Plan Review Details - Permit 15060686
Plan Review Stops For Permit 15060686
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2016-06-01 Cont ID  
Sent By rmcdouga Date 2016-06-01 Time 17:23 Rev Time 0.00
Received By rmcdouga Date 2016-06-01 Time 10:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2016-05-11 Cont ID  
Sent By rmcdouga Date 2016-05-11 Time 10:26 Rev Time 0.00
Received By rmcdouga Date 2016-05-10 Time 17:57 Sent To  
Notes
2016-05-11 10:26:49PLAN
 REVIEW COMMENTS
  
 4TH REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR THE
 STRUCTURAL WINDOW MULLIONS.
  
 2) THE PRODUCT APPROVALS FOR THE MODIFIED ROOFING FOR
 THE SECOND FLOOR COVERED PATIO IS FOR USE OVER
 CEMENTITIOUS WOOD FIBER AND THE PLANS INDICATE THIS AS
 A CDX PLYWOOD DECK. SUBMIT PRODUCT APPROVAL FOR WOOD
 DECK. SIGNED AND SEALED RAS 117 CALCULATIONS WILL ALSO
 BE REQUIRED IF THE DESIGN UPLIFT PRESSURE OF THE
 ASSEMBLY REQUIRES ENHANCED FASTENING IN THE PERIMETER
 AND CORNER AREAS.
  
 3) BOTH SETS OF PLANS ARE MISSING THE STRUCTURAL SHEETS
 A.7, A.8 AND A.9. FBC 107.1
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-01-19 Cont ID  
Sent By rmcdouga Date 2016-01-19 Time 16:14 Rev Time 0.00
Received By rmcdouga Date 2016-01-19 Time 16:14 Sent To E
Notes
2016-01-19 16:19:02PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF
 THE HOP MOPPED 90 LB ROOFING FOR THE BALCONY, THE HARDI
 PLANK SIDING, THE WINDOWS /GLASS TYPES, STRUCTURAL
 MULLIONS, THE SECTIONAL GARAGE DOOR AND ALL EXTERIOR
 DOOR TYPES THAT WILL BE INSTALLED.
  
 2) THE PRODUCT APPROVALS FOR THE GAF ASPHALT ROOF
 SHINGLES (NOA NO. 14-1022.20) ARE REQUIRED TO BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD FOR THE PROJECT. FBC 107.3.4.1
  
 3) THE ENERGY FORMS ARE REQUIRED TO BE SIGNED AND DATED
 BY THE OWNER/AGENT. SEE MECHANICAL COMMENTS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-12-07 Cont ID  
Sent By rmcdouga Date 2015-12-07 Time 16:53 Rev Time 0.00
Received By rmcdouga Date 2015-12-07 Time 15:52 Sent To  
Notes
2015-12-07 16:48:08PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF
 THE HOP MOPPED 90 LB ROOFING FOR THE BALCONY, THE HARDI
 PLANK SIDING, THE WINDOWS /GLASS TYPES, STRUCTURAL
 MULLIONS, THE SECTIONAL GARAGE DOOR AND ALL EXTERIOR
 DOOR TYPES THAT WILL BE INSTALLED.
  
 2) THE PRODUCT APPROVALS FOR THE GAF ASPHALT ROOF
 SHINGLES (NOA NO. 14-1022.20) ARE REQUIRED TO BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD FOR THE PROJECT. FBC 107.3.4.1
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-08-04 Cont ID  
Sent By rmcdouga Date 2015-08-04 Time 18:25 Rev Time 0.00
Received By rmcdouga Date 2015-08-03 Time 18:49 Sent To  
Notes
2015-08-04 14:58:37PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
 THESE PLANS HAVE BEEN REVIEWED AS A SINGLE FAMILY
 RESIDENCE. ADDITIONAL COMMENTS WILL RESULT IF THIS IS
 MEANT TO BE A TWO FAMILY DWELLING.
  
 1) PROVIDE A DRAINAGE PLAN THAT SHOWS COMPLIANCE WITH
 R401.3.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN
 SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE
 SHALL FALL A MINIMUM OF 6 INCHES (152 MM)WITHIN THE
 FIRST 10 FEET (3048 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE
 BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2
 PERCENT AWAY FROM THE BUILDING.
  
 2) THE OCCUPANCY TYPE FOR ONE AND TWO FAMILY DWELLINGS
 IS R-3, NOT R-2 AS SPECIFIED ON SHEET A-1. FBC 310.1
  
 3) THE MINIMUM CONSTRUCTION TYPE FOR THIS STRUCTURE IS
 TYPE V-B. THE SECOND FLOOR EXTERIOR WALLS ARE WOOD
 FRAME, THEREFORE IT IS NOT TYPE II CONSTRUCTION PER FBC
 602.2.
 602.1.1 MINIMUM REQUIREMENTS. A BUILDING OR PORTION
 THEREOF SHALL NOT BE REQUIRED TO CONFORM TO THE DETAILS
 OF A TYPE OF CONSTRUCTION HIGHER THAN THAT TYPE WHICH
 MEETS THE MINIMUM REQUIREMENTS BASED ON OCCUPANCY EVEN
 THOUGH CERTAIN FEATURES OF SUCH A BUILDING ACTUALLY
 CONFORM TO A HIGHER TYPE OF CONSTRUCTION.
  
 4) THE 2010 REFERENCES THE 2009 EDITION OF NFPA 101.
 THE 2012 EDITION IS SPECIFIED ON SHEET A-1.
  
 5) THE DOOR FROM THE GARAGE TO THE FOYER IS REQUIRED TO
 COMPLY WITH FBC-R 302.5.1.
  
 6) THE DOORS FROM THE GARAGE TO THE CONDITIONED STORAGE
 CLOSETS ARE REQUIRED TO COMPLY WITH FBC ENERGY
 CONSERVATION FOR THERMAL ENVELOPE REQUIREMENTS AND
 TABLE 402.1.1.
  
 7) THE GARAGE IS REQUIRED TO COMPLY WITH FBC-R 302.6
 DWELLING/GARAGE FIRE SEPARATION.
 THE GARAGE SHALL BE SEPARATED AS REQUIRED BY TABLE
 R302.6. OPENINGS IN GARAGE WALLS SHALL COMPLY WITH
 SECTION R302.5. THIS PROVISION DOES NOT APPLY TO GARAGE
 WALLS THAT ARE PERPENDICULAR TO THE ADJACENT DWELLING
 UNIT WALL.
 TABLE R302.6 DWELLING/GARAGE SEPARATION
 SEPARATION -MATERIAL
 FROM THE RESIDENCE AND ATTICS- NOT LESS THAN 1/2-INCH
 GYPSUM BOARD OR EQUIVALENT APPLIED TO THE
 GARAGE SIDE
 FROM ALL HABITABLE ROOMS ABOVE THE GARAGE - NOT LESS
 THAN 5/8-INCH TYPE X GYPSUM BOARD OR EQUIVALENT
 STRUCTURE(S) SUPPORTING FLOOR/CEILING ASSEMBLIES USED
 FOR SEPARATION REQUIRED BY THIS SECTION - NOT LESS THAN
 1/2-INCH GYPSUM BOARD OR EQUIVALENT
  
 8) SHOW COMPLIANCE WITH FBC-R806.4 UNVENTED ATTIC
 ASSEMBLIES. UNVENTED ATTIC ASSEMBLIES (SPACES BETWEEN
 THE CEILING JOISTS OF THE TOP STORY AND THE ROOF
 RAFTERS) SHALL BE PERMITTED IF ALL THE FOLLOWING
 CONDITIONS ARE MET:
 1. THE UNVENTED ATTIC SPACE IS COMPLETELY CONTAINED
 WITHIN THE BUILDING THERMAL ENVELOPE.
 2. NO INTERIOR VAPOR RETARDERS ARE INSTALLED ON THE
 CEILING SIDE (ATTIC FLOOR) OF THE UNVENTED ATTIC
 ASSEMBLY.
 3. WHERE WOOD SHINGLES OR SHAKES ARE USED, A MINIMUM
 1/4 INCH (6 MM) VENTED AIR SPACE SEPARATES THE SHINGLES
 OR SHAKES AND THE ROOFING UNDERLAYMENT ABOVE THE
 STRUCTURAL SHEATHING.
 4. EITHER ITEMS 4.1, 4.2 OR 4.3 SHALL BE MET, DEPENDING
 ON THE AIR PERMEABILITY OF THE INSULATION DIRECTLY
 UNDER THE STRUCTURAL ROOF SHEATHING.
 4.1 AIR-IMPERMEABLE INSULATION ONLY. INSULATION SHALL
 BE APPLIED IN DIRECT CONTACT WITH THE UNDERSIDE OF THE
 STRUCTURAL ROOF SHEATHING.
 4.2 AIR-PERMEABLE INSULATION ONLY. IN ADDITION TO THE
 AIR-PERMEABLE INSTALLED DIRECTLY BELOW THE STRUCTURAL
 SHEATHING, RIGID BOARD OR SHEET INSULATION SHALL BE
 INSTALLED DIRECTLY ABOVE THE STRUCTURAL ROOF SHEATHING
 AS SPECIFIED IN TABLE R806.4 FOR CONDENSATION CONTROL.
 4.3 AIR-IMPERMEABLE AND AIR-PERMEABLE INSULATION. THE
 AIR-IMPERMEABLE INSULATION SHALL BE APPLIED IN DIRECT
 CONTACT WITH THE UNDERSIDE OF THE STRUCTURAL ROOF
 SHEATHING AS SPECIFIED IN TABLE R806.4 FOR CONDENSATION
 CONTROL. THE AIR-PERMEABLE INSULATION SHALL BE
 INSTALLED DIRECTLY UNDER THE AIR-IMPERMEABLE
 INSULATION.
  
 9) SHOW COMPLIANCE WITH FBC-R807.1 ATTIC ACCESS.
 BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF CONSTRUCTION
 SHALL HAVE AN ATTIC ACCESS OPENING TO ATTIC AREAS THAT
 EXCEED 30 SQUARE FEET (2.8 M2) AND HAVE A VERTICAL
 HEIGHT OF 30 INCHES (762 MM) OR GREATER. THE VERTICAL
 HEIGHT SHALL BE MEASURED FROM THE TOP OF THE CEILING
 FRAMING MEMBERS TO THE UNDERSIDE OF THE ROOF FRAMING
 MEMBERS. THE ROUGH-FRAMED OPENING SHALL NOT BE LESS
 THAN 22 INCHES BY 30 INCHES (559 MM BY 762 MM) AND
 SHALL BE LOCATED IN A HALLWAY OR OTHER READILY
 ACCESSIBLE LOCATION. WHEN LOCATED IN A WALL, THE
 OPENING SHALL BE A MINIMUM OF 22 INCHES WIDE BY 30
 INCHES HIGH. WHEN THE ACCESS IS LOCATED IN A CEILING,
 MINIMUM UNOBSTRUCTED HEADROOM IN THE ATTIC SPACE SHALL
 BE 30 INCHES (762 MM) AT SOME POINT ABOVE THE ACCESS
 MEASURED VERTICALLY FROM THE BOTTOM OF CEILING FRAMING
 MEMBERS.
  
 10) THE OUT-SWING DOOR TO THE GARAGE IS NOT SHOWN ON
 THE WEST ELEVATION DRAWING. FBC 107.2.1
  
 11) SHOW COMPLIANCE WITH FBC-R 311.3 FOR THE REQUIRED
 LANDING ON THE EXTERIOR AT THE 3-8 X 6-8 OUT-SWING
 GARAGE DOOR.
  
 12) SPECIFY THE HEIGHT AND OPENING LIMITATIONS FOR THE
 GUARDS AT THE SECOND FLOOR COVERED PORCH AND THE
 INTERIOR STAIR WELL. FBC-R 312.2 & R312.3
  
 13) SPECIFY THE MAXIMUM RISER HEIGHT AND MINIMUM TREAD
 DEPTH FOR THE STAIRS ON THE PLANS. FBC-R 311.7.4.1 &
 311.7.4.2
  
 14) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF
 THE DIFFERENT ROOFING MATERIALS, WINDOW/GLASS TYPES,
 STRUCTURAL MULLIONS AND EXTERIOR DOOR TYPES.
 -THE FOLLOWING IS A LINK TO THE MIAMI - DADE PRODUCT
 APPROVAL WEBSITE.
 HTTP://WWW.MIAMIDADE.GOV/BUILDING/PC-SEARCH_APP.ASP
 -THE FOLLOWING IS A LINK TO THE FLORIDA PRODUCT
 APPROVAL WEBSITE.
 HTTPS://FLORIDABUILDING.ORG/PR/PR_APP_SRCH.ASPX
  
 15) THE VALUE OF THE WORK HAS BEEN INCREASED FROM
 $187,000.00 TO $356,930.00 BASED ON THE LATEST ICC
 BUILDING VALUATION DATA. FBC 109.3
  
 16) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2016-03-23 Cont ID  
Sent By albarran Date 2016-03-23 Time 18:46 Rev Time 0.00
Received By albarran Date 2016-03-23 Time 18:04 Sent To  
Notes
2016-03-23 18:48:12PASSED ELECTRICAL REVIEW WITH A NOTE OF A MISSING CO
 DETECTOR OUTSIDE OF THE MASTER BEDROOM.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2016-01-21 Cont ID  
Sent By albarran Date 2016-01-21 Time 10:35 Rev Time 0.00
Received By albarran Date 2016-01-21 Time 08:48 Sent To I
Notes
2016-01-21 10:35:44YOUR RESUBMITTAL ADDRESSING THE PREVIOUSLY MENTIONED
 DEFICIENCIES HAS ONCE AGAIN FAILED THE ELECTRICAL
 REVIEW AS INDICATED BELOW. NEW COMMENTS IF ANY PROMPTED
 BY ANOTHER REVIEW, MOST LIKELY DUE TO YOUR FAILURE TO
 SUBMIT A RESPONSE LETTER (NARRATIVE) ADDRESSING THE
 REQUIRED CORRECTIONS WILL BE NUMBERED IN CONTINUATION
 OF ANY PREVIOUS COMMENTS.
  
 THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE
 EDITION OF THE NEC, (NATIONAL ELECTRICAL CODE) AND THE
 FBC, (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF
 WEST PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL.
  
 IN A TELEPHONE CONVERSATION WITH MR. LES CZACZYK OF LCA
 I WAS PROMPTED TO ISSUE THIS WITH A PROVISO, BUT LATER
 REALIZED THAT NONE OF THE TRADES COMMENTS FROM PRIOR
 REVIEWS HAD BEEN ADDRESSED SO I DECIDED TO ISSUE THE
 NOTES FOR THE REQUIRED CORRECTIONS AS PREVIOUSLY
 MENTIONED SO THAT THE PLANS CAN ALL GET CORRECTED
 PROPERLY.
  
 1. CARBON MONOXIDE DETECTORS HAVE NOT ADDED TO THE
 PLANS. REVISE PLANS TO SHOW PROPER COVERAGE.
 2. COMMENTS 5 & 6 REFER TO LOAD CALCS AND PANEL
 SCHEDULES. THE PANEL SCHEDULE AS INDICATED ON THE
 DRAWINGS REFLECTS CIRCUITS FOR THE CONDENSING UNITS IN
 PANEL ?A? AS WELL AS MAIN FOR SAME IN THE SPLIT BUS
 EXTERIOR PANEL. BEING THAT YOU HAVE THIS ARRANGEMENT,
 LOAD CALCS WILL VARY FROM PANEL SCHEDULES. SUBMIT AS
 REQUIRED.
 3. THE PREVIOUSLY DISCUSSED MISSING INTER-SYSTEM
 BONDING TERMINAL PER NEC 250.94 HAS NOT BEEN ADDED TO
 THE SERVICED RISER.
 4. ADD A NOTE TO THE PLANS ADDRESSING THE NEC 406.8(B)
 REQUIREMENT FOR WEATHER RATED RECEPTACLES IN WET
 LOCATIONS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE
 THE CORRECTIONS ARE ON ALONG WITH THE STANDARD CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-12-01 Cont ID  
Sent By albarran Date 2015-12-01 Time 11:35 Rev Time 0.00
Received By albarran Date 2015-12-01 Time 10:26 Sent To B
Notes
2015-12-01 13:03:11HEARD BACK FROM DESIGN PROFESSIONAL AND WE CONCUR ON
 THE COMMENTS, BUT SINCE THIS HAS TO GO BACK FOR
 REVISION & CORRECTIONS LET THE ELECTRICAL PAGE BE
 CORRECTED AS WELL.
  
2015-12-01 11:33:37PLACED A PHONE CALL TO MS. DENISE CRAVY OF LCA TO
 DISCUSS THE STILL REMAINING ITEMS. IF WE CAN AGREE ON
 THEIR NEED I WILL GLADLY ISSUE WITH PROVISO. WITH THE
 EXCEPTION OF THE CO DETECTOR REQUIREMENT AND THE
 MISSING INTER-SYSTEM BONDING TERMINAL, ALL OTHER ITEMS
 HAVE BEEN SATISFACTORILY ADDRESSED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-07-22 Cont ID  
Sent By albarran Date 2015-07-22 Time 15:06 Rev Time 0.00
Received By albarran Date 2015-07-22 Time 13:35 Sent To  
Notes
2015-07-22 15:50:16PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 1. PER FBC-R 315, YOU SHALL HAVE A CO (CARBON MONOXIDE)
 DETECTOR WITHIN 10' OF EACH BEDROOM DOOR
 2. PER NEC 314.27, ALL CEILING MOUNTED LUMINAIRE
 OUTLETS SHALL BE LISTED TO SUPPORT 50 LBS.
 3. PER NEC 210.52(A)(2)(3), A FLOOR OUTLET SHALL BE
 PLACED ALONG THE FLOOR LINE OF THE STAIR RAIL ON THE
 SECOND FLOOR.
 4. PER FBC-E 404, A MINIMUM OF 50% OF PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL HAVE HIGH-EFFICIENCY
 LAMPS.
 5. PER NEC 408.4, PROVIDE AN ACCURATE AND SITE SPECIFIC
 CIRCUIT IDENTIFICATION LIST, (PANEL SCHEDULE)
 6. PER NEC 220.82, PROVIDE SITE SPECIFIC LOAD CALCS TO
 VERIFY SERVICE CAPACITY/REQUIREMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2016-06-16 Cont ID  
Sent By rmcdouga Date 2016-06-16 Time 15:33 Rev Time 0.00
Received By rmcdouga Date 2016-06-06 Time 10:28 Sent To  
Notes
2016-06-07 10:28:56ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2016-06-01 Cont ID  
Sent By rmcdouga Date 2016-06-01 Time 17:50 Rev Time 0.00
Received By rmcdouga Date 2016-05-24 Time 10:38 Sent To  
Notes
2016-05-26 10:38:51RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-05-11 Cont ID  
Sent By rmcdouga Date 2016-05-11 Time 10:51 Rev Time 0.00
Received By rmcdouga Date 2016-03-22 Time 15:22 Sent To  
Notes
2016-05-06 11:23:40RMCDOUGAL'S DESK
2016-03-22 15:22:46R29

