| 2015-06-22 09:41:21 | 6/22/2015 |
| | PROJECT: PNC BANK SECURITY AND CCTV |
| | PERMIT#: 15060747 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED. |
| | |
| | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | 1) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN WPB AMENDMENTS TO |
| | FBC SECTION 107.2.1 |
| | 1A) THE SUBMITTED PLANS ARE PHOTOCOPIED PLANS OF AN |
| | ORIGINAL SIGNED AND SEALED PLAN. PLANS, SPECIFICATIONS, |
| | REPORTS OR OTHER DOCUMENTS PREPARED BY THE DESIGN |
| | PROFESSIONAL AND BEING FILED FOR PUBLIC RECORD SHALL |
| | HAVE THE SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL |
| | AFFIXED TO THE DOCUMENT. |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS |
| | |
| | 2) PROVIDE TWO COPIES OF ALL PLANS AND SPECIFICATIONS |
| | FOR SUBMITTAL WITH AN APPLICATION FOR PERMIT. ONE COPY |
| | TO BE REATAINED FOR PUBLIC RECORD AND THE OTHER TO BE |
| | RELEASED BACK TO THE CONTRACTOR FOR INSTALLATION AND |
| | INSPECTION PURPOSES. WPB AMENDMENTS TO FBC SECTION |
| | 107.3.1. |
| | |
| | 3) PROVIDE SUPPORTING DOCUMENTATION SUCH AS A CONTRACT |
| | EQALLING THE STATED VALUE FOR THIS SCOPE OF WORK. FOR |
| | PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS |
| | SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT . WPB AMENDMENTS |
| | TO FBC SECTION 109.3 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |