| Plan Review Stops For Permit 15060686 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2016-06-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-06-01 |
Time |
17:23 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-06-01 |
Time |
10:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2016-05-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-05-11 |
Time |
10:26 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-05-10 |
Time |
17:57 |
Sent To |
|
|
| Notes |
| 2016-05-11 10:26:49 | PLAN | | | REVIEW COMMENTS | | | | | | 4TH REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 | | | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT | | | APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION | | | INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR THE | | | STRUCTURAL WINDOW MULLIONS. | | | | | | 2) THE PRODUCT APPROVALS FOR THE MODIFIED ROOFING FOR | | | THE SECOND FLOOR COVERED PATIO IS FOR USE OVER | | | CEMENTITIOUS WOOD FIBER AND THE PLANS INDICATE THIS AS | | | A CDX PLYWOOD DECK. SUBMIT PRODUCT APPROVAL FOR WOOD | | | DECK. SIGNED AND SEALED RAS 117 CALCULATIONS WILL ALSO | | | BE REQUIRED IF THE DESIGN UPLIFT PRESSURE OF THE | | | ASSEMBLY REQUIRES ENHANCED FASTENING IN THE PERIMETER | | | AND CORNER AREAS. | | | | | | 3) BOTH SETS OF PLANS ARE MISSING THE STRUCTURAL SHEETS | | | A.7, A.8 AND A.9. FBC 107.1 | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2016-01-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-01-19 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-01-19 |
Time |
16:14 |
Sent To |
E |
|
| Notes |
| 2016-01-19 16:19:02 | PLAN | | | REVIEW COMMENTS | | | | | | 3RD REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 | | | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT | | | APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION | | | INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF | | | THE HOP MOPPED 90 LB ROOFING FOR THE BALCONY, THE HARDI | | | PLANK SIDING, THE WINDOWS /GLASS TYPES, STRUCTURAL | | | MULLIONS, THE SECTIONAL GARAGE DOOR AND ALL EXTERIOR | | | DOOR TYPES THAT WILL BE INSTALLED. | | | | | | 2) THE PRODUCT APPROVALS FOR THE GAF ASPHALT ROOF | | | SHINGLES (NOA NO. 14-1022.20) ARE REQUIRED TO BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD FOR THE PROJECT. FBC 107.3.4.1 | | | | | | 3) THE ENERGY FORMS ARE REQUIRED TO BE SIGNED AND DATED | | | BY THE OWNER/AGENT. SEE MECHANICAL COMMENTS. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2015-12-07 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-12-07 |
Time |
16:53 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-12-07 |
Time |
15:52 |
Sent To |
|
|
| Notes |
| 2015-12-07 16:48:08 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 | | | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT | | | APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION | | | INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF | | | THE HOP MOPPED 90 LB ROOFING FOR THE BALCONY, THE HARDI | | | PLANK SIDING, THE WINDOWS /GLASS TYPES, STRUCTURAL | | | MULLIONS, THE SECTIONAL GARAGE DOOR AND ALL EXTERIOR | | | DOOR TYPES THAT WILL BE INSTALLED. | | | | | | 2) THE PRODUCT APPROVALS FOR THE GAF ASPHALT ROOF | | | SHINGLES (NOA NO. 14-1022.20) ARE REQUIRED TO BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD FOR THE PROJECT. FBC 107.3.4.1 | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2015-08-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-08-04 |
Time |
18:25 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-08-03 |
Time |
18:49 |
Sent To |
|
|
| Notes |