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-01-21 Cont ID  
Sent By albarran Date 2016-01-21 Time 10:37 Rev Time 0.00
Received By albarran Date 2015-12-09 Time 14:16 Sent To  
Notes
2016-01-21 10:41:011/21/816 FAILED ELECTRICAL REVIEW AS NOTED. EMAILED
 OWNER TO ADDRESS ON PERMIT. SENT TO LARGE DENIED DRAWER
 "H". MA
2015-12-10 14:16:32R28

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-12-07 Cont ID  
Sent By rmcdouga Date 2015-12-07 Time 17:35 Rev Time 0.00
Received By rmcdouga Date 2015-10-16 Time 07:16 Sent To  
Notes
2015-10-19 07:16:45R24

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-08-04 Cont ID  
Sent By rmcdouga Date 2015-08-04 Time 18:25 Rev Time 0.00
Received By rmcdouga Date 2015-06-16 Time 13:20 Sent To  
Notes
2015-06-16 13:20:31R28

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 6 Status P Date 2016-06-16 Cont ID  
Sent By rmcdouga Date 2016-06-16 Time 15:33 Rev Time 0.00
Received By rmcdouga Date 2016-06-16 Time 15:33 Sent To  
Notes
2016-06-16 15:36:31MU 2016 - 13980 , PAID $417.24 VERIFIED BY TELEPHONE
 CALL TO WILLIE SWOOPE ON 6/16/16.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 5 Status F Date 2016-06-01 Cont ID  
Sent By rmcdouga Date 2016-06-01 Time 15:03 Rev Time 0.00
Received By rmcdouga Date 2016-06-01 Time 15:03 Sent To  
Notes
2016-06-01 15:04:26BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status F Date 2016-05-10 Cont ID  
Sent By rmcdouga Date 2016-05-10 Time 18:35 Rev Time 0.00
Received By rmcdouga Date 2016-05-10 Time 17:57 Sent To  
Notes
2016-05-10 18:35:59BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2016-01-19 Cont ID  
Sent By rmcdouga Date 2016-01-19 Time 16:42 Rev Time 0.00
Received By rmcdouga Date 2016-01-19 Time 16:42 Sent To  
Notes
2016-01-19 16:42:58BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-12-07 Cont ID  
Sent By rmcdouga Date 2015-12-07 Time 14:52 Rev Time 0.00
Received By rmcdouga Date 2015-12-07 Time 14:52 Sent To  
Notes
2015-12-07 14:52:35SEE PREVIOUS COMMENTS.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-08-03 Cont ID  
Sent By rmcdouga Date 2015-08-03 Time 18:49 Rev Time 0.00
Received By rmcdouga Date 2015-08-03 Time 18:49 Sent To  
Notes
2015-08-03 18:50:20BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2016-06-01 Cont ID  
Sent By rmcdouga Date 2016-06-01 Time 17:00 Rev Time 0.00
Received By rmcdouga Date 2016-06-01 Time 17:00 Sent To  
Notes
2016-06-01 16:07:43APPROVED WITH EXCEPTIONS
 SUBMIT TWO SETS OF CORRECTED ENERGY COMPLIANCE FORMS
 WITH THE CORRECT LOCATION(PALM BEACH COUNTY),
 ORIENTATION AND ALL INFORMATION ON THE FORMS MATCHING
 THE PLANS WITH THE SIGNATURES OF THE PREPARER AND THE
 OWNER/AGENT.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2016-05-10 Cont ID  
Sent By rmcdouga Date 2016-05-10 Time 19:00 Rev Time 0.00
Received By rmcdouga Date 2016-05-10 Time 17:57 Sent To  
Notes
2016-05-10 19:00:08PLAN
 REVIEW COMMENTS
  
