Plan Review Details - Permit 15060678
| Plan Review Stops For Permit 15060678 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2015-07-22 |
|
|
Cont ID |
|
| Sent By |
aclange |
Date |
2015-07-22 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
aclange |
Date |
2015-07-22 |
Time |
16:30 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2015-08-11 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-08-11 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-08-11 |
Time |
15:36 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2015-08-06 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-08-06 |
Time |
11:30 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-08-06 |
Time |
11:14 |
Sent To |
|
|
| Notes |
| 2015-08-06 11:32:02 | I REVIEWED AND CORRECTED A PDF FOR THIS PERMIT. THE | | | CONTRACTOR WILL MAKE THE NECESSARY CORRECTIONS, PRINT | | | THE SHEETS AND RESUBMIT. VIA THE FRONT COUNTER. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2015-07-31 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-07-31 |
Time |
13:58 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-07-31 |
Time |
13:28 |
Sent To |
|
|
| Notes |
| 2015-07-31 13:58:45 | SIGN CONTRACTOR SENT ME A PDF OF THE REVISED DRAWING | | | WHICH STILL PROVED TO BE INCOMPLETE. I REVIEWED IT AND | | | GAVE HER A LIST OF REQUIRED CORRECTIONS.. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2015-07-22 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-07-22 |
Time |
18:10 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-07-22 |
Time |
17:52 |
Sent To |
I |
|
| Notes |
| 2015-07-22 18:10:31 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE | | | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO | | | THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE | | | CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. | | | 1. NEC 600.6, REQUIRES THE EACH SIGN HAVE A DISCONNECT. | | | 2. NEC 600.6(A) REQUIRES THAT THE DISCONNECT BE WITHIN | | | SIGHT OF THE SIGN. | | | 3. NEC ARTICLE 600 HAS SPECIFIC ELECTRICAL REQUIREMENTS | | | FOR SIGNS. | | | 4. FBC-E 505 HAS SPECIFIC SWITCHING REQUIREMENTS FOR | | | SIGNS. | | | | | | ALL OF THE ABOVE SHALL BE COMPLIED WITH AND REFLECTED | | | ON THE ELECTRICAL PAGE FOR THIS PERMIT APPLICATION. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2015-08-11 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-08-11 |
Time |
16:10 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-08-11 |
Time |
13:21 |
Sent To |
|
|
| Notes |
| 2015-08-11 16:13:41 | 8/11/15 - PASSED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED | | | VIA EMAIL. SENT TO SMALL READY BIN "E". MA | | 2015-08-11 13:22:04 | RESUB ROUTED TO MALBARRAN |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-07-22 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-07-22 |
Time |
18:11 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-06-16 |
Time |
11:18 |
Sent To |
|
|
| Notes |
| 2015-07-22 18:12:23 | 7/22/15 - FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR | | | NOTIFIED VIA EMAIL. SENT WITH OTHER PERMITS IN THE | | | PACKET TO SMALL DENIED BIN "E". MA | | 2015-06-23 13:47:42 | MISC 2 BOX. | | 2015-06-16 11:19:44 | TO ZONING | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2015-06-23 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2015-06-23 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2015-06-23 |
Time |
13:47 |
Sent To |
|
|
| Notes |
|
|
|