| 2015-08-04 14:58:37 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | THESE PLANS HAVE BEEN REVIEWED AS A SINGLE FAMILY | | | RESIDENCE. ADDITIONAL COMMENTS WILL RESULT IF THIS IS | | | MEANT TO BE A TWO FAMILY DWELLING. | | | | | | 1) PROVIDE A DRAINAGE PLAN THAT SHOWS COMPLIANCE WITH | | | R401.3. | | | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER | | | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT | | | DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN | | | SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE | | | SHALL FALL A MINIMUM OF 6 INCHES (152 MM)WITHIN THE | | | FIRST 10 FEET (3048 MM). | | | EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER | | | PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL | | | WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE | | | CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE. | | | IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE | | | BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2 | | | PERCENT AWAY FROM THE BUILDING. | | | | | | 2) THE OCCUPANCY TYPE FOR ONE AND TWO FAMILY DWELLINGS | | | IS R-3, NOT R-2 AS SPECIFIED ON SHEET A-1. FBC 310.1 | | | | | | 3) THE MINIMUM CONSTRUCTION TYPE FOR THIS STRUCTURE IS | | | TYPE V-B. THE SECOND FLOOR EXTERIOR WALLS ARE WOOD | | | FRAME, THEREFORE IT IS NOT TYPE II CONSTRUCTION PER FBC | | | 602.2. | | | 602.1.1 MINIMUM REQUIREMENTS. A BUILDING OR PORTION | | | THEREOF SHALL NOT BE REQUIRED TO CONFORM TO THE DETAILS | | | OF A TYPE OF CONSTRUCTION HIGHER THAN THAT TYPE WHICH | | | MEETS THE MINIMUM REQUIREMENTS BASED ON OCCUPANCY EVEN | | | THOUGH CERTAIN FEATURES OF SUCH A BUILDING ACTUALLY | | | CONFORM TO A HIGHER TYPE OF CONSTRUCTION. | | | | | | 4) THE 2010 REFERENCES THE 2009 EDITION OF NFPA 101. | | | THE 2012 EDITION IS SPECIFIED ON SHEET A-1. | | | | | | 5) THE DOOR FROM THE GARAGE TO THE FOYER IS REQUIRED TO | | | COMPLY WITH FBC-R 302.5.1. | | | | | | 6) THE DOORS FROM THE GARAGE TO THE CONDITIONED STORAGE | | | CLOSETS ARE REQUIRED TO COMPLY WITH FBC ENERGY | | | CONSERVATION FOR THERMAL ENVELOPE REQUIREMENTS AND | | | TABLE 402.1.1. | | | | | | 7) THE GARAGE IS REQUIRED TO COMPLY WITH FBC-R 302.6 | | | DWELLING/GARAGE FIRE SEPARATION. | | | THE GARAGE SHALL BE SEPARATED AS REQUIRED BY TABLE | | | R302.6. OPENINGS IN GARAGE WALLS SHALL COMPLY WITH | | | SECTION R302.5. THIS PROVISION DOES NOT APPLY TO GARAGE | | | WALLS THAT ARE PERPENDICULAR TO THE ADJACENT DWELLING | | | UNIT WALL. | | | TABLE R302.6 DWELLING/GARAGE SEPARATION | | | SEPARATION -MATERIAL | | | FROM THE RESIDENCE AND ATTICS- NOT LESS THAN 1/2-INCH | | | GYPSUM BOARD OR EQUIVALENT APPLIED TO THE | | | GARAGE SIDE | | | FROM ALL HABITABLE ROOMS ABOVE THE GARAGE - NOT LESS | | | THAN 5/8-INCH TYPE X GYPSUM BOARD OR EQUIVALENT | | | STRUCTURE(S) SUPPORTING FLOOR/CEILING ASSEMBLIES USED | | | FOR SEPARATION REQUIRED BY THIS SECTION - NOT LESS THAN | | | 1/2-INCH GYPSUM BOARD OR EQUIVALENT | | | | | | 8) SHOW COMPLIANCE WITH FBC-R806.4 UNVENTED ATTIC | | | ASSEMBLIES. UNVENTED ATTIC ASSEMBLIES (SPACES BETWEEN | | | THE CEILING JOISTS OF THE TOP STORY AND THE ROOF | | | RAFTERS) SHALL BE PERMITTED IF ALL THE FOLLOWING | | | CONDITIONS ARE MET: | | | 1. THE UNVENTED ATTIC SPACE IS COMPLETELY CONTAINED | | | WITHIN THE BUILDING THERMAL ENVELOPE. | | | 2. NO INTERIOR VAPOR RETARDERS ARE INSTALLED ON THE | | | CEILING SIDE (ATTIC FLOOR) OF THE UNVENTED ATTIC | | | ASSEMBLY. | | | 3. WHERE WOOD SHINGLES OR SHAKES ARE USED, A MINIMUM | | | 1/4 INCH (6 MM) VENTED AIR SPACE SEPARATES THE SHINGLES | | | OR SHAKES AND THE ROOFING UNDERLAYMENT ABOVE THE | | | STRUCTURAL SHEATHING. | | | 4. EITHER ITEMS 4.1, 4.2 OR 4.3 SHALL BE MET, DEPENDING | | | ON THE AIR PERMEABILITY OF THE INSULATION DIRECTLY | | | UNDER THE STRUCTURAL ROOF SHEATHING. | | | 4.1 AIR-IMPERMEABLE INSULATION ONLY. INSULATION SHALL | | | BE APPLIED IN DIRECT CONTACT WITH THE UNDERSIDE OF THE | | | STRUCTURAL ROOF SHEATHING. | | | 4.2 AIR-PERMEABLE INSULATION ONLY. IN ADDITION TO THE | | | AIR-PERMEABLE INSTALLED DIRECTLY BELOW THE STRUCTURAL | | | SHEATHING, RIGID BOARD OR SHEET INSULATION SHALL BE | | | INSTALLED DIRECTLY ABOVE THE STRUCTURAL ROOF SHEATHING | | | AS SPECIFIED IN TABLE R806.4 FOR CONDENSATION CONTROL. | | | 4.3 AIR-IMPERMEABLE AND AIR-PERMEABLE INSULATION. THE | | | AIR-IMPERMEABLE INSULATION SHALL BE APPLIED IN DIRECT | | | CONTACT WITH THE UNDERSIDE OF THE