 4TH REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SOME OF THE INFORMATION LISTED IN THE ENERGY
 COMPLIANCE FORMS IS INCORRECT OR MISSING. THE DESIGN
 LOCATION ON THE FORMS IS LISTED AS FORT LAUDERDALE AND
 THE PROJECT IS IN WEST PALM BEACH FL IN PALM BEACH
 COUNTY. THE SECOND FLOOR 2 X 6 WOOD FRAME WALLS ARE NOT
 LISTED. ONLY ONE WATER HEATER IS LISTED ON THE FORMS
 AND TWO ARE SHOWN ON THE PLANS (ONE ON EACH FLOOR). THE
 INSULATED ADJACENT WOOD FRAME WALLS BETWEEN THE GARAGE
 AND THE CONDITIONED SPACE IS NOT LISTED. THE RAISED
 FLOOR OF THE MASTER BED ROOM AREA ABOVE THE GARAGE IS
 NOT LISTED ON THE ENERGY FORMS. THE INSULATION IN THE
 CEILING OF THE FIRST FLOOR BEDROOM THAT IS BELOW THE
 SECOND FLOOR COVERED PORCH DOES NOT APPEAR TO BE
 INCLUDED ON THE FORMS. FBC ENERGY CONSERVATION SEC.
 R405
  
 2) THE ENERGY FORM 405-10 IS REQUIRED TO BE SIGNED AND
 DATED BY THE OWNER/AGENT. FBC ENERGY CONSERVATION
 SECTION R405.
  
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-01-19 Cont ID  
Sent By rmcdouga Date 2016-01-19 Time 16:11 Rev Time 0.00
Received By rmcdouga Date 2016-01-19 Time 16:11 Sent To  
Notes
2016-01-19 16:13:14PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW: (SAME COMMENTS AS
 LAST REVIEW. COMMENTS HAVE NOT BEEN ADDRESSED.)
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. THE PRINTED
 NAME, SIGNATURE AND LICENSE NUMBER OF THE SYSTEM
 DESIGNER IS REQUIRED ON THE MECHANICAL DRAWINGS.
  
 2) FBC-R - M 1602.4 PROVIDE BALANCED AIR RETURN AT
 BEDROOMS. TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING
 THE RETURN TRANSFER 1-1/2 TIMES THE CROSS SECTIONAL
 AREA (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE
 ROOM OR SPACE IT IS SERVING AND THE DOOR HAVING AT
 LEAST AN UNRESTRICTED 1 INCH UNDERCUT TO ACHIEVE PROPER
 RETURN AIR BALANCE. THERE IS NO RETURN SHOWN FOR THE
 FIRST FLOOR MASTER BEDROOM AND THE TRANSFER DUCT FOR
 BEDROOM #2 IS NOT 1-1/2 TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM.
 THE TRANSFER DUCT FOR THE SECOND FLOOR MASTER BEDROOM
 IS NOT 1-1/2 TIMES THE CROSS SECTIONAL AREA (SQUARE
 INCHES) OF THE 12" SUPPLY DUCT SUPPLYING THE MASTER
 SUITE ( ALL SUPPLY AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED ).
  
 3) SOME OF THE INFORMATION LISTED IN THE ENERGY
 COMPLIANCE FORMS IS INCORRECT OR MISSING. THERE ARE 5
 BEDROOMS LISTED ON THE FORMS/SIZING CALCULATIONS AND
 ONLY 4 BEDROOMS ARE SHOWN ON THE PLANS. ONLY ONE WATER
 HEATER IS LISTED ON THE FORMS AND TWO ARE SHOWN ON THE
 PLANS (ONE ON EACH FLOOR). THE INSULATED WALLS AND
 FLOOR/CEILING ASSEMBLY ADJACENT TO THE GARAGE ARE NOT
 LISTED ON THE ENERGY FORMS. THE INSULATION IN THE
 CEILING OF THE FIRST FLOOR BEDROOM THAT IS BELOW THE
 SECOND FLOOR COVERED PORCH DOES NOT APPEAR TO BE
 INCLUDED ON THE FORMS. FBC ENERGY CONSERVATION SEC.
 R405
  
 4) THE ENERGY FORM 405-10 IS REQUIRED TO BE SIGNED AND
 DATED BY THE OWNER/AGENT. FBC ENERGY CONSERVATION
 SECTION R405.
  
