010 FBC. CLARIFY.
 17) SHT. A-1 - NOTES THAT THE OCCUPANCY IS BASED ON AN
 AREA NOTED AS SALES AREA. THE TYPE OF OCCUPANCY FOR A
 NAIL SALON WOULD BE A BUSINESS OCCUPANCY. THE OCCUPANT
 LOAD WOULD BE 100 SQ. FT. PER PERSON BUT THE PLAN NOTES
 60 SQ. FT. PER PERSON. CLARIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  