Plan Review Details - Permit 15060724
Plan Review Stops For Permit 15060724
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-06 Cont ID  
Sent By rmcdouga Date 2015-08-06 Time 15:37 Rev Time 0.00
Received By rmcdouga Date 2015-08-04 Time 19:17 Sent To  
Notes
2015-08-06 11:38:51PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE NOTE ON SHEET A4 STATES THAT THE EXISTING
 SECTIONAL GARAGE DOOR IS TO REMAIN TO IN ORDER TO
 SATISFY HISTORIC PRESERVATION REQUIREMENTS. IT APPEARS
 FROM THE WALL SECTION ON A4 THAT A NEW EXTERIOR FALSE
 WALL IS PROPOSED TO BE CONSTRUCTED IN FRONT WITH THE
 GARAGE DOOR ATTACHED TO IT. THE FLOOR PLAN, THE WALL
 SECTION AND THE ELEVATION SHOW A WINDOW AT THIS
 LOCATION. PLEASE CLARIFY. FBC 107.2.1
  
 2) THE WALL LEGEND ON SHEET A-3 IS INCONSISTENT WITH
 THE REST OF THE PLANS. PLEASE REVISE IT TO CORRESPOND
 WITH THE REST OF THE PLANS. FBC 107.2.1
  
 3) THE ENERGY COMPLIANCE FORM LISTS THE GARAGE EXTERIOR
 WALLS AS CONCRETE BLOCK WITH R-5 INSULATION AND THE
 PLANS HAVE EXTERIOR WOOD WALLS WITH R-3 SPRAYED
 CELLULOSE INSULATION. THE 2 X 6 WOOD FRAME WALLS SHOULD
 HAVE R-19 INSULATION. THE PLANS ARE REQUIRED TO SHOW
 COMPLIANCE WITH THE ENERGY CODE. THE ENERGY FORMS ARE
 REQUIRED TO REFLECT WHAT IS SHOWN ON THE PLANS. FBC
 107.2.1 & SECTION 401.2 OF THE ENERGY CODE.
  
 4) SHOW THE EGRESS WINDOW LOCATION ON THE PLANS AND
 SPECIFY THE WINDOW TYPES AND SIZES. FBC 107.1 & R310
  
 5) PROVIDE A WINDOW SCHEDULE FOR WINDOWS A AND B THAT
 ARE SHOWN ON SHEET A-3 AND SPECIFY THE TYPES AND SIZES.
 FBC 612
  
 6) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 NEW WINDOWS THAT HAVE BEEN REVIEWED AND APPROVED BY THE
 DESIGNER OF RECORD FOR THE PROJECT. DCA RULE 9N-3 AND
 FBC 107.3.4.1
  
 7) PROVIDE A BUCK DETAIL FOR THE WINDOWS. FBC-R612.10.2
  
 8) THERE DOES NOT APPEAR TO BE THE 21 INCHES OF
 CLEARANCE IN FRONT OF THE WATER CLOSET IN THE NEW
 BATHROOM. FBC-R307.1
  
 9) FBC-R703.6.3 WHERE CEMENT PLASTER (STUCCO) IS TO BE
 APPLIED TO LATH OVER FRAME CONSTRUCTION, MEASURES SHALL
 BE TAKEN TO PREVENT BONDING BETWEEN THE CEMENT PLASTER
 AND THE WATER-RESISTIVE BARRIER. A BOND BREAK SHALL BE
 PROVIDED BETWEEN THE WATER-RESISTIVE BARRIER AND THE
 CEMENT PLASTER (STUCCO) CONSISTING OF ONE OF THE
 FOLLOWING:
 1. TWO LAYERS OF AN APPROVED WATER-RESISTANT BARRIER
 MATERIAL; OR
 2. ONE LAYER OF AN APPROVED WATER-RESISTANT BARRIER
 OVER AN APPROVED PLASTIC HOUSE WRAP; OR
 3. OTHER APPROVED METHODS OR MATERIALS APPLIED IN
 ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS.
  