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-12-07 Cont ID  
Sent By rmcdouga Date 2015-12-07 Time 17:35 Rev Time 0.00
Received By rmcdouga Date 2015-12-07 Time 17:10 Sent To  
Notes
2015-12-07 17:10:31PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. THE PRINTED
 NAME, SIGNATURE AND LICENSE NUMBER OF THE SYSTEM
 DESIGNER IS REQUIRED ON THE MECHANICAL DRAWINGS.
  
 2) FBC-R - M 1602.4 PROVIDE BALANCED AIR RETURN AT
 BEDROOMS. TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING
 THE RETURN TRANSFER 1-1/2 TIMES THE CROSS SECTIONAL
 AREA (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE
 ROOM OR SPACE IT IS SERVING AND THE DOOR HAVING AT
 LEAST AN UNRESTRICTED 1 INCH UNDERCUT TO ACHIEVE PROPER
 RETURN AIR BALANCE. THERE IS NO RETURN SHOWN FOR THE
 FIRST FLOOR MASTER BEDROOM AND THE TRANSFER DUCT FOR
 BEDROOM #2 IS NOT 1-1/2 TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM.
 THE TRANSFER DUCT FOR THE SECOND FLOOR MASTER BEDROOM
 IS NOT 1-1/2 TIMES THE CROSS SECTIONAL AREA (SQUARE
 INCHES) OF THE 12" SUPPLY DUCT SUPPLYING THE MASTER
 SUITE ( ALL SUPPLY AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED ).
  
 3) SOME OF THE INFORMATION LISTED IN THE ENERGY
 COMPLIANCE FORMS IS INCORRECT OR MISSING. THERE ARE 5
 BEDROOMS LISTED ON THE FORMS/SIZING CALCULATIONS AND
 ONLY 4 BEDROOMS ARE SHOWN ON THE PLANS. ONLY ONE WATER
 HEATER IS LISTED ON THE FORMS AND TWO ARE SHOWN ON THE
 PLANS (ONE ON EACH FLOOR). THE INSULATED WALLS AND
 FLOOR/CEILING ASSEMBLY ADJACENT TO THE GARAGE ARE NOT
 LISTED ON THE ENERGY FORMS. THE INSULATION IN THE
 CEILING OF THE FIRST FLOOR BEDROOM THAT IS BELOW THE
 SECOND FLOOR COVERED PORCH DOES NOT APPEAR TO BE
 INCLUDED ON THE FORMS. FBC ENERGY CONSERVATION SEC.
 R405
  
 4) THE ENERGY FORM 405-10 IS REQUIRED TO BE SIGNED AND
 DATED BY THE OWNER/AGENT. FBC ENERGY CONSERVATION
 SECTION R405.
  
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-08-04 Cont ID  
Sent By rmcdouga Date 2015-08-04 Time 11:29 Rev Time 0.00
Received By rmcdouga Date 2015-08-04 Time 07:54 Sent To  
Notes
2015-08-04 09:00:33PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. THE PRINTED
 NAME, SIGNATURE AND LICENSE NUMBER OF THE SYSTEM
 DESIGNER IS REQUIRED ON THE MECHANICAL DRAWINGS.
  
 2) FBC-R - M 1602.4 PROVIDE BALANCED AIR RETURN AT
 BEDROOMS. TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING
 THE RETURN TRANSFER 1-1/2 TIMES THE CROSS SECTIONAL
 AREA (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE
 ROOM OR SPACE IT IS SERVING AND THE DOOR HAVING AT
 LEAST AN UNRESTRICTED 1 INCH UNDERCUT TO ACHIEVE PROPER
 RETURN AIR BALANCE. THERE IS NO RETURN SHOWN FOR THE
 FIRST FLOOR MASTER BEDROOM AND THE TRANSFER DUCT FOR
 BEDROOM #2 IS NOT 1-1/2 TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM.
 THE TRANSFER DUCT FOR THE SECOND FLOOR MASTER BEDROOM
 IS NOT 1-1/2 TIMES THE CROSS SECTIONAL AREA (SQUARE
 INCHES) OF THE 12" SUPPLY DUCT SUPPLYING THE MASTER
 SUITE ( ALL SUPPLY AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED ).
  