STRUCTURAL ROOF | | | SHEATHING AS SPECIFIED IN TABLE R806.4 FOR CONDENSATION | | | CONTROL. THE AIR-PERMEABLE INSULATION SHALL BE | | | INSTALLED DIRECTLY UNDER THE AIR-IMPERMEABLE | | | INSULATION. | | | | | | 9) SHOW COMPLIANCE WITH FBC-R807.1 ATTIC ACCESS. | | | BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF CONSTRUCTION | | | SHALL HAVE AN ATTIC ACCESS OPENING TO ATTIC AREAS THAT | | | EXCEED 30 SQUARE FEET (2.8 M2) AND HAVE A VERTICAL | | | HEIGHT OF 30 INCHES (762 MM) OR GREATER. THE VERTICAL | | | HEIGHT SHALL BE MEASURED FROM THE TOP OF THE CEILING | | | FRAMING MEMBERS TO THE UNDERSIDE OF THE ROOF FRAMING | | | MEMBERS. THE ROUGH-FRAMED OPENING SHALL NOT BE LESS | | | THAN 22 INCHES BY 30 INCHES (559 MM BY 762 MM) AND | | | SHALL BE LOCATED IN A HALLWAY OR OTHER READILY | | | ACCESSIBLE LOCATION. WHEN LOCATED IN A WALL, THE | | | OPENING SHALL BE A MINIMUM OF 22 INCHES WIDE BY 30 | | | INCHES HIGH. WHEN THE ACCESS IS LOCATED IN A CEILING, | | | MINIMUM UNOBSTRUCTED HEADROOM IN THE ATTIC SPACE SHALL | | | BE 30 INCHES (762 MM) AT SOME POINT ABOVE THE ACCESS | | | MEASURED VERTICALLY FROM THE BOTTOM OF CEILING FRAMING | | | MEMBERS. | | | | | | 10) THE OUT-SWING DOOR TO THE GARAGE IS NOT SHOWN ON | | | THE WEST ELEVATION DRAWING. FBC 107.2.1 | | | | | | 11) SHOW COMPLIANCE WITH FBC-R 311.3 FOR THE REQUIRED | | | LANDING ON THE EXTERIOR AT THE 3-8 X 6-8 OUT-SWING | | | GARAGE DOOR. | | | | | | 12) SPECIFY THE HEIGHT AND OPENING LIMITATIONS FOR THE | | | GUARDS AT THE SECOND FLOOR COVERED PORCH AND THE | | | INTERIOR STAIR WELL. FBC-R 312.2 & R312.3 | | | | | | 13) SPECIFY THE MAXIMUM RISER HEIGHT AND MINIMUM TREAD | | | DEPTH FOR THE STAIRS ON THE PLANS. FBC-R 311.7.4.1 & | | | 311.7.4.2 | | | | | | 14) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 | | | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT | | | APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION | | | INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF | | | THE DIFFERENT ROOFING MATERIALS, WINDOW/GLASS TYPES, | | | STRUCTURAL MULLIONS AND EXTERIOR DOOR TYPES. | | | -THE FOLLOWING IS A LINK TO THE MIAMI - DADE PRODUCT | | | APPROVAL WEBSITE. | | | HTTP://WWW.MIAMIDADE.GOV/BUILDING/PC-SEARCH_APP.ASP | | | -THE FOLLOWING IS A LINK TO THE FLORIDA PRODUCT | | | APPROVAL WEBSITE. | | | HTTPS://FLORIDABUILDING.ORG/PR/PR_APP_SRCH.ASPX | | | | | | 15) THE VALUE OF THE WORK HAS BEEN INCREASED FROM | | | $187,000.00 TO $356,930.00 BASED ON THE LATEST ICC | | | BUILDING VALUATION DATA. FBC 109.3 | | | | | | 16) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE | | | CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER | | | INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN | | | ADDRESSED. | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2016-03-23 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2016-03-23 |
Time |
18:46 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2016-03-23 |
Time |
18:04 |
Sent To |
|
|
| Notes |
| 2016-03-23 18:48:12 | PASSED ELECTRICAL REVIEW WITH A NOTE OF A MISSING CO | | | DETECTOR OUTSIDE OF THE MASTER BEDROOM. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2016-01-21 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2016-01-21 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2016-01-21 |
Time |
08:48 |
Sent To |
I |
|
| Notes |
| 2016-01-21 10:35:44 | YOUR RESUBMITTAL ADDRESSING THE PREVIOUSLY MENTIONED | | | DEFICIENCIES HAS ONCE AGAIN FAILED THE ELECTRICAL | | | REVIEW AS INDICATED BELOW. NEW COMMENTS IF ANY PROMPTED | | | BY ANOTHER REVIEW, MOST LIKELY DUE TO YOUR FAILURE TO | | | SUBMIT A RESPONSE LETTER (NARRATIVE) ADDRESSING THE | | | REQUIRED CORRECTIONS WILL BE NUMBERED IN CONTINUATION | | | OF ANY PREVIOUS COMMENTS. | | | | | | THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE | | | EDITION OF THE NEC, (NATIONAL ELECTRICAL CODE) AND THE | | | FBC, (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF | | | WEST PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF | | | SUBMITTAL. | | | | | | IN A TELEPHONE CONVERSATION WITH MR. LES CZACZYK OF LCA | | | I WAS PROMPTED TO ISSUE THIS WITH A PROVISO, BUT LATER | | | REALIZED THAT NONE OF THE TRADES COMMENTS FROM PRIOR | | | REVIEWS HAD BEEN ADDRESSED SO I DECIDED TO ISSUE THE | | | NOTES FOR THE REQUIRED CORRECTIONS AS PREVIOUSLY | | | MENTIONED SO THAT THE PLANS CAN ALL GET CORRECTED | | | PROPERLY. | | | | | | 1. CARBON MONOXIDE DETECTORS HAVE NOT ADDED TO THE | | | PLANS. REVISE PLANS TO SHOW PROPER COVERAGE. | | | 2. COMMENTS 5 & 6 REFER TO LOAD CALCS AND PANEL | | | SCHEDULES. THE PANEL SCHEDULE AS INDICATED ON THE | | | DRAWINGS REFLECTS CIRCUITS FOR THE CONDENSING UNITS IN | | | PANEL ?A? AS WELL AS MAIN FOR SAME IN THE SPLIT BUS | | | EXTERIOR PANEL. BEING THAT YOU HAVE THIS ARRANGEMENT, | | | LOAD CALCS WILL VARY FROM PANEL SCHEDULES. SUBMIT AS | | | REQUIRED. | | | 3. THE PREVIOUSLY DISCUSSED MISSING INTER-SYSTEM | | | BONDING TERMINAL PER NEC 250.94 HAS NOT BEEN ADDED TO | | | THE SERVICED RISER. | | | 4. ADD A NOTE TO THE PLANS ADDRESSING THE NEC 406.8(B) | | | REQUIREMENT FOR WEATHER RATED RECEPTACLES IN WET | | | LOCATIONS. | | | | | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE | | | LETTER (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE | | | THE CORRECTIONS ARE ON ALONG WITH THE STANDARD CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. | | | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU, | | | MIKE ALBARRAN | | | ELECTRICAL PLANS EXAMINER | | | PH: 561-805-6746 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2015-12-01 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-12-01 |
Time |
11:35 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-12-01 |
Time |
10:26 |
Sent To |
B |
|
| Notes |
| 2015-12-01 13:03:11 | HEARD BACK FROM DESIGN PROFESSIONAL AND WE CONCUR ON | | | THE COMMENTS, BUT SINCE THIS HAS TO GO BACK FOR | | | REVISION & CORRECTIONS LET THE ELECTRICAL PAGE BE | | | CORRECTED AS WELL. | | | | | 2015-12-01 11:33:37 | PLACED A PHONE CALL TO MS. DENISE CRAVY OF LCA TO | | | DISCUSS THE STILL REMAINING ITEMS. IF WE CAN AGREE ON | | | THEIR NEED I WILL GLADLY ISSUE WITH PROVISO. WITH THE | | | EXCEPTION OF THE CO DETECTOR REQUIREMENT AND THE | | | MISSING INTER-SYSTEM BONDING TERMINAL, ALL OTHER ITEMS | | | HAVE BEEN SATISFACTORILY ADDRESSED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2015-07-22 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-07-22 |
Time |
15:06 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-07-22 |
Time |
13:35 |
Sent To |
|
|
| Notes |
| 2015-07-22 15:50:16 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE | | | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. | | | | | | 1. PER FBC-R 315, YOU SHALL HAVE A CO (CARBON MONOXIDE) | | | DETECTOR WITHIN 10' OF EACH BEDROOM DOOR | | | 2. PER NEC 314.27, ALL CEILING MOUNTED LUMINAIRE | | | OUTLETS SHALL BE LISTED TO SUPPORT 50 LBS. | | | 3. PER NEC 210.52(A)(2)(3), A FLOOR OUTLET SHALL BE | | | PLACED ALONG THE FLOOR LINE OF THE STAIR RAIL ON THE | | | SECOND FLOOR. | | | 4. PER FBC-E 404, A MINIMUM OF 50% OF PERMANENTLY | | | INSTALLED LIGHTING FIXTURES SHALL HAVE HIGH-EFFICIENCY | | | LAMPS. | | | 5. PER NEC 408.4, PROVIDE AN ACCURATE AND SITE SPECIFIC | | | CIRCUIT IDENTIFICATION LIST, (PANEL SCHEDULE) | | | 6. PER NEC 220.82, PROVIDE SITE SPECIFIC LOAD CALCS TO | | | VERIFY SERVICE CAPACITY/REQUIREMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2016-06-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-06-16 |
Time |
15:33 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-06-06 |
Time |
10:28 |
Sent To |
|
|
| Notes |
| 2016-06-07 10:28:56 | ROUTED TO RMCDOUGAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2016-06-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-06-01 |
Time |
17:50 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-05-24 |
Time |
10:38 |
Sent To |
|
|
| Notes |
| 2016-05-26 10:38:51 | RESUB ROUTED TO RMCDOUGAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2016-05-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-05-11 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-03-22 |