 10) FBC-R704 INSPECTION FOR TERMITES
 IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE
 INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS
 AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING
 SHALL NOT BE LESS THAN 6 INCHES (152 MM).
 EXCEPTIONS:
 3. A 4-INCH (102 MM) INSPECTION SPACE ABOVE PATIO AND
 GARAGE SLABS AND ENTRY AREAS.
  
 11) FBC- R404.1.6 HEIGHT ABOVE FINISHED GRADE.
 CONCRETE AND MASONRY FOUNDATION WALLS SHALL EXTEND
 ABOVE THE FINISHED GRADE ADJACENT TO THE FOUNDATION AT
 ALL POINTS A MINIMUM OF 4 INCHES (102 MM) WHERE MASONRY
 VENEER IS USED AND A MINIMUM OF 6 INCHES (152 MM)
 ELSEWHERE.
  
 12) THE ENERGY COMPLIANCE FORM IS REQUIRED TO BE SIGNED
 BY THE OWNER/AGENT. FBC ENERGY CONSERVATION SECTION
 405.4
  
 13) THE VALUATION FOR THE WORK ON THE APPLICATION OF
 $2400.00 IS LOW. SUBMIT A COPY OF THE SIGNED CONTRACT.
 FBC 109.3
  
 14) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-07-22 Cont ID  
Sent By albarran Date 2015-07-22 Time 16:53 Rev Time 0.00
Received By albarran Date 2015-07-22 Time 16:00 Sent To  
Notes
2015-07-22 17:25:11PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. CORRECT NOTES #7, 16, 17 & 30 ACCORDINGLY: ROMEX IS
 A BRAND NAME AND NOT A RECOGNIZED CABLE TYPE. USE NM,
 NMC, OR MNS IN PLACE THEREOF.
 2. ALL CEILING MOUNTED LUMINAIRE OUTLETS SHALL BE
 LISTED TO SUPPORT 50 LBS, PER NEC 314.27.
 3.THE LOAD ANALYSIS AS SUBMITTED DOES NOT MATCH WITH
 THE SQUARE FOOTAGE STATEMENT OF PAGE A-2.
 4. CORRECT AND EXPLAIN ON THE RISE DIAGRAM:
 A) WHAT IS CAM AT THE METER.
 B) ROUTE OF RACEWAY BETWEEN METER AND PANEL A. THIS
 WILL DETERMINE THE NEED FOR A MAIN DISCONNECT OUTSIDE.
 5. GROUND SERVICE PER NEC AT METER SOCKET.
 6. INCLUDE ON THE RISER THE INTER-SYSTEM BONDING
 TERMINAL REQUIRED BY NEC 250.94.
 7. IF NOT ALREADY IN PLACE, SMOKE DETECTORS AS PER
 FBC-R 314, WILL BE REQUIRED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2015-07-21 Cont ID  
Sent By fmittner Date 2015-07-21 Time 16:43 Rev Time 0.00
Received By fmittner Date 2015-07-21 Time 16:43 Sent To  
Notes
2015-07-21 16:44:04BASED ON GOOGLE STREETVIEW, WORK IS ALREADY COMPLETED
 AND HAS BEEN FOR SOME TIME.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-06 Cont ID  
Sent By rmcdouga Date 2015-08-06 Time 15:37 Rev Time  
Received By rmcdouga Date 2015-06-17 Time   Sent To  
Notes
2015-06-18 13:30:22R03

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-08-04 Cont ID  
Sent By rmcdouga Date 2015-08-04 Time 19:16 Rev Time 0.00
Received By rmcdouga Date 2015-08-04 Time 19:16 Sent To  
Notes
2015-08-04 19:17:19BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-08-06 Cont ID  
Sent By rmcdouga Date 2015-08-06 Time 07:21 Rev Time 0.00
Received By rmcdouga Date 2015-08-04 Time 19:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-07-16 Cont ID  
Sent By tklarge Date 2015-07-16 Time 12:26 Rev Time 0.00
Received By tklarge Date 2015-07-16 Time 11:58 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-07-21 Cont ID  
Sent By fmittner Date 2015-07-21 Time 16:43 Rev Time 0.00
Received By fmittner Date 2015-07-21 Time 16:43 Sent To  
Notes
***NONE***