 3) SOME OF THE INFORMATION LISTED IN THE ENERGY
 COMPLIANCE FORMS IS INCORRECT OR MISSING. THERE ARE 5
 BEDROOMS LISTED ON THE FORMS/SIZING CALCULATIONS AND
 ONLY 4 BEDROOMS ARE SHOWN ON THE PLANS. ONLY ONE WATER
 HEATER IS LISTED ON THE FORMS AND TWO ARE SHOWN ON THE
 PLANS (ONE ON EACH FLOOR). THE INSULATED WALLS AND
 FLOOR/CEILING ASSEMBLY ADJACENT TO THE GARAGE ARE NOT
 LISTED ON THE ENERGY FORMS. THE INSULATION IN THE
 CEILING OF THE FIRST FLOOR BEDROOM THAT IS BELOW THE
 SECOND FLOOR COVERED PORCH DOES NOT APPEAR TO BE
 INCLUDED ON THE FORMS. FBC ENERGY CONSERVATION SEC. 405
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-12-14 Cont ID  
Sent By gjohnson Date 2015-12-14 Time 15:52 Rev Time 0.00
Received By gjohnson Date 2015-12-14 Time 15:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-10-22 Cont ID  
Sent By gjohnson Date 2015-10-22 Time 17:09 Rev Time 0.00
Received By gjohnson Date 2015-10-22 Time 17:08 Sent To  
Notes
2015-10-22 17:15:04 
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
  
 1.PLANS NOT SIGNED BY DESIGN PROFESSIONAL.
 PER WPB AMEND. TO FBC SEC 107.2.1

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-07-12 Cont ID  
Sent By tklarge Date 2015-07-12 Time 05:48 Rev Time 0.00
Received By tklarge Date 2015-07-12 Time 05:34 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2016-06-01 Cont ID  
Sent By rmcdouga Date 2016-06-01 Time 17:07 Rev Time 0.00
Received By rmcdouga Date 2016-06-01 Time 17:07 Sent To  
Notes
2016-06-01 17:23:07ROOFING MATERIALS
  
 - GAF ASPHALT SHINGLES NOA NO.14-1022.20
 - CERTAINTEED MODIFIED BITUMEN ROOFING OVER WOOD DECKS
 NOA NO.14-0529.02 (PAGE 36)
 - US PLY APP MODIFIED BITUMEN ROOFING OVER WOOD DECKS
 NOA NO. 10-1123.05 **(REQUIRES SIGNED AND SEALED RAS
 117 CALCULATIONS)

Review Stop Z ZONING
Rev No 4 Status P Date 2016-04-20 Cont ID  
Sent By ajones Date 2016-04-20 Time 14:15 Rev Time 0.00
Received By ajones Date 2016-04-20 Time 14:15 Sent To  
Notes
2016-05-06 11:23:56RMCDOUGAL'S DESK

Review Stop Z ZONING
Rev No 3 Status F Date 2015-12-17 Cont ID  
Sent By sgraham Date 2015-12-17 Time 11:00 Rev Time 0.00
Received By sgraham Date 2015-12-17 Time 11:00 Sent To  
Notes
2015-12-17 11:02:4412/17/15 ZONING FAILED
  
 1. THIS ZONING DISTRICT IS SINGLE FAMILY 7, WHCIH MEANS
 ONE FAMILY, YOU CAN NOT LABEL THE FIRST FLOOR AS
 MOTHER-IN-LAWS QUARTERS, NO DOORS TO LIVING ROOM ON 1ST
 FLOOR AND 2ND FLOOR THIS HOUSE IS NOT A
 DUPLEX.

Review Stop Z ZONING
Rev No 2 Status F Date 2015-10-22 Cont ID  
Sent By sgraham Date 2015-10-22 Time 16:16 Rev Time 0.00
Received By sgraham Date 2015-10-22 Time 16:16 Sent To  
Notes
2015-10-22 16:18:4210/22/15 ZONING FAILED 2ND CHECKLILST
  
 1. THIS IS SF7 ZONING, CAN NOT HAVE TWO UNITS, REMOVE
 DOOR AT STAIRS, REMOVE DOOR HEADING IN LIVING ROOM ON
 THE FIRST FLOOR AND REMOVE KITCHENETTE.

Review Stop Z ZONING
Rev No 1 Status F Date 2015-06-24 Cont ID  
Sent By sgraham Date 2015-06-24 Time 09:52 Rev Time 0.00
Received By sgraham Date 2015-06-24 Time 09:52 Sent To  
Notes
2015-06-24 09:55:196/24/15 ZONING FAILED
  
 1. HOUSE LOCATION NOT MEETING THE SIDE SETBACKS OF A
 TOTAL OF 15' FEET.
 2. THE ZONING FOR THIS ADDRESS IS SF7, MEANING ONE
 FAMILY HOUSE WITH ONE KITCHEN, ONE OF THE KITCHEN MUST
 BE REMOVED, YOU CAN NOT HAVE A TWO FAMILY RESIDENT AT
 THIS ADDRESS.