Time |
15:22 |
Sent To |
|
|
| Notes |
| 2016-05-06 11:23:40 | RMCDOUGAL'S DESK | | 2016-03-22 15:22:46 | R29 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2016-01-21 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2016-01-21 |
Time |
10:37 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-12-09 |
Time |
14:16 |
Sent To |
|
|
| Notes |
| 2016-01-21 10:41:01 | 1/21/816 FAILED ELECTRICAL REVIEW AS NOTED. EMAILED | | | OWNER TO ADDRESS ON PERMIT. SENT TO LARGE DENIED DRAWER | | | "H". MA | | 2015-12-10 14:16:32 | R28 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2015-12-07 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-12-07 |
Time |
17:35 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-10-16 |
Time |
07:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-08-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-08-04 |
Time |
18:25 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-06-16 |
Time |
13:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
6 |
Status |
P |
Date |
2016-06-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-06-16 |
Time |
15:33 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-06-16 |
Time |
15:33 |
Sent To |
|
|
| Notes |
| 2016-06-16 15:36:31 | MU 2016 - 13980 , PAID $417.24 VERIFIED BY TELEPHONE | | | CALL TO WILLIE SWOOPE ON 6/16/16. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
5 |
Status |
F |
Date |
2016-06-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-06-01 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-06-01 |
Time |
15:03 |
Sent To |
|
|
| Notes |
| 2016-06-01 15:04:26 | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES | | | MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE | | | SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM | | | BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH | | | THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT | | | MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE | | | THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL | | | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
4 |
Status |
F |
Date |
2016-05-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-05-10 |
Time |
18:35 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-05-10 |
Time |
17:57 |
Sent To |
|
|
| Notes |
| 2016-05-10 18:35:59 | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES | | | MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE | | | SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM | | | BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH | | | THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT | | | MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE | | | THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL | | | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
F |
Date |
2016-01-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-01-19 |
Time |
16:42 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-01-19 |
Time |
16:42 |
Sent To |
|
|
| Notes |
| 2016-01-19 16:42:58 | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES | | | MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE | | | SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM | | | BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH | | | THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT | | | MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE | | | THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL | | | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2015-12-07 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-12-07 |
Time |
14:52 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-12-07 |
Time |
14:52 |
Sent To |
|
|
| Notes |
| 2015-12-07 14:52:35 | SEE PREVIOUS COMMENTS. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2015-08-03 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-08-03 |
Time |
18:49 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-08-03 |
Time |
18:49 |
Sent To |
|
|
| Notes |
| 2015-08-03 18:50:20 | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES | | | MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE | | | SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM | | | BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH | | | THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT | | | MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE | | | THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL | | | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2016-06-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-06-01 |
Time |
17:00 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-06-01 |
Time |
17:00 |
Sent To |
|
|
| Notes |
| 2016-06-01 16:07:43 | APPROVED WITH EXCEPTIONS | | | SUBMIT TWO SETS OF CORRECTED ENERGY COMPLIANCE FORMS | | | WITH THE CORRECT LOCATION(PALM BEACH COUNTY), | | | ORIENTATION AND ALL INFORMATION ON THE FORMS MATCHING | | | THE PLANS WITH THE SIGNATURES OF THE PREPARER AND THE | | | OWNER/AGENT. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2016-05-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-05-10 |
Time |
19:00 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-05-10 |
Time |
17:57 |
Sent To |
|
|
| Notes |
| 2016-05-10 19:00:08 | PLAN | | | REVIEW COMMENTS | | | | | | 4TH REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SOME OF THE INFORMATION LISTED IN THE ENERGY | | | COMPLIANCE FORMS IS INCORRECT OR MISSING. THE DESIGN | | | LOCATION ON THE FORMS IS LISTED AS FORT LAUDERDALE AND | | | THE PROJECT IS IN WEST PALM BEACH FL IN PALM BEACH | | | COUNTY. THE SECOND FLOOR 2 X 6 WOOD FRAME WALLS ARE NOT | | | LISTED. ONLY ONE WATER HEATER IS LISTED ON THE FORMS | | | AND TWO ARE SHOWN ON THE PLANS (ONE ON EACH FLOOR). THE | | | INSULATED ADJACENT WOOD FRAME WALLS BETWEEN THE GARAGE | | | AND THE CONDITIONED SPACE IS NOT LISTED. THE RAISED | | | FLOOR OF THE MASTER BED ROOM AREA ABOVE THE GARAGE IS | | | NOT LISTED ON THE ENERGY FORMS. THE INSULATION IN THE | | | CEILING OF THE FIRST FLOOR BEDROOM THAT IS BELOW THE | | | SECOND FLOOR COVERED PORCH DOES NOT APPEAR TO BE | | | INCLUDED ON THE FORMS. FBC ENERGY CONSERVATION SEC. | | | R405 | | | | | | 2) THE ENERGY FORM 405-10 IS REQUIRED TO BE SIGNED AND | | | DATED BY THE OWNER/AGENT. FBC ENERGY CONSERVATION | | | SECTION R405. | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2016-01-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-01-19 |
Time |
16:11 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-01-19 |
Time |
16:11 |
Sent To |
|
|
| Notes |
| 2016-01-19 16:13:14 | PLAN | | | REVIEW COMMENTS | | | | | | 3RD REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: (SAME COMMENTS AS | | | LAST REVIEW. COMMENTS HAVE NOT BEEN ADDRESSED.) | | | | | | 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. THE PRINTED | | | NAME, SIGNATURE AND LICENSE NUMBER OF THE SYSTEM | | | DESIGNER IS REQUIRED ON THE MECHANICAL DRAWINGS. | | | | | | 2) FBC-R - M 1602.4 PROVIDE BALANCED AIR RETURN AT | | | BEDROOMS. TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING | | | THE RETURN TRANSFER 1-1/2 TIMES THE CROSS SECTIONAL | | | AREA (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE | | | ROOM OR SPACE IT IS SERVING AND THE DOOR HAVING AT | | | LEAST AN UNRESTRICTED 1 INCH UNDERCUT TO ACHIEVE PROPER | | | RETURN AIR BALANCE. THERE IS NO RETURN SHOWN FOR THE | | | FIRST FLOOR MASTER BEDROOM AND THE TRANSFER DUCT FOR | | | BEDROOM #2 IS NOT 1-1/2 TIMES THE CROSS SECTIONAL AREA | | | (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM. | | | THE TRANSFER DUCT FOR THE SECOND FLOOR MASTER BEDROOM | | | IS NOT 1-1/2 TIMES THE CROSS SECTIONAL AREA (SQUARE | | | INCHES) OF THE 12" SUPPLY DUCT SUPPLYING THE MASTER | | | SUITE ( ALL SUPPLY AIR INTO THE MASTER SUITE SHALL BE | | | INCLUDED ). | | | | | | 3) SOME OF THE INFORMATION LISTED IN THE ENERGY | | | COMPLIANCE FORMS IS INCORRECT OR MISSING. THERE ARE 5 | | | BEDROOMS LISTED ON THE FORMS/SIZING CALCULATIONS AND | | | ONLY 4 BEDROOMS ARE SHOWN ON THE PLANS. ONLY ONE WATER | | | HEATER IS LISTED ON THE FORMS AND TWO ARE SHOWN ON THE | | | PLANS (ONE ON EACH FLOOR). THE INSULATED WALLS AND | | | FLOOR/CEILING ASSEMBLY ADJACENT TO THE GARAGE ARE NOT | | | LISTED ON THE ENERGY FORMS. THE INSULATION IN THE | | | CEILING OF THE FIRST FLOOR BEDROOM THAT IS BELOW THE | | | SECOND FLOOR COVERED PORCH DOES NOT APPEAR TO BE | | | INCLUDED ON THE FORMS. FBC ENERGY CONSERVATION SEC. | | | R405 | | | | | | 4) THE ENERGY FORM 405-10 IS REQUIRED TO BE SIGNED AND | | | DATED BY THE OWNER/AGENT. FBC ENERGY CONSERVATION | | | SECTION R405. | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2015-12-07 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-12-07 |
Time |
17:35 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-12-07 |
Time |
17:10 |
Sent To |
|
|
| Notes |
| 2015-12-07 17:10:31 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. THE PRINTED | | | NAME, SIGNATURE AND LICENSE NUMBER OF THE SYSTEM | | | DESIGNER IS REQUIRED ON THE MECHANICAL DRAWINGS. | | | | | | 2) FBC-R - M 1602.4 PROVIDE BALANCED AIR RETURN AT | | | BEDROOMS. TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING | | | THE RETURN TRANSFER 1-1/2 TIMES THE CROSS SECTIONAL | | | AREA (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE | | | ROOM OR SPACE IT IS SERVING AND THE DOOR HAVING AT | | | LEAST AN UNRESTRICTED 1 INCH UNDERCUT TO ACHIEVE PROPER | | | RETURN AIR BALANCE. THERE IS NO RETURN SHOWN FOR THE | | | FIRST FLOOR MASTER BEDROOM AND THE TRANSFER DUCT FOR | | | BEDROOM #2 IS NOT 1-1/2 TIMES THE CROSS SECTIONAL AREA | | | (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM. | | | THE TRANSFER DUCT FOR THE SECOND FLOOR MASTER BEDROOM | | | IS NOT 1-1/2 TIMES THE CROSS SECTIONAL AREA (SQUARE | | | INCHES) OF THE 12" SUPPLY DUCT SUPPLYING THE MASTER | | | SUITE ( ALL SUPPLY AIR INTO THE MASTER SUITE SHALL BE | | | INCLUDED ). | | | | | | 3) SOME OF THE INFORMATION LISTED IN THE ENERGY | | | COMPLIANCE FORMS IS INCORRECT OR MISSING. THERE ARE 5 | | | BEDROOMS LISTED ON THE FORMS/SIZING CALCULATIONS AND | | | ONLY 4 BEDROOMS ARE SHOWN ON THE PLANS. ONLY ONE WATER | | | HEATER IS LISTED ON THE FORMS AND TWO ARE SHOWN ON THE | | | PLANS (ONE ON EACH FLOOR). THE INSULATED WALLS AND | | | FLOOR/CEILING ASSEMBLY ADJACENT TO THE GARAGE ARE NOT | | | LISTED ON THE ENERGY FORMS. THE INSULATION IN THE | | | CEILING OF THE FIRST FLOOR BEDROOM THAT IS BELOW THE | | | SECOND FLOOR COVERED PORCH DOES NOT APPEAR TO BE | | | INCLUDED ON THE FORMS. FBC ENERGY CONSERVATION SEC. | | | R405 | | | | | | 4) THE ENERGY FORM 405-10 IS REQUIRED TO BE SIGNED AND | | | DATED BY THE OWNER/AGENT. FBC ENERGY CONSERVATION | | | SECTION R405. | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2015-08-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-08-04 |
Time |
11:29 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-08-04 |
Time |
07:54 |
Sent To |
|
|
| Notes |
| 2015-08-04 09:00:33 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. THE PRINTED | | | NAME, SIGNATURE AND LICENSE NUMBER OF THE SYSTEM | | | DESIGNER IS REQUIRED ON THE MECHANICAL DRAWINGS. | | | | | | 2) FBC-R - M 1602.4 PROVIDE BALANCED AIR RETURN AT | | | BEDROOMS. TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING | | | THE RETURN TRANSFER 1-1/2 TIMES THE CROSS SECTIONAL | | | AREA (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE | | | ROOM OR SPACE IT IS SERVING AND THE DOOR HAVING AT | | | LEAST AN UNRESTRICTED 1 INCH UNDERCUT TO ACHIEVE PROPER | | | RETURN AIR BALANCE. THERE IS NO RETURN SHOWN FOR THE | | | FIRST FLOOR MASTER BEDROOM AND THE TRANSFER DUCT FOR | | | BEDROOM #2 IS NOT 1-1/2 TIMES THE CROSS SECTIONAL AREA | | | (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM. | | | THE TRANSFER DUCT FOR THE SECOND FLOOR MASTER BEDROOM | | | IS NOT 1-1/2 TIMES THE CROSS SECTIONAL AREA (SQUARE | | | INCHES) OF THE 12" SUPPLY DUCT SUPPLYING THE MASTER | | | SUITE ( ALL SUPPLY AIR INTO THE MASTER SUITE SHALL BE | | | INCLUDED ). | | | | | | 3) SOME OF THE INFORMATION LISTED IN THE ENERGY | | | COMPLIANCE FORMS IS INCORRECT OR MISSING. THERE ARE 5 | | | BEDROOMS LISTED ON THE FORMS/SIZING CALCULATIONS AND | | | ONLY 4 BEDROOMS ARE SHOWN ON THE PLANS. ONLY ONE WATER | | | HEATER IS LISTED ON THE FORMS AND TWO ARE SHOWN ON THE | | | PLANS (ONE ON EACH FLOOR). THE INSULATED WALLS AND | | | FLOOR/CEILING ASSEMBLY ADJACENT TO THE GARAGE ARE NOT | | | LISTED ON THE ENERGY FORMS. THE INSULATION IN THE | | | CEILING OF THE FIRST FLOOR BEDROOM THAT IS BELOW THE | | | SECOND FLOOR COVERED PORCH DOES NOT APPEAR TO BE | | | INCLUDED ON THE FORMS. FBC ENERGY CONSERVATION SEC. 405 | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2015-12-14 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2015-12-14 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2015-12-14 |
Time |
15:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2015-10-22 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2015-10-22 |
Time |
17:09 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2015-10-22 |
Time |
17:08 |
Sent To |
|
|
| Notes |
| 2015-10-22 17:15:04 | | | | 1ST REVIEW: FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | | | | 1.PLANS NOT SIGNED BY DESIGN PROFESSIONAL. | | | PER WPB AMEND. TO FBC SEC 107.2.1 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2015-07-12 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-07-12 |
Time |
05:48 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-07-12 |
Time |
05:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2016-06-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2016-06-01 |
Time |
17:07 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2016-06-01 |
Time |
17:07 |
Sent To |
|
|
| Notes |
| 2016-06-01 17:23:07 | ROOFING MATERIALS | | | | | | - GAF ASPHALT SHINGLES NOA NO.14-1022.20 | | | - CERTAINTEED MODIFIED BITUMEN ROOFING OVER WOOD DECKS | | | NOA NO.14-0529.02 (PAGE 36) | | | - US PLY APP MODIFIED BITUMEN ROOFING OVER WOOD DECKS | | | NOA NO. 10-1123.05 **(REQUIRES SIGNED AND SEALED RAS | | | 117 CALCULATIONS) |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2016-04-20 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2016-04-20 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2016-04-20 |
Time |
14:15 |
Sent To |
|
|
| Notes |
| 2016-05-06 11:23:56 | RMCDOUGAL'S DESK |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2015-12-17 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2015-12-17 |
Time |
11:00 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2015-12-17 |
Time |
11:00 |
Sent To |
|
|
| Notes |
| 2015-12-17 11:02:44 | 12/17/15 ZONING FAILED | | | | | | 1. THIS ZONING DISTRICT IS SINGLE FAMILY 7, WHCIH MEANS | | | ONE FAMILY, YOU CAN NOT LABEL THE FIRST FLOOR AS | | | MOTHER-IN-LAWS QUARTERS, NO DOORS TO LIVING ROOM ON 1ST | | | FLOOR AND 2ND FLOOR THIS HOUSE IS NOT A | | | DUPLEX. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2015-10-22 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2015-10-22 |
Time |
16:16 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2015-10-22 |
Time |
16:16 |
Sent To |
|
|
| Notes |
| 2015-10-22 16:18:42 | 10/22/15 ZONING FAILED 2ND CHECKLILST | | | | | | 1. THIS IS SF7 ZONING, CAN NOT HAVE TWO UNITS, REMOVE | | | DOOR AT STAIRS, REMOVE DOOR HEADING IN LIVING ROOM ON | | | THE FIRST FLOOR AND REMOVE KITCHENETTE. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2015-06-24 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2015-06-24 |
Time |
09:52 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2015-06-24 |
Time |
09:52 |
Sent To |
|
|
| Notes |
| 2015-06-24 09:55:19 | 6/24/15 ZONING FAILED | | | | | | 1. HOUSE LOCATION NOT MEETING THE SIDE SETBACKS OF A | | | TOTAL OF 15' FEET. | | | 2. THE ZONING FOR THIS ADDRESS IS SF7, MEANING ONE | | | FAMILY HOUSE WITH ONE KITCHEN, ONE OF THE KITCHEN MUST | | | BE REMOVED, YOU CAN NOT HAVE A TWO FAMILY RESIDENT AT | | | THIS ADDRESS. |